Plan Review Details - Permit 02030756
Plan Review Stops For Permit 02030756
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-30 Cont ID  
Sent By jwitmer Date 2002-04-30 Time 13:33 Rev Time 1.33
Received By jwitmer Date 2002-04-30 Time 13:33 Sent To  
Notes
2002-04-30 00:00:00PLANS TO BE SUBMITTED TO P.B. COUNTY
 FOR IMPACT FEE ASSESSMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-15 Cont ID  
Sent By jwitmer Date 2002-04-15 Time 14:22 Rev Time 2.50
Received By jwitmer Date 2002-04-15 Time 14:22 Sent To  
Notes
2002-04-15 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02030756
 9031 SAND PINE LANE
 CONT: NLS COMMUNITIES
 TEL: (561) 691-1771
  
 FL BLDG CODE= 2001 FLORIDA BUILDING CODE
  
 1)- PLANS SUBMITTED AFTER FEB. 28, 2001
 SHALL BE DESIGNED TO THE 2001 FLORIDA
 BUILDING CODE.
 2)- DESIGN CRITERIA & FOR BUILDING CODE
 COMPLIANCE, FL BLDG CODE 1606.1.7 THE IN
 FORMATION RELATED TO WIND SHALL BE SHOWN
 ON THE CONSTRUCTION DRAWINGS.
 3)- FL BLDG CODE 1909.3 JOINTS (2)
 EXCEPTION: CONCRETE SLABS ON GRADE
 CONTAINING 6X6 W1.4XW1.4 WELDED WIRE
 REINFORCEMENT FABRIC LOCATED IN THE
 MIDDLE TO THE UPPER 1/3 OF THE SLAB,
 APPROVED MATERIALS OR SUPPORTS AT SPAC-
 ING NOT TO EXCEED 3 FT OR IN ACCORDANCE
 WITH MANUFACTURES SPEC.
 4)- SHEET A8 DETAIL #9 SEE FL BLDG CODE
 2117.1.1 GABLE ENDWALLS SHALL BE STRUC-
 TURALLY CONTINUOUS BETWEEN POINTS OF
 LATERAL SUPPORT.
 5)SHEET A-5A SEMCO IS NO LONGER IN BUS-
 INESS, UPDATE PLANS, USP 2001 CATALOG
 FOR TAPR 216 VALUE IS 1485 LSB FOR
 UPLIFT. NOTE WHEN MULTIPLE STRAPS ARE
 CLOSER THAN 8" A DERATING SHALL OCCUR.
 SEE MANUFACTURES NOTES, PAGE40.
 FOR (2) TARP 216 2X 1485=2970X.80%=
 2376 LBS NOT 3900 LBS?
 6)- TAPR222 THE VALUE OF 1485 FOR ONE
 STRAP REVISIT THE FIGURES FOR MULTIPLE
 STRAPS, LETTER SEALED FROM ENGINEER FOR
 USP GIVING THESE VALUES!!!!!
 8)- USP HAS NO RTP 1812?
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-03 Cont ID  
Sent By dpalmer Date 2002-04-03 Time 06:46 Rev Time 0.00
Received By dpalmer Date 2002-04-03 Time 06:46 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-30 Cont ID  
Sent By hmoser Date 2002-03-30 Time 13:23 Rev Time 0.33
Received By hmoser Date 2002-03-30 Time 13:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-30 Cont ID  
Sent By jleech Date 2002-03-30 Time 08:40 Rev Time 0.33
Received By jleech Date 2002-03-30 Time 08:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-21 Cont ID  
Sent By sgraham Date 2002-03-21 Time 12:43 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***