Plan Review Details - Permit 02031299
Plan Review Stops For Permit 02031299
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-04-04 Cont ID  
Sent By mcarsill Date 2002-04-04 Time 15:01 Rev Time 0.00
Received By mcarsill Date 2002-04-04 Time 15:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-03-28 Cont ID  
Sent By pkrauss Date 2002-03-27 Time 13:23 Rev Time 0.00
Received By mcarsill Date 2002-03-28 Time 12:27 Sent To  
Notes
2002-03-28 00:00:00A) PLEASE PROVIDE 3M FIREWRAP PRODUCT
 APPROVALS THAT WERE REFERENCED ON THE
 PLANS.
 B) PLEASE CLEARLY INDICATE CLEAN-OUT
 LOCATIONS ON DUCT.
 C) PLEASE SEE MECHANICAL REVIEW COMMENTS
 AND PROPERLY ADDRESS THEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-05 Cont ID  
Sent By pkrauss Date 2002-04-05 Time 13:04 Rev Time 0.35
Received By pkrauss Date 2002-04-05 Time 13:04 Sent To  
Notes
2002-04-05 00:00:00PROVISO ON PLAN - WELDS ON GREASE DUCT
 TO BE INSPECTED PRIOR TO COVERING WITH
 THE FYREWRAP.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-27 Cont ID  
Sent By pkrauss Date 2002-03-27 Time 13:23 Rev Time 0.45
Received By pkrauss Date 2002-03-27 Time 13:18 Sent To FIRE
Notes
2002-03-27 00:00:002001 FBC, MECHANICAL & NFPA 96
  
 PROVIDE MANUFACTURER SUMITTAL DATA AND
 INSTALLATION INSTRUCTIONS FOR THE 3M
 FASTWRAP.INDICATE 1 OR 2 HR RATING.
  
 INDICATE LOCATION OF CLEANOUTS ON PLAN.
  
 PLEASE NOTE, EXHAUST OUTLETS SHALL BE
 LOCATED NOT LESS THAN 10 FT
 HORIZONTALLY FROM PARTS OF THE SAME OR
 CONTIGUOUS BUILDINGS, PROPERTY LINES
 AND AIR INTAKE OPENINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.