Plan Review Details - Permit 02031076
Plan Review Stops For Permit 02031076
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-15 Cont ID  
Sent By jgomez Date 2002-05-15 Time 18:21 Rev Time 1.00
Received By jgomez Date 2002-05-15 Time 18:21 Sent To  
Notes
2002-05-15 00:00:00APPROVED WITH PROVISO:
 1-TWO HOUR OVERHANG DETAIL FOR WOOD
 ASSEMBLY USING CALCULATED RATINGS IS
 NOT ALLOWED. SEE SECTION 709.6.1.2
 FBC 2001. REVISE AS REQUIRED.
 2-REVISE OR OMIT 2HR FIRE RATED GLASS
 BLOCK DETAIL. SEE UL ASSEMBLY SPECS
 FOR TWO HR FIRE RATED ASSEMBLY.
 3-REVISE BUCK DETAILS. SEE SECTION
 1704.4.2 FBC 2001 FOR SPECIFICATIONS
 REGARDING THE EXTEND OF THE BUCK.
 4-PROVIDE COMPLETE SPECIFICATIONS FOR
 INSTALLATION OF CEILINGS AT FRONT AND
 REAR PORCHES. SEE ASTM C-1063 FOR
 FASTENERS, TYPE, SIZE AND SPACING.
 SECTION 2504.2 FBC 2001.
 5-CLARIFY GARAGE DOOR DETAIL. SEE DETAIL
 1/DS-1 AND DETAIL 4/S4.
 6-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF TILE PRODUCT APPROVAL SUBMITTED
 IS NOT GOOD. IT WAS DELETED FROM SBCCI
 7-UPDATE ALL CONNECTORS AS REQUIRED.
 HUGHES OR SEMCO ARE OUT OF BUSINESS.
 8-APPLY FOR SEPARATE PERMITS FOR UNITS
 TO HAVE SCREEN ENCLOSURES.
  
 NOTES:
 *DRAWINGS AND COMMENTS TO BE FILED UNDER
 PERMIT #02031076.
 *THESE COMMENTS APPLY TO PERMIT #S:
 02031076, 02031077, 02031078 AND
 02031080.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-06 Cont ID  
Sent By jwitmer Date 2002-04-06 Time 09:05 Rev Time 4.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-06 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02031076
 LOTS: 75-78
 8596 LINYARD CAY
  
 FL CODE= 2001 FLORIDA BUILDING CODE
 FR HOUS= FAIR HOUSING ACT
  
 1)- SOILS REPORT NOT SIGNED & SEALED,
 61G15-23.002 REQUIRES THE PROFESSIONAL
 ENGINEER SHALL SIGN HIS NAME AND AFFIX
 HIS SEAL TO ALL PLANS SPECIFICATIONS,
 REPORTS OR DOCUMENTS PREPARED OR ISSUED
 BY SAID REGISTRANT AND BEING FILED FOR
 PUBLIC RECORD.
  
 2)- STRUCTURAL CUT SECTIONS MISSING A
 NEW CODE ELEMENT FL CODE 1909.3(2)
 CONCRETE SLABS ON GROUND CONTAINING 6X6
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3 OF THE SLAB, SHALL BE SUPPORT-
 ED WITH AN APPROVED MATERIALS OR SUPPORT
 AT SPACINGS TO NOT EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURES SPECIFICA-
 TIONS.
 3)- STRUCURAL PLANS- HUGHES MANUFACTUR-
 ING AS WELL AS SEMCO WERE BOUGHT OUT BY
 USP CONNECTORS OVER A YEAR AGO. THERE
 IS A NEW PRODUCT REFRENCE NUMBERS AND
 NEW TESTING DATA.
 4)- SH-1 EGRESS TYPE WINDOW NOTES: INDIC
 ATES A NOTE "DELTA 5" THAT ALL EXTERIOR
 GLAZED OPENINGS SHALL COMPLY WITH THE
 FBC 2001 ED CHAPTER 3? THREE IS TYPE
 OF OCCUPANCIES? 1005.4 EMERGENCY ESCAPE
 AND RESCUE OPENINGS.
 5)- SHEET SH-1WINDOW SCHEDULE INDICATE
 A "I" 8" GLASS BLOCK TO BE A 2 HR RATING
 SHEET DS-1 DETAILS GLASS BLOCK IN MODEL
 "C". A 2 HR RATING?
 BUILDING PLAN REVIEW
 JIM WITMER
 (5610659-8096X8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-26 Cont ID  
Sent By btrobaug Date 2002-03-26 Time 17:13 Rev Time 0.00
Received By btrobaug Date 2002-03-26 Time 16:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-03-28 Cont ID  
Sent By mcarsill Date 2002-03-28 Time 15:28 Rev Time 0.00
Received By mcarsill Date 2002-03-28 Time 15:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-05-22 Cont ID  
Sent By pkrauss Date 2002-05-22 Time 08:49 Rev Time 1.30
Received By pkrauss Date 2002-05-22 Time 08:49 Sent To  
Notes
2002-05-22 00:00:00MECHANICAL PERMIT 02031110
 PROVISO ON PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-05-13 Cont ID  
Sent By pkrauss Date 2002-05-13 Time 15:50 Rev Time 0.35
Received By hmoser Date 2002-05-13 Time 15:50 Sent To  
Notes
2002-05-13 00:00:00MECHANICAL PERMIT 02031110
  
 OTHER COMMENTS NOT ADDRESSED FROM
 PREVIOUS REVIEW.
  
 1. SEER ON ENERGY CALCS STILL DO NOT
 MATCH SEER SHOWN ON EQUIPMENT SCHEDULE.
  
 2. O.A. CALCS. SHALL PROVIDE COMPLIANCE
 WITH 402.2 (4% OF THE FLOOR AREA BEING
 VENTILATED) OR TABLE 403.3 (MECHANICAL
 VENTILATION NOT INFILTRATION)
  
 3. DRYER CFM NOT PROVIDED.
  
 4. DRYER LENGTHS IN EXCESS OF CODE
 MINIMUM OF 25' PER 504.6. SUBMIT
 SPECIFIC MANUFACTURER SPECIFICATIONS OF
 ALLOWABLE LENGTH OF DUCT.
  
 5. SECONDARY DRAIN CONSPICUOUS POINT
 SHALL NOT BE BEHIND AHU CLOSET DOOR. IF
 NO SUITABLE CONSPICUOUS LOCATION IS
 AVAILABLE, A PAN WITH A FLOAT SWITCH PER
 307.2.4 IS ACCEPTABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-02 Cont ID  
Sent By ndenmark Date 2002-04-02 Time 13:32 Rev Time 0.25
Received By ndenmark Date 2002-04-02 Time 13:32 Sent To  
Notes
2002-04-02 00:00:00******************DENIED***************
  
 ADDITIONAL INFORMATION REQUIRED:
 1. PROVIDE CFM REQUIREMENTS FOR DRYER TO
 DETERMINE COMPLIANCE PER 2001 FBC(M)
 504.5
 2. PROVIDE OUTSIDE AIR PER FBC(M) TABLE
 403.3
 3. SEER ON EQUIPMENT SCHEDULE DOES NOT
 MATCH SEER ON ENERGY CALCS
  
 NOTE: DRYER AND BATH EXHAUST DUCTS SHAL
 NOT PENETRATE RATED PARTYWALL OR
 ADJACENT ROOF

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-13 Cont ID  
Sent By kstevens Date 2002-05-13 Time 18:14 Rev Time 0.00
Received By kstevens Date 2002-05-13 Time 18:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-19 Cont ID  
Sent By kstevens Date 2002-04-19 Time 11:23 Rev Time 0.00
Received By kstevens Date 2002-04-19 Time 11:23 Sent To  
Notes
2002-04-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 1) SHT BR_MP-1 SANITARY RISER DIAGRAM,
 MASTER BATH SHOWS 2 LAVS, ONLY 1 SHOWN
 ON FLOOR PLAN. (IF OPTIONAL, STATE ON
 PLAN)
 2) SHT BR_MP-1 WATER RISER DIAGRAM, RE-
 MOVE AIR CHAMBER AT WATER HEATER. WATER
 HAMMER ARRESTORS SHALL BE INSTALLED
 WHERE QUICK CLOSING VALVES ARE UTILIZED.
 (WASH MACHINE, DISHWASHER, ICE MAKER)
 SECTION 604.9
 3) SHT B_MP-4 PLUMBING NOTES AND SPECS.,
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 4) SHT A_MP-1 SANITARY RISER DIAGRAM,
 OPTIONAL LAUNDRY SINK TO RUN TO THE
 RIGHT OF THE BLDG. DRAIN AWAY FROM WASH
 MACHINE TO REFLECT FLOOR PLAN.
 5) SHT A_MP-1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE INSTALLED
 WHERE QUICK CLOSING VALVES ARE UTILIZED.
 (WASH MACHINES, DISHWASHERS, ICE MAKERS)
 SECTION 604.9
 6) SHT A_MP-3 PLUMBING NOTES AND SPECS.,
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 7) SHT A1_MP-1 SANITARY RISER DIAGRAM,
 OPTIONAL LAUNDRY SINK TO RUN TO THE
 RIGHT OF THE BLDG. DRAIN AWAY FROM WASH
 MACHINE TO REFLECT FLOOR PLAN.
 8) SHT A1_MP-1 WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS SHALL BE INSTALL-
 ED WHERE QUICK CLOSING VALVES ARE UTIL-
 IZED. (WASH MACHINE, DISHWASHER, ICE
 MAKER). SECTION 604.9
 9) SHT A1_MP-1 PLUMBING NOTES AND SPECS.
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 10) SHT B_MP-1 WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS SHALL BE INSTALL-
 ED WHERE QUICK CLOSING VALVES ARE UTIL-
 IZED. (WASH MACHINE, DISHWASHER, ICE
 MAKER) SECTION 604.9
 11) SHT B_MP-4 PLUMBING NOTES AND SPECS.
 NOTE #1(B) TO READ FBC-2001 PLUMBING, &
 FHA AMEND-98 DESIGN MANUAL.
 12) 504.7.1 THE DISCHARGE PIPE SHALL NOT
 HAVE ANY TRAPPED SECTIONS AND SHALL HAVE
 A VISIBLE AIR GAP OR AIR GAP FITTING LO-
 CATED IN THE SAME ROOM AS THE WATER
 HEATER. SEE SHTS A_MP-3 & B_MP-4 WATER
 HEATER DETAILS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-21 Cont ID  
Sent By sgraham Date 2002-03-21 Time 12:47 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***