Plan Review Details - Permit 02031203
Plan Review Stops For Permit 02031203
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-04 Cont ID  
Sent By dpalmer Date 2002-04-04 Time 12:37 Rev Time 0.00
Received By dpalmer Date 2002-04-04 Time 12:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-21 Cont ID  
Sent By btrobaug Date 2002-03-21 Time 08:54 Rev Time 0.00
Received By btrobaug Date 2002-03-21 Time 08:35 Sent To  
Notes
2002-03-21 00:00:00*****************UNSAT!*****************
 QUALITY OF DRAWING IS NOT ACCEPTABLE
 PER 104.2 AND 104.2.1.3 CITY
 AMMENDMENTS.
 PLEASE RESUBMIT WITH THE FOLLOWING
 INFORMATION:
  
 1} CLARIFY THE LOCATION OF THE NEW PANEL
 ON THE DRAWINGS TO INSURE CONFORMITY
 WITH 384-7 AND 110-26 OF THE NEC.
  
 2} INDICATE THE SIZE AND TYPE OF THE
 RACEWAY CONTAINING THE FEEDER
 CONDUCTORS TO THE NEW PANEL.
  
 3} INDCATE THE LOCATION OF THE METER TO
 INSURE CONFORMITY WITH 230-70 NEC AND
 230-70(A) OF THE CITY AMMENDMENTS.
  
 4} THE OPEN AIR SPLICES INDICATED ON
 DRAWING TO CONFORM TO 300-16 WHERE
 PRACTICABLE.
  
 5} THE RECEPTACLES SHOWN ON THE DRAWING
 INDICATING "NEW WALL W/ EXIST.OUTLETS"
 TO CONFORM TO 210-7(D).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392