Plan Review Stops For Permit 02030743 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
98 |
Status |
P |
Date |
2003-09-15 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-09-15 |
Time |
13:14 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-09-15 |
Time |
13:14 |
Sent To |
|
|
Notes |
2003-09-15 00:00:00 | LETTER SUBMITTAL ON 9/15/03 FOR | | ELEVATION SURVEY OF ACCESSIBLE RAMP. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
97 |
Status |
P |
Date |
2003-09-02 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-09-15 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-09-02 |
Time |
15:01 |
Sent To |
|
|
Notes |
2003-09-02 00:00:00 | SUBMITTAL ON 8/29/03 FOR ZEIDLER | | GRINNELL PARTNERSHIP LETTER DATED | | 8/28/03. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
96 |
Status |
P |
Date |
2003-08-27 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-08-27 |
Time |
16:44 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-08-27 |
Time |
16:44 |
Sent To |
|
|
Notes |
2003-08-27 00:00:00 | SUBMITTAL 8/27/03 OF LETTER DATED | | 8/19/03 FROM ENGINEER OF RECORD ABOUT | | REMOVAL OF EXIST'G PARKING GARAGE COLUMN |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
95 |
Status |
P |
Date |
2003-08-14 |
|
|
Cont ID |
|
Sent By |
dbaxter |
Date |
2003-08-27 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-08-14 |
Time |
17:00 |
Sent To |
|
|
Notes |
2003-08-14 00:00:00 | STRUCTURAL SUBMITTAL 8/14/03 FOR METAL | | STAIR AS-BUILT SHOP DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
94 |
Status |
P |
Date |
2003-08-14 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-08-14 |
Time |
11:51 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-08-14 |
Time |
11:50 |
Sent To |
|
|
Notes |
2003-08-14 00:00:00 | STRUCTURAL REVISION SUBMITTED 8/12/03 | | FOR REINFORCED CONCRETE BEAM (SHEETS | | SK-141 AND SK-142) |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
93 |
Status |
P |
Date |
2003-07-21 |
|
|
Cont ID |
|
Sent By |
dbaxter |
Date |
2003-08-12 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-07-21 |
Time |
16:54 |
Sent To |
|
|
Notes |
2003-07-21 00:00:00 | REVISION SUBMITTED 7/21/03 FOR SHEETS | | SK125, SK139 AND SK140 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
92 |
Status |
P |
Date |
2003-07-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-07-21 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-07-21 |
Time |
16:52 |
Sent To |
|
|
Notes |
2003-07-21 00:00:00 | REVISION SUBMITTED 7/14/03 FOR SHEETS | | SK124 TO SK129 AND SK135 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
91 |
Status |
P |
Date |
2003-07-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-07-21 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-07-21 |
Time |
15:33 |
Sent To |
|
|
Notes |
2003-07-21 00:00:00 | SUBMITTAL OF STEEL SHOP DRAWINGS FOR | | MEZZANINE LEVEL FRAMING. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
90 |
Status |
P |
Date |
2003-07-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-07-21 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-07-21 |
Time |
15:30 |
Sent To |
|
|
Notes |
2003-07-21 00:00:00 | SUBMITTAL 7/14/03 FOR STRUCTURAL LETTER | | ON PRIMARY DRAINAGE FROM CANOPY ROOFS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
89 |
Status |
P |
Date |
2003-07-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-07-21 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-07-21 |
Time |
14:56 |
Sent To |
|
|
Notes |
2003-07-21 00:00:00 | SUBMITTAL 7/14/03 FOR SHEET SH1- | | SHORING FOR WET BEAM AT NEW OPENING |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
88 |
Status |
P |
Date |
2003-07-09 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-21 |
Time |
10:38 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-07-09 |
Time |
13:56 |
Sent To |
|
|
Notes |
2003-07-09 00:00:00 | SUBMITTAL 7/7/03 FOR GLASS CANOPY SHOP | | DRAWINGS AND GLASS PRODUCT DATA |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
87 |
Status |
P |
Date |
2003-07-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-07-09 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-07-09 |
Time |
13:54 |
Sent To |
|
|
Notes |
2003-07-09 00:00:00 | REVISION SUBMITTED 7/7/03 FOR COVERED | | WALKWAY AND GLASS CANOPY SUPPORT DETAILS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
86 |
Status |
P |
Date |
2003-07-08 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-07-08 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-07-08 |
Time |
