Plan Review Details - Permit 02030965
Plan Review Stops For Permit 02030965
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-03-15 Cont ID  
Sent By mcarsill Date 2002-03-15 Time 16:15 Rev Time 0.00
Received By mcarsill Date 2002-03-15 Time 16:15 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status P Date 2002-03-15 Cont ID  
Sent By mcarsill Date 2002-03-15 Time 16:16 Rev Time 0.00
Received By mcarsill Date 2002-03-15 Time 16:16 Sent To  
Notes
2002-03-15 00:00:00A) ENTIRE BUILDING IS REQUIRED TO BE
 FIRE SPRINKLER PROTECTED.
 B) THE FIRE DEPARTMENT CONNECTION IS TO
 NO MORE THAN 150 FEET FROM A FIRE
 HYDRANT.
 C) FIRE SPRINKLER PIPING THAT ENTERS
 THE STAIRWAY IS NOT TO INTERFERE WITH
 MINIMUM HEADROOM REQUIREMENTS.
 D) FIRE SPRINKLER HEADS IN GARAGE SHOULD
 BE WAX COATED.
 E) TWO SMALL BOXES ON THE SECOND AND
 THIRD FLOOR ARE TO BE FIRE SPRINKLER
 PROTECTED. THESE AREAS APPEAR TO BE
 LOCATED ABOVE THE FIRST FLOOR MECHANICAL
 ROOM.
 F) BACKFLOW DEVICE IS REQUIRED TO BE
 SUPERVISED WITH TAMPER SWITCHES AND
 A CHAIN AND LOCK.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-03-15 Cont ID  
Sent By mcarsill Date 2002-03-15 Time 16:23 Rev Time 0.00
Received By mcarsill Date 2002-03-15 Time 16:23 Sent To  
Notes
***NONE***