Plan Review Stops For Permit 02031231 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-03-19 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-03-19 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-03-19 |
Time |
15:20 |
Sent To |
|
|
Notes |
2002-03-19 00:00:00 | A) IT WAS NOTED FROM THE PLANS THAT | | NO SMOKE DETECTORS EITHER ONES | | CONNECTED TO THE FIRE ALARM SYSTEM OR | | SINGLE STATION ONES WERE PRESENT IN THE | | UPSTAIR ROOMS. IT IS BELIEVED THAT | | SOME OF THE ROOMS MAY BE USED FOR | | SLEEPING PURPOSES. PLEASE BE ADVISED | | THAT NFPA 101, THE LIFE SAFETY CODE, | | 2000 EDITION, SECTION 29.3.4.5, | | EXISTING DORMITORIES AND HOTELS, | | INDICATES " AN APPROVED SINGLE-STATION | | SMOKE ALARM SHALL BE INSTALLED IN | | EVERY GUEST ROOM AND EVERY LIVING AREA | | AND SLEEPING ROOM WITHIN A GUEST SUITE". | | " THESE ALARMS SHALL NOT BE REQUIRED | | TO BE INTERCONNECTED. SINGLE STATION | | SMOKE ALARMS WITHOUT A SECONDARY POWER | | SUPPLY POWER SOURCE SHALL BE PERMITTED". | | PLEASE ADVISE THIS OFFICE IN WRITING | | HOW COMPLIANCE WITH THIS CODE SECTION | | WILL BE ACCOMPLISHED. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
|