Plan Review Details - Permit 02031078
Plan Review Stops For Permit 02031078
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-15 Cont ID  
Sent By jgomez Date 2002-05-15 Time 18:51 Rev Time 1.00
Received By jgomez Date 2002-05-15 Time 18:51 Sent To  
Notes
2002-05-15 00:00:00APPROVED WITH PROVISO: SEE COMMENTS ON
 PERMIT #02031076.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-26 Cont ID  
Sent By btrobaug Date 2002-03-26 Time 17:44 Rev Time 0.00
Received By btrobaug Date 2002-03-26 Time 17:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-03-28 Cont ID  
Sent By mcarsill Date 2002-03-28 Time 15:28 Rev Time 0.00
Received By mcarsill Date 2002-03-28 Time 15:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-05-22 Cont ID  
Sent By pkrauss Date 2002-05-22 Time 08:54 Rev Time 1.30
Received By pkrauss Date 2002-05-22 Time 08:54 Sent To  
Notes
2002-05-22 00:00:00MECHANICAL PERMIT 02031106
 PROVISO ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-05-13 Cont ID  
Sent By pkrauss Date 2002-05-13 Time 15:59 Rev Time 0.35
Received By pkrauss Date 2002-05-13 Time 15:59 Sent To  
Notes
2002-05-13 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 02031106
  
 SEER ON ENERGY CALCS OKAY.
  
 OTHER COMMENTS NOT ADDRESSED FROM
 PREVIOUS REVIEW.
  
 1. O.A. CALCS. SHALL PROVIDE COMPLIANCE
 WITH 402.2 (4% OF THE FLOOR AREA BEING
 VENTILATED) OR TABLE 403.3 (MECHANICAL
 VENTILATION NOT INFILTRATION)
  
 2. DRYER CFM NOT PROVIDED.
  
 3. DRYER LENGTHS IN EXCESS OF CODE
 MINIMUM OF 25' PER 504.6. SUBMIT
 SPECIFIC MANUFACTURER SPECIFICATIONS OF
 ALLOWABLE LENGTH OF DUCT.
  
 4. SECONDARY DRAIN CONSPICUOUS POINT
 SHALL NOT BE BEHIND AHU CLOSET DOOR. IF
 NO SUITABLE CONSPICUOUS LOCATION IS
 AVAILABLE, A PAN WITH A FLOAT SWITCH PER
 307.2.4 IS ACCEPTABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-02 Cont ID  
Sent By ndenmark Date 2002-04-02 Time 13:36 Rev Time 0.33
Received By ndenmark Date 2002-04-02 Time 13:36 Sent To  
Notes
2002-04-02 00:00:00*************DENIED*********************
 ADDITIONAL INFORMATION REQUIRED
 1. PROVIDE CFM REQUIREMENTS FOR DRYER TO
 DETERMINE COMPLIANCE REQUIREMENTS PER
 2001 FBC(M) 504.5
 2. PROVIDE OUTSIDE AIR PER FBC(M) TABLE
 403.3
 3. SEER ON EQUIPMENT SCHEDULE DOES NOT
 MATCH SEER ON ENERGY CALCS
  
 NOTE: DRYER AND BATH EXHAUST DUCT SHALL
 NOT PENETRATE RATED PARTY WALL OR
 ADJACENT ROOF

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-13 Cont ID  
Sent By kstevens Date 2002-05-13 Time 18:20 Rev Time 0.00
Received By kstevens Date 2002-05-13 Time 18:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-19 Cont ID  
Sent By kstevens Date 2002-04-19 Time 13:23 Rev Time 0.00
Received By kstevens Date 2002-04-19 Time 13:23 Sent To  
Notes
2002-04-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 SEE COMMENTS FROM PEMIT #02031076
 REVIEW
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-21 Cont ID  
Sent By sgraham Date 2002-03-21 Time 12:48 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***