Plan Review Details - Permit 02030911
Plan Review Stops For Permit 02030911 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-05-08 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2002-05-08 |
Time |
13:40 |
Rev Time |
0.75 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-04-19 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-04-10 |
Time |
17:52 |
Rev Time |
0.75 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-19 00:00:00 | FAILED BUILDING | | | | 1. FBC 2001 IS THE CODE ADOPTED 3/1/02 | | NEED DETAILS OF EQUIPMENT PAD & | | ANCHORING DETAILS | | | | 2. POOL SAFETY FEATURES ARE IN FBC 2001 | | NOT SS 515. | | | | ANY QUESTIONS PLEASE CALL: | | LEA SMITH, BUILDING PLANS EXAMINER | | 659-8096 EXT 8394 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-04-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-04 |
Time |
12:22 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-04-10 |
Time |
17:48 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-05-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-04 |
Time |
12:22 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-04 |
Time |
12:22 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-04-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-10 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-10 |
Time |
15:03 |
Sent To |
E |
|
Notes |
2002-04-10 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 PRIVATE POOLS | | | | 1) COMPLY WITH FBC-2001 SEC 424.2 | | PRIVATE SWIMMING POOLS. NOTE SAYS FBC | | SECT 104.1 2001 EDT. | | 2) FBC-2001 SEC 424.2.6.1 ENGINEERING | | DESIGN, CONSTRUCTION AND WORKMANSHIP. | | ANSI/NSPI-4 92. GENERAL NOTE #14 SAYS | | DESIGNED PER WEST PALM BEACH SWIMMING | | POOL CODE. | | 3) | | FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | NUMBER AND MANUF INFO FOR VAC LOCK. | | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) | | 4) | | FBC-2001 SEC 424.2.7.2 PUMPS AND EQUIP- | | MENT SHALL BE MOUNTED ON A SUBSTANTIAL | | BASE IN A MANNER THAT WILL ELIMINATE | | STRAIN ON PIPING. SLAB SHALL BE A NOMIN- | | AL 4" THICK. (DETAIL) | | 5) | | FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL | | ORD. #2853-95, BACKFLOW REQUIRED ON | | WATER SERVICE. (ADD TO NOTES) | | 6) | | FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 7) | | FBC-2001 SEC 424.2.13.2JOINTS AND CON- | | NECTIONS, FBC PLMG SEC 605.21, PURPLE | | PRIMER REQUIRED ON PVC PIPING. (ADD TO | | NOTES) | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-03-19 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-03-19 |
Time |
10:52 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|