13:50 |
Sent To |
|
|
Notes |
2003-07-08 00:00:00 | SUBMITTAL 7/7/03 FOR GARAGE BEAM SHORING | | SHOP DRAWINGS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
85 |
Status |
P |
Date |
2003-07-02 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-08 |
Time |
09:49 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-07-02 |
Time |
09:31 |
Sent To |
|
|
Notes |
2003-07-02 00:00:00 | SUBMITTAL 7-2-03 FOR LOUVER PRODUCT | | APPROVAL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
84 |
Status |
P |
Date |
2003-06-13 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-01 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-06-13 |
Time |
15:45 |
Sent To |
|
|
Notes |
2003-06-13 00:00:00 | REVISION SUBMITTED 5/30/03 FOR SHEET | | A-803 (WALL TYPES) |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
83 |
Status |
F |
Date |
2003-06-13 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-06-13 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-06-13 |
Time |
13:21 |
Sent To |
|
|
Notes |
2003-06-13 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6716 | | E-MAIL: [email protected] | | | | SUBMITTAL 6/12/03 FOR LOUVER PRODUCT | | APPROVAL. | | | | 1) THE SUBMITTED CONSTRUCTION | | SPECIALTIES INC. LOUVER PRODUCT APPROVAL | | NOA# 00-1107.03 (SHEET 2 UNDER ITEM 2.1 | | PRODUCT DESCRIPTION) STATES THAT THE | | SYSTEM SHALL BE INSTALLED IN COMPLIANCE | | WITH DRAWING# RD 104-1 THROUGH RD 104-9 | | BEARING THE MIAMI-DADE COUNTY PRODUCT | | CONTROL APPROVAL STAMP.THOSE DRAWINGS | | WERE NOT INCLUDED WITH THE PRODUCT | | APPROVAL.SUBMIT THE REQUIRED DRAWINGS. | | COPIES OF MIAMI-DADE PRODUCT APPROVALS | | CAN BE PRINTED FROM THEIR WEBSITE,WWW. | | MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | TELEPHONE: (561) 805 6716ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
82 |
Status |
P |
Date |
2003-06-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-06-13 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-06-12 |
Time |
09:45 |
Sent To |
|
|
Notes |
2003-06-12 00:00:00 | R.I. JOHNSON & ASSOCIATES RE-SUBMITTAL | | 6/12/03 FOR STAIR #3 RAILING CALCS | | (PREVIOUS REVIEW 3/14/03) |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
81 |
Status |
P |
Date |
2003-06-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-06-12 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-06-12 |
Time |
08:27 |
Sent To |
|
|
Notes |
2003-06-12 00:00:00 | SUBMITTAL 6/3/03 FOR SKYLITE FRAMING | | SHOP DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
80 |
Status |
P |
Date |
2003-06-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-06-11 |
Time |
16:48 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-06-11 |
Time |
16:48 |
Sent To |
|
|
Notes |
2003-06-11 00:00:00 | SUBMITTAL 6/3/03 FOR LOUVER SHOP | | DRAWINGS. | | PASSED WITH PROVISO TO 'ISOLATE | | DISSIMILAR METALS' |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
79 |
Status |
P |
Date |
2003-05-29 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-04 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-05-29 |
Time |
16:51 |
Sent To |
|
|
Notes |
2003-05-29 00:00:00 | SUBMITTAL ON 5-27-03 FOR CANOPY SHOP | | DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
78 |
Status |
P |
Date |
2003-05-29 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-05-29 |
Time |
16:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-05-29 |
Time |
16:45 |
Sent To |
|
|
Notes |
2003-05-29 00:00:00 | SUBMITTAL ON 5-27-03 FOR SEGMENTED | | RETAINING WALL |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
77 |
Status |
P |
Date |
2003-05-29 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-05-29 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-05-29 |
Time |
16:26 |
Sent To |
|
|
Notes |
2003-05-29 00:00:00 | REVISION SUBMITTED 5-27-03 FOR SK-134 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
76 |
Status |
P |
Date |
2003-05-15 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-28 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-05-15 |
Time |
11:12 |
Sent To |
|
|
Notes |
2003-05-15 00:00:00 | 5-9-03 SUBMITTAL FOR 45 MINUTE PYROSTOP | | GLASS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
75 |
Status |
P |
Date |
2003-05-05 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-12 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-05-05 |
Time |
12:23 |
Sent To |
|
|
Notes |
2003-05-05 00:00:00 | STRUCTURAL REVISION SUBMITTED 4-25-13 | | FOR RFI 356 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
74 |
Status |
P |
Date |
2003-05-05 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-05-05 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-05-05 |
Time |
12:03 |
Sent To |
|
|
Notes |
2003-05-05 00:00:00 | STRUCTURAL REVISION SUBMITTED 4-25-03 | | FOR SKETCHES SK-120 AND SK-123. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
73 |
Status |
P |
Date |
2003-05-05 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-05-05 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-05-05 |
Time |
11:50 |
Sent To |
|
|
Notes |
2003-05-05 00:00:00 | SUBMITTAL ON 4-25-03 FOR FIRE RETARDANT | | (INTUMESCENT) COATING FOR MILLWORK. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
72 |
Status |
P |
Date |
2003-04-22 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-25 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-04-22 |
Time |
18:02 |
Sent To |
|
|
Notes |
2003-04-22 00:00:00 | 4-14-03 SUBMITTAL FOR COVERED WALKWAY | | SHOP DRAWINGS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
71 |
Status |
P |
Date |
2003-04-14 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-15 |
Time |
09:29 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-04-14 |
Time |
09:01 |
Sent To |
|
|
Notes |
2003-04-14 00:00:00 | REVISION SUBMITTED 4-7-03 FOR CURTAIN | | WALL SUPPORT STEEL SKETCHES SK118, SK121 | | AND SK122 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
70 |
Status |
P |
Date |
2003-04-14 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-04-14 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-04-14 |
Time |
08:44 |
Sent To |
|
|
Notes |
2003-04-14 00:00:00 | SUBMITTAL ON 4-7-03 FOR ENTRY CANOPY | | STEEL SHOP DRAWINGS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
69 |
Status |
P |
Date |
2003-03-31 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-04-09 |
Time |
10:59 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-03-31 |
Time |
16:04 |
Sent To |
|
|
Notes |
2003-03-31 00:00:00 | STRUCTURAL SUBMITTAL ON 3-31-03 FOR | | RFI #246 - BENT PLATE FIELD REPAIR. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
68 |
Status |
P |
Date |
2003-03-31 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-03-31 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-03-31 |
Time |
16:02 |
Sent To |
|
|
Notes |
2003-03-31 00:00:00 | STRUCTURAL SUBMITTAL ON 3-31-03 FOR | | SHEETS SK-118 THRU SK-122. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
67 |
Status |
F |
Date |
2003-03-31 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-03-31 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-03-31 |
Time |
14:27 |
Sent To |
|
|
Notes |
2003-03-31 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | STEEL SHOP DRAWING SUBMITTAL ON 3-25-03 | | FOR ENTRY CANOPY. | | | | 1) STRUCTURAL SHOP DRAWINGS SHALL BE | | REVIEWED AND STAMPED BY THE ENGINEER OF | | RECORD BEFORE SUBMITTAL. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
66 |
Status |
P |
Date |
2003-03-31 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-03-31 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-03-31 |
Time |
12:06 |
Sent To |
|
|
Notes |
2003-03-31 00:00:00 | STRUCTURAL SUBMITTAL ON 3-25-03 FOR | | SK116 & SK117 CANOPY AT LOADING DOCK |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
65 |
Status |
P |
Date |
2003-03-31 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-03-31 |
Time |
09:37 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-03-31 |
Time |
09:37 |
Sent To |
|
|
Notes |
2003-03-31 00:00:00 | BUILDING PLAN REVIEW | | ******PROVISO******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | REVISION SUBMITTED 3-24-03 FOR AMENDMENT | | TO THE WIDTH OF STAIR 4. | | | | --PROVISO-- | | THE MINIMUM STAIR WIDTH DIMENSIONS HAVE | | BEEN REDLINED WHERE THEY WERE INCOMPLETE | | ON THE PLANS AS SUBMITTED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
64 |
Status |
P |
Date |
2003-03-20 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-03-25 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-03-20 |
Time |
08:44 |
Sent To |
|
|
Notes |
2003-03-20 00:00:00 | STRUCTURAL REVISION SUBMITTED 3-19-03, | | FOR GX-1 EXHAUST FAN SUPPORT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
63 |
Status |
F |
Date |
2003-03-14 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-03-19 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-03-14 |
Time |
11:27 |
Sent To |
|
|
Notes |
