Plan Review Stops For Permit 02031081 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-03-25 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-03-25 |
Time |
09:34 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-03-25 |
Time |
09:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-03-18 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-03-18 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-03-18 |
Time |
14:13 |
Sent To |
|
|
Notes |
2002-03-18 00:00:00 | NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | PLEASE INDICATE THE SIZE OF THE OVER | | CURRENT PROTECTION FOR THE#3 FEEDERS | | TO THE INDOOR PANEL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT.8392 |
|
|
|