Plan Review Details - Permit 02031269
Plan Review Stops For Permit 02031269
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-09 Cont ID  
Sent By jwitmer Date 2002-04-09 Time 16:43 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-29 Cont ID  
Sent By jwitmer Date 2002-03-29 Time 13:09 Rev Time 0.75
Received By jwitmer Date 2002-03-29 Time 13:09 Sent To  
Notes
2002-03-29 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02031269
 7880 NILE RIVER ROAD
 CONT: SCREEN ETC INC
 TEL: 439-3619
  
 FL BLDG CODE= 2001 FLORIDA BUILDING CODE
  
 1)- THE DESIGN PARAMETERS SHEET INDI-
 CATES A BASIC VELOCITY PRESSURE OF 10BLS
 TABLE 2002.4 DESIGN WIND PRESSURES FOR
 ALUMINIUM SCREEN ENCLOSURE FRAMING.
 THE TABLE FOR 140 MPH WIND SPEED INDICAT
 ES FOR A FLAT ROOF A MINIMUM OF 10 PSF
 TO BE USED.
 WALLS L/W EXPOS "B" 16 PSF TO BE USED.
  
 2) ELEVATION DETAIL DOESN'T INDICATE THE
 MANSARD, IS THERE ANY EXT SCREEN DOOR?
  
 3) DISCREPANCY BETWEEN DETAILS:
 CARRY-BEAM TO BEAM CONNECTION, IN DETAIL
 THREE BOLTS DRAWN AND THE WRITTEN EX-
 PLINATION TWO BOLTS?
  
 4)- FL BLDG CODE 2002.3.2 SCREEN DENSITY
 SHALL BE A MAXIMUM OF 20X20 MESH.
  
 5)- FL BLDG 2003.8.1.4 WELDER QUALIFICA-
 TION ALL WELDING OF STRUCTURAL MEMBERS
 SHALL BE PERFORMED BY CERTIFIED WELDERS.
  
 6)- ENCIRLE ALL DETAILS TO BE USED, IF N
 OT WELDED BOX BEAM SPLICE SHOULD BE
 ENCIRCLED.
  
 7)- ALL CONNECTION DEVISES SHALL BE
 RATED BY LOAD TESTING LAB. 2003.7.5
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-27 Cont ID  
Sent By sgraham Date 2002-03-27 Time 16:20 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***