Plan Review Details - Permit 02030911
Plan Review Stops For Permit 02030911
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-08 Cont ID  
Sent By lsmith Date 2002-05-08 Time 13:40 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-19 Cont ID  
Sent By btrobaug Date 2002-04-10 Time 17:52 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-04-19 00:00:00FAILED BUILDING
  
 1. FBC 2001 IS THE CODE ADOPTED 3/1/02
 NEED DETAILS OF EQUIPMENT PAD &
 ANCHORING DETAILS
  
 2. POOL SAFETY FEATURES ARE IN FBC 2001
 NOT SS 515.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT 8394

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-10 Cont ID  
Sent By kstevens Date 2002-05-04 Time 12:22 Rev Time 0.00
Received By btrobaug Date 2002-04-10 Time 17:48 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-04 Cont ID  
Sent By kstevens Date 2002-05-04 Time 12:22 Rev Time 0.00
Received By kstevens Date 2002-05-04 Time 12:22 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-10 Cont ID  
Sent By kstevens Date 2002-04-10 Time 15:03 Rev Time 0.00
Received By kstevens Date 2002-04-10 Time 15:03 Sent To E
Notes
2002-04-10 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 PRIVATE POOLS
  
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. NOTE SAYS FBC
 SECT 104.1 2001 EDT.
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92. GENERAL NOTE #14 SAYS
 DESIGNED PER WEST PALM BEACH SWIMMING
 POOL CODE.
 3)
 FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 4)
 FBC-2001 SEC 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 5)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 6)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 7)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-19 Cont ID  
Sent By sgraham Date 2002-03-19 Time 10:52 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***