Plan Review Details - Permit 02031089
Plan Review Stops For Permit 02031089
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-06-03 Cont ID  
Sent By jgomez Date 2002-06-03 Time 12:05 Rev Time 0.25
Received By jgomez Date 2002-06-03 Time 12:05 Sent To  
Notes
2002-06-03 00:00:00PRODUCT APPROVAL SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-15 Cont ID  
Sent By pkrauss Date 2002-05-22 Time 10:23 Rev Time 1.00
Received By jgomez Date 2002-05-15 Time 10:06 Sent To  
Notes
2002-05-15 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE AO. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 2-REVISE STRUCTURAL BUCK DETAIL TO
 SATISFY THE REQUIREMENTS OF SECTION
 1704.4.4 FBC 2001. DON'T CITE THE
 SECTION REVISE DETAIL SHOWING PROPER
 INSTALLATION OF BUCK.
 3-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF TILE. ONE SUBMITTED WAS DELETED
 FROM SBCCI.
  
  
  
 NOTES:
 *DRAWINGS AND COMMENTS TO BE FILED UNDER
 PERMIT #02031089.
 *THESE COMMENTS APPLY TO PERMIT NUMBERS:
 02031089, 02031088, 02031084 AND
 02031083.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-17 Cont ID  
Sent By jgomez Date 2002-04-17 Time 13:49 Rev Time 1.50
Received By jgomez Date 2002-04-17 Time 13:49 Sent To  
Notes
2002-04-17 00:00:00CHECKLIST:
 1-DESIGN CRITERIA:
 FBC 2001 SEC. 1606.2 SHALL NOT BE USED
 TO DESIGN A "PARTIALLY ENCLOSED" BLDG.
 SEE SEC. 1606.1.4.1 FBC 2001.
 *THE ONLY DESIGN CRITERIA ACCEPTABLE
 UNDER FBC 2001 IS ASCE 7-98 METHOD 2 -
 ANALYTICAL PROCEDURE USING FIG. 6-3.
 2-TWO HR OVERHANG DETAIL FOR WD ASSEMBLY
 USING CALCULATED RATINGS IS NOT
 ACCEPTABLE. SEC. 709.6.1.2 FBC 2001.
 3-UPDATE ALL PLANS AND SPECIFICATIONS.
 SEE COMMENTS ON PLANS. PLEASE, RETURN
 REVIEWED SET TO EXPEDITE REVIEW.
 4-REVISE 2 HR FIRE RATED GLASS BLOCK
 ASSEMBLY DETAIL FOR MODEL "C". SEE UL
 LISTING FOR ASSEMBLY SPECIFICATIONS.
 5-REVISE STRUCTURAL BUCK DETAILS TO
 SATISFY REQUIREMENTS OF SEC. 1707.4.4
 FBC 2001.
 6-PROVIDE COMPLETE SPECIFICATIONS FOR
 CEILING INSTALLATION AT FRONT AND BACK
 PORCHES. SEE ASTM C1063 FOR SPECIFIC
 FASTENERS AND SPACING.
 SEC. 2504.2 FBC 2001.
 7-CLARIFY GARAGE DOOR BUCK DETAIL. SEE
 DET. 1/DS-1 AND DET. 4/S4.
 8-REVISE ENERGY CALCULATIONS:
 A)UNDER ATTIC AREA. SEE SEC. 604.1.A.1
 OF CHAPTER 13 FBC 2001.
 B)THIS IS MULTIFAMILY UNITS, NOT SINGLE
 FAMILY. ALSO SPECIFY NUMBER OF UNITS.
 9-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF TILE. REPORT SUBMITTED WAS
 DELETED FROM SBCCI LISTING.
 B)HORIZONTAL ROLLING WINDOWS WHEN USED.
 10-LOTS 27, 26, 25, AND 24 DON'T COMPLY
 WITH TABLE 600 FBC 2001 AT REAR ELEV.
 10'-0" DISTANCE FROM PROPERTY LINE
 ALLOWS 20% OPENINGS ONLY.
 11-CONCRETE SLAB SPECIFICATIONS TO ADD
 NOTE REQUIRING SUPPORTS AS REQUIRED ON
 SECTION 1909.3 FBC 2001.
 12-UPDATE ALL CONNECTORS AS REQUIRED
 WHEN SPECIFYING HUGHES OR SEMCO
 CONNECTORS. THESE COMPANIES ARE OUT OF
 BUSINESS.
  
  
  
 NOTES:
 -DRAWINGS AND NOTES TO BE FILED UNDER
 PERMIT #02031089.
 -THESE COMMENTS APPLY TO PERMIT NUMBERS:
 02031089,02031088, 02031086, 02031084
 AND 02031083.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-27 Cont ID  
Sent By btrobaug Date 2002-03-27 Time 06:48 Rev Time 0.00
Received By btrobaug Date 2002-03-27 Time 06:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-03-28 Cont ID  
Sent By mcarsill Date 2002-03-28 Time 15:47 Rev Time 0.00
Received By mcarsill Date 2002-03-28 Time 15:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-05-22 Cont ID  
Sent By pkrauss Date 2002-05-22 Time 10:16 Rev Time 0.30
Received By pkrauss Date 2002-05-22 Time 10:16 Sent To B
Notes
2002-05-22 00:00:00MECHANICAL PERMIT 02031134
 SUBMITTAL LTR FROM WHIRLPOOL ON DRYER
 CFM (LESS THAN 200).

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-05-17 Cont ID  
Sent By ndenmark Date 2002-05-17 Time 09:48 Rev Time 0.50
Received By ndenmark Date 2002-05-17 Time 09:48 Sent To  
Notes
2002-05-17 00:00:00PROVISO:
 DRYER CFM DATA SUBMITTAL REQUIRED BEFORE
 FIRST ROUGH INSPECTION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-05-13 Cont ID  
Sent By pkrauss Date 2002-05-13 Time 16:22 Rev Time 0.35
Received By pkrauss Date 2002-05-13 Time 16:22 Sent To  
Notes
2002-05-13 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 02031134
  
 OTHER COMMENTS NOT ADDRESSED FROM
 PREVIOUS REVIEW.
  
 1. SEER ON ENERGY CALCS STILL DO NOT
 MATCH SEER SHOWN ON EQUIPMENT SCHEDULE.
  
 2. O.A. CALCS. SHALL PROVIDE COMPLIANCE
 WITH 402.2 (4% OF THE FLOOR AREA BEING
 VENTILATED) OR TABLE 403.3 (MECHANICAL
 VENTILATION NOT INFILTRATION)
  
 2. DRYER CFM NOT PROVIDED.
  
 4. DRYER LENGTHS IN EXCESS OF CODE
 MINIMUM OF 25' PER 504.6. SUBMIT
 SPECIFIC MANUFACTURER SPECIFICATIONS OF
 ALLOWABLE LENGTH OF DUCT.
  
 5. SECONDARY DRAIN CONSPICUOUS POINT
 SHALL NOT BE BEHIND AHU CLOSET DOOR. IF
 NO SUITABLE CONSPICUOUS LOCATION IS
 AVAILABLE, A PAN WITH A FLOAT SWITCH PER
 307.2.4 IS ACCEPTABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-02 Cont ID  
Sent By ndenmark Date 2002-04-02 Time 14:00 Rev Time 0.33
Received By ndenmark Date 2002-04-02 Time 14:00 Sent To  
Notes
2002-04-02 00:00:00**************DENIED********************
 1. SEER ON EQUIPMENT SCHEDULE DOES NOT
 MATCH SEER ON ENERGY CALCS
 2. PROVIDE CFM INFORMATION ON DRYER TO
 DETERMINE COMPLIANCE WITH FBC(M) 504.5
 3. PROVIDE OUTSIDE AIR PER 2001 FBC(M)
 TABLE 403.3
  