2003-03-14 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | R.I. JOHNSON & ASSOCIATES SUBMITTAL FOR | | STAIR #3 RAILING CALCS. | | | | FBC 1608.2.2.2THE SUBMITTED | | CALCULATIONS AND TEST REPORT ONLY | | CONSIDER CONCENTRATED LOADING APPLIED | | HORIZONTALLY. IN ADDITION, THE GUARDRAIL | | SHALL BE DESIGNED TO RESIST UNIFORMLY | | DISTRIBUTED LOADS OF 50 LB/FT APPLIED | | HORIZONTALLY TOGETHER WITH A | | SIMULTANEOUS 100 LB/FT APPLIED | | VERTICALLY DOWN AT THE TOP OF THE | | HANDRAIL.SUBMIT FURTHER CALCULATIONS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
62 |
Status |
P |
Date |
2003-03-14 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-03-14 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-03-14 |
Time |
10:03 |
Sent To |
|
|
Notes |
2003-03-14 00:00:00 | TRAINOR GLASS CO. SUBMITTAL 3-7-03 FOR | | ADDITIONAL 3RD FLOOR WINDOWS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
61 |
Status |
P |
Date |
2003-03-14 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-03-14 |
Time |
09:18 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-03-14 |
Time |
09:18 |
Sent To |
|
|
Notes |
2003-03-14 00:00:00 | SUBMITTAL 3-7-03 FOR 500 LB PICK POINT | | FRAMING. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
60 |
Status |
P |
Date |
2003-03-14 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-03-14 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-03-14 |
Time |
08:49 |
Sent To |
|
|
Notes |
2003-03-14 00:00:00 | SUBMITTAL 2-26-03 FOR ALUM. STOREFRONT | | DOOR (MISSILE IMPACT). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
59 |
Status |
P |
Date |
2003-02-21 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-03-11 |
Time |
09:37 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-02-21 |
Time |
15:39 |
Sent To |
|
|
Notes |
2003-02-21 00:00:00 | SUBMITTAL 2-20-03 FOR TRAINOR CURTAIN | | WALL SHOP DRAWINGS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
58 |
Status |
P |
Date |
2003-02-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-02-21 |
Time |
14:20 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-02-21 |
Time |
14:20 |
Sent To |
|
|
Notes |
2003-02-21 00:00:00 | SUBMITTAL 2-20-03 FOR STAIR #3 HANDRAIL/ | | GUARDRAIL SHOP DRAWINGS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
57 |
Status |
P |
Date |
2003-02-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-02-20 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-02-13 |
Time |
13:27 |
Sent To |
|
|
Notes |
2003-02-13 00:00:00 | SUBMITTAL 2-13-03 FOR WINDOW CLEANING | | FALL ARREST SYSTEM ATTACHMENT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
56 |
Status |
P |
Date |
2003-02-13 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-02-13 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-02-13 |
Time |
13:25 |
Sent To |
|
|
Notes |
2003-02-13 00:00:00 | SUBMITTAL 2-12-03 FOR STAIR #3 WINDOW | | WASHER BEAM |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
55 |
Status |
P |
Date |
2003-02-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-02-12 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-02-11 |
Time |
16:44 |
Sent To |
|
|
Notes |
2003-02-11 00:00:00 | STRUCTURAL SUBMITTAL 2-5-03 FOR 'FINAL | | LIGHT GUAGE TRUSS' |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
54 |
Status |
P |
Date |
2003-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-02-11 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-02-11 |
Time |
16:42 |
Sent To |
|
|
Notes |
2003-02-11 00:00:00 | STRUCTURAL REVISION SUBMITTED 2-5-03 FOR | | SHEETS SK113 TO SK115 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
53 |
Status |
P |
Date |
2003-01-30 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-02-06 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-01-30 |
Time |
16:56 |
Sent To |
|
|
Notes |
2003-01-30 00:00:00 | STRUCTURAL REVISION SUBMITTED ON 1-29-03 | | FOR SHEET SK-112 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
52 |
Status |
P |
Date |
2003-01-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-30 |
Time |
12:42 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-01-29 |
Time |
10:00 |
Sent To |
|
|
Notes |
2003-01-29 00:00:00 | BUILDING PLAN REVIEW | | ******PROVISO******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | SUBMITTAL ON 1-23-03 FOR OTIS ELEVATOR | | DRAWING NOS 519027-PN AND 519027-MR | | | | --PROVISO-- | | FBC 3003.2EACH ELEVATOR SHALL HAVE AN | | EMERGENCY EXIT AS REQUIRED BY ASME A17.1 | | | | --PROVISO-- | | FBC 3003.4.2(1)(B)EACH ELEVATOR CAR | | MUST HAVE A SUPPORT RAIL ON AT LEAST ONE | | WALL FOR USE BY PHYSICALLY HANDICAPPED | | PERSONS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
