Plan Review Stops For Permit 02031203 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-04-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-04-04 |
Time |
12:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-04-04 |
Time |
12:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-03-21 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-03-21 |
Time |
08:54 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-03-21 |
Time |
08:35 |
Sent To |
|
|
Notes |
2002-03-21 00:00:00 | *****************UNSAT!***************** | | QUALITY OF DRAWING IS NOT ACCEPTABLE | | PER 104.2 AND 104.2.1.3 CITY | | AMMENDMENTS. | | PLEASE RESUBMIT WITH THE FOLLOWING | | INFORMATION: | | | | 1} CLARIFY THE LOCATION OF THE NEW PANEL | | ON THE DRAWINGS TO INSURE CONFORMITY | | WITH 384-7 AND 110-26 OF THE NEC. | | | | 2} INDICATE THE SIZE AND TYPE OF THE | | RACEWAY CONTAINING THE FEEDER | | CONDUCTORS TO THE NEW PANEL. | | | | 3} INDCATE THE LOCATION OF THE METER TO | | INSURE CONFORMITY WITH 230-70 NEC AND | | 230-70(A) OF THE CITY AMMENDMENTS. | | | | 4} THE OPEN AIR SPLICES INDICATED ON | | DRAWING TO CONFORM TO 300-16 WHERE | | PRACTICABLE. | | | | 5} THE RECEPTACLES SHOWN ON THE DRAWING | | INDICATING "NEW WALL W/ EXIST.OUTLETS" | | TO CONFORM TO 210-7(D). | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT.8392 |
|
|
|