 NOTE: DRYER AND BATH EXHAUST DUCT SHALL
 NOT PENETRATE RATED PARTYWALL OR
 ADJACENT ROOF

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-13 Cont ID  
Sent By kstevens Date 2002-05-13 Time 17:36 Rev Time 0.00
Received By kstevens Date 2002-05-13 Time 17:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-19 Cont ID  
Sent By kstevens Date 2002-04-19 Time 17:07 Rev Time 0.00
Received By kstevens Date 2002-04-19 Time 14:46 Sent To  
Notes
2002-04-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 1) SHT SH-1 GENERAL NOTES #6 TO READ
 FBC-2001 PLUMBING.
 2) SHT A3_MP-1 SANITARY RISER DIAGRAM,
 OPTIONAL LAUNDRY SINK TO RUN TO THE
 RIGHT OF THE BLDG. DRAIN AWAY FROM WASH
 MACHINE TO REFLECT FLOOR PLAN.
 3) SHT A3A_MP-1 WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS SHALL BE INSTALL-
 ED WHERE QUICK CLOSING VALVES ARE UTILI-
 ZED. (WASH MACHINE, DISHWASHER, ICE
 MAKER). SECTION 604.9
 4) SHT A3_MP-3 PLUMBING NOTES AND SPECS.
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL
 5) SHT A3_MP-3 WATER HEATER DETAIL. SEC
 504.7.1 THE DISCHARGE PIPE SHALL NOT
 HAVE ANY TRAPPED SECTIONS AND SHALL HAVE
 A VISIBLE AIR GAP OR AIR GAP FITTING LO-
 CATED IN THE SAME ROOM AS THE HEATER.
 6) SHT A2_MP-1 SANITARY RISER DIAGRAM.
 OPTIONAL LAUNDRY SINK TO RUN TO THE
 RIGHT OF THE BLDG. DRAIN AWAY FROM WASH
 MACHINE TO REFLECT FLOOR PLAN.
 7) SHT A2_MP-1 WATER RISER DIAGRAM.
 WATER HAMMER ARRESTORS SHALL BE INSTALL-
 ED WHERE QUICK CLOSING VALVES AR UTILI-
 ZED. (WASH MACHINES, DISHWASHERS, ICE
 MAKERS.) SECTION 604.9
 8) SHT A_MP-3 PLUMBING NOTES AND SPECS.
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 9) SHT A_MP-3 WATER HEATER DETAIL. THE
 DISCHARGE PIPE SHALL NOT HAVE ANY TRAPP-
 ED SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING LOCATED IN THE
 SAME ROOM AS THE HEATER.
 10) SHT A1_MP-1 SANITARY RISER DIAGRAM,
 OPTIONAL LAUNDRY SINK TO RUN TO THE
 RIGHT OF THE BLDG. DRAIN AWAY FROM WASH
 MACHINE TO REFLECT FLOOR PLAN.
 11) SHT A1_MP-1 WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS SHALL BE INSTALL-
 ED WHERE QUICK CLOSING VALVES ARE UTILI-
 ZED. (WASH MACHINE, DISHWASHER, ICE
 MAKER) SECTION 604.9
 12) SHT A1_MP-3 PLUMBING NOTES AND SPECS
 NOTE #1(B)TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 13) SHT A1_MP-3 WATER HEATER DETAIL. THE
 DISCHARGE PIPE SHALL NOT HAVE ANY TRAPP-
 ED SECTIONS AND SHALL HAVE A VISIBLE AIR
 GAP OR AIR GAP FITTING LOCATED IN THE
 SAME ROOM AS THE WATER HEATER. SECTION
 504.7.1 (RELIEF VALVES - P/T)
 14) SHT B_MP-1 WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS SHALL BE INSTALL-
 ED WHERE QUICK CLOSING VALVES ARE UTILI-
 ZED. (WASH MACHINE, DISHWASHER, ICE
 MAKER) SECTION 604.9
 15) SHT B_MP-4 PLUMBING NOTES AND SPECS.
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 16) SHT B_MP-4 WATER HEATER DETAIL. RE-
 LIEF VENT - THE DISCHARGE PIPE SHALL NOT
 HAVE ANY TRAPPED SECTIONS AND SHALL HAVE
 A VISIBLE AIR GAP OR A AIR GAP FITTING
 LOCATED IN THE SAME ROOM AS THE HEATER.
 SECTION 504.7.1.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-21 Cont ID  
Sent By sgraham Date 2002-03-21 Time 11:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***