Plan Review Details - Permit 02031078
Plan Review Stops For Permit 02031078 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-05-15 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2002-05-15 |
Time |
18:51 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2002-05-15 |
Time |
18:51 |
Sent To |
|
|
Notes |
2002-05-15 00:00:00 | APPROVED WITH PROVISO: SEE COMMENTS ON | | PERMIT #02031076. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-03-26 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-03-26 |
Time |
17:44 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-03-26 |
Time |
17:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-03-28 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-03-28 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-03-28 |
Time |
15:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2002-05-22 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-05-22 |
Time |
08:54 |
Rev Time |
1.30 |
Received By |
pkrauss |
Date |
2002-05-22 |
Time |
08:54 |
Sent To |
|
|
Notes |
2002-05-22 00:00:00 | MECHANICAL PERMIT 02031106 | | PROVISO ON PLAN |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2002-05-13 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-05-13 |
Time |
15:59 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-05-13 |
Time |
15:59 |
Sent To |
|
|
Notes |
2002-05-13 00:00:00 | *******************DENIED*************** | | | | MECHANICAL PERMIT 02031106 | | | | SEER ON ENERGY CALCS OKAY. | | | | OTHER COMMENTS NOT ADDRESSED FROM | | PREVIOUS REVIEW. | | | | 1. O.A. CALCS. SHALL PROVIDE COMPLIANCE | | WITH 402.2 (4% OF THE FLOOR AREA BEING | | VENTILATED) OR TABLE 403.3 (MECHANICAL | | VENTILATION NOT INFILTRATION) | | | | 2. DRYER CFM NOT PROVIDED. | | | | 3. DRYER LENGTHS IN EXCESS OF CODE | | MINIMUM OF 25' PER 504.6. SUBMIT | | SPECIFIC MANUFACTURER SPECIFICATIONS OF | | ALLOWABLE LENGTH OF DUCT. | | | | 4. SECONDARY DRAIN CONSPICUOUS POINT | | SHALL NOT BE BEHIND AHU CLOSET DOOR. IF | | NO SUITABLE CONSPICUOUS LOCATION IS | | AVAILABLE, A PAN WITH A FLOAT SWITCH PER | | 307.2.4 IS ACCEPTABLE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-04-02 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-04-02 |
Time |
13:36 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2002-04-02 |
Time |
13:36 |
Sent To |
|
|
Notes |
2002-04-02 00:00:00 | *************DENIED********************* | | ADDITIONAL INFORMATION REQUIRED | | 1. PROVIDE CFM REQUIREMENTS FOR DRYER TO | | DETERMINE COMPLIANCE REQUIREMENTS PER | | 2001 FBC(M) 504.5 | | 2. PROVIDE OUTSIDE AIR PER FBC(M) TABLE | | 403.3 | | 3. SEER ON EQUIPMENT SCHEDULE DOES NOT | | MATCH SEER ON ENERGY CALCS | | | | NOTE: DRYER AND BATH EXHAUST DUCT SHALL | | NOT PENETRATE RATED PARTY WALL OR | | ADJACENT ROOF |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-05-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-13 |
Time |
18:20 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-13 |
Time |
18:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-04-19 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-19 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-19 |
Time |
13:23 |
Sent To |
|
|
Notes |
2002-04-19 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FHA AMEND-98 DESIGN MANUAL | | | | SEE COMMENTS FROM PEMIT #02031076 | | REVIEW | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-03-21 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-03-21 |
Time |
12:48 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|