Plan Review Details - Permit 02030773
Plan Review Stops For Permit 02030773 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-04-29 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2002-04-29 |
Time |
16:14 |
Rev Time |
0.50 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-04-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-23 |
Time |
17:19 |
Rev Time |
0.75 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-03 00:00:00 | **************FAILED****************** | | | | 1. DRAWINGS MUST SHOW DETAIL OF CONCRETE | | EQUIPMENT SLAB INCLUDING THE TYPES & | | METHOD OF ANCHORING OF EQUIPMENT. | | | | 2. DIRECT ACCESS TO POOL AREA MUST BE | | PROTECTED ACCORDING TOFBC 424. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-03-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-03-29 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-03-29 |
Time |
11:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-04-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-23 |
Time |
17:19 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-23 |
Time |
17:19 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-03-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-03-29 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-03-29 |
Time |
10:34 |
Sent To |
E |
|
Notes |
2002-03-29 00:00:00 | DENIED | | REFERENCE: FBC-2001 | | | | 1) POOL PIPING DIAGRAM, SHOW VENT PIPING | | 2) SEC 4.24.2.7.2 PROVIDE MOUNTING DE- | | TAIL FOR EQUIPMENT. SLAB SHALL BE NOMIN- | | AL 4" | | 3) SEC 4.24.2.9 WATER SUPPLY. ORD 2835- | | 95 - BACKFLOW REQUIRED ON WATER SERVICE. | | (ADD TO NOTES) | | 4) SEC 4.24.2.12 NO AIR TEST FOR PVC. - | | (ADD TO NOTES) | | 5) SEC 4.24.2.13.2 PURPLE CLEANER REQ- | | UIRED FOR PVC. FBC PLMG. SEC 605.21 | | (ADD TO NOTES) | | 6) FOR FUTURE REFERENCE: WHEN POOL HEAT- | | ER IS SUPPLIED, SEC 4.24.2.6.4 MANUF. | | RECOMMENDATION REQUIRED., SEC 4.24.14.2 | | WATER RETENTION - PROVIDE MANUF. CUT | | SHEETS SHOWING COMPLIANCE., SEC 4.24.2. | | 14.4 CONNECTIONS TO HEATER SHALL BE | | FLANGED OR UNIONS. (ADD TO NOTES) | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-03-19 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-03-19 |
Time |
08:51 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|