51 |
Status |
P |
Date |
2003-01-28 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-01-28 |
Time |
17:03 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-01-28 |
Time |
17:03 |
Sent To |
|
|
Notes |
2003-01-28 00:00:00 | SUBMITTAL ON 1-15-03 FOR ADDITIONAL | | WINDOWS ON THIRD FLOOR PLAN A-106 AND | | ELEVATION SHEET A-403 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
50 |
Status |
P |
Date |
2003-01-28 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-01-28 |
Time |
16:31 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-01-28 |
Time |
16:31 |
Sent To |
|
|
Notes |
2003-01-28 00:00:00 | BUILDING PLAN REVIEW | | ******PROVISO******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | SUBMITTAL ON 1-14-03 OF PRODUCT APPROVAL | | NOA# 02-0221.07 | | | | --PROVISO-- | | THE SUBMITTED COPIES OF THE YKK OUTSWING | | ALUMINUM OUTSWING DOOR PRODUCT APPROVAL | | NOA# 02-0221.07 ARE NOT COMPLETE.ALL | | COPIES ARE MISSING DRAWING SHEETS 3 AND | | 4 OF 16.SUBMIT COMPLETE COPIES.IN | | THE EVENT THAT THESE HAVE BEEN OMITTED | | AS 'NOT APPLICABLE', SUBMIT COMPLETE | | COPIES AND STRIKE OUT ANY SHEETS WHICH | | ARE NOT RELEVANT FOR THIS PROJECT. | | NOTE:TWO OF THE SUBMITTED COPIES ARE | | MISSING OTHER DRAWING SHEETS ALSO. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
49 |
Status |
P |
Date |
2003-01-28 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-01-28 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-01-28 |
Time |
16:14 |
Sent To |
|
|
Notes |
2003-01-28 00:00:00 | BUILDING PLAN REVIEW | | ******PROVISO******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | SUBMITTAL ON 1-14-03 FOR AEICOR METAL | | PRODUCTS INC. COPPER ROOFING DRAWING | | SHEETS 1 TO 4 | | | | --PROVISO-- | | SHEET 2 OF 4.TO PREVENT GALVANIC | | CORROSION BY ELECTROLYSIS, PROVIDE | | ISOLATION MEMBRANE BETWEEN THE COPPER | | AND ALUMINUM.RED-LINED ON THE PLANS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
48 |
Status |
P |
Date |
2003-01-28 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-01-28 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-01-28 |
Time |
14:24 |
Sent To |
|
|
Notes |
2003-01-28 00:00:00 | SUBMITTAL ON 1-13-03 OF STAIR SHOP DRG | | SHEETS M1,M1-A,M2,M2-A,M2-B |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
47 |
Status |
P |
Date |
2003-01-28 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-01-28 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-01-28 |
Time |
13:39 |
Sent To |
|
|
Notes |
2003-01-28 00:00:00 | SUBMITTAL ON 1-13-03 OF STRUCTURAL DRG | | SHEETS SK108 - SK111 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
46 |
Status |
P |
Date |
2003-01-28 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-01-28 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-01-28 |
Time |
13:37 |
Sent To |
|
|
Notes |
2003-01-28 00:00:00 | REVISION SUBMITTED ON 1-13-03 FOR STRUCT | | SHEETS SK100 - SK107 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
45 |
Status |
P |
Date |
2003-01-28 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-01-27 |
Time |
13:43 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-01-27 |
Time |
13:43 |
Sent To |
|
|
Notes |
2003-01-27 00:00:00 | SUBMITTAL ON 1-23-03 FOR LIGHT GAUGE | | METAL CEILING 500LB PICK POINTS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
44 |
Status |
P |
Date |
2002-12-31 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-12-31 |
Time |
08:20 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-12-31 |
Time |
08:20 |
Sent To |
|
|
Notes |
2002-12-31 00:00:00 | SUBMITTAL DATED 12-19-02 FOR | | FIRESTOPPING AT HEAD OF CMU WALL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
43 |
Status |
F |
Date |
2002-12-23 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-12-23 |
Time |
12:16 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-12-23 |
Time |
08:27 |
Sent To |
|
|
Notes |
2002-12-23 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | 12-13-02 SUBMITTAL FOR MANSARD TRUSS BY | | USA FRAMETEK LTD. | | | | FBC* 1606.1.6THE MANSARD TRUSS | | SUBMITTAL DOCUMENT SHEET 4, AND TRUSS | | DESIGN SHEETS 502\\TBR-1 AND 502\\BR-1 | | STATE THAT THE DESIGN IS FOR 110 MPH | | WIND UNDER UNIFORM BUILDING CODE 1997. | | THE ADOPTED CODE FOR THE CITY OF WEST | | PALM BEACH IS FLORIDA BUILDING CODE 2001 | | SUBMIT DESIGN DOCUMENTS DEMONSTRATING | | COMPLIANCE WITH THE 140 MPH WIND LOAD | | REQUIREMