Plan Review Details - Permit 02031009
Plan Review Stops For Permit 02031009
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-04-19 Cont ID  
Sent By btrobaug Date 2002-04-10 Time 18:05 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2002-04-19 00:00:00**************PROVISO****************
  
  
 11. REFERENCE SECTION FOR POOL SAFETY
 ACT IS INCORRECT.SHOULD BE FBC2001
 CHA. 424
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-10 Cont ID  
Sent By kstevens Date 2002-04-10 Time 17:10 Rev Time 0.00
Received By btrobaug Date 2002-04-10 Time 17:54 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-21 Cont ID  
Sent By kstevens Date 2002-05-21 Time 08:34 Rev Time 0.00
Received By kstevens Date 2002-05-21 Time 08:34 Sent To  
Notes
2002-05-21 00:00:00PASSED/PROVISO
  
 EXTERNAL HARTFORD LOOP REQUIRED. NO IN-
 TERNAL POSITIVE MEANS OF WATER RETENTION
 SHOWN.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-10 Cont ID  
Sent By kstevens Date 2002-04-10 Time 16:50 Rev Time 0.00
Received By kstevens Date 2002-04-10 Time 16:50 Sent To E
Notes
2002-04-10 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92. GENERAL NOTES #10 READS
 POOL DESIGN BASED ON RATIONAL ANALYSIS.
 2)
 FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 3)
 FBC-2001 SEC 424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 4)
 FBC-2001 SEC 424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 5)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 6)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 7)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 8)
 FBC-2001 SEC 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 9)
 FBC-2001 SEC 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 10)
 FBC-2001 SEC 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 11)
 FBC-2001 SEC 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
 12) NOTES AT POOL PIPING DIAGRAM REFER
 TO S F B C. THIS CODE REFERENCE NOT IN
 EFFECT - SEE ABOVE FOR FBC-2001 REFEREN-
 CES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-20 Cont ID  
Sent By sgraham Date 2002-03-20 Time 08:03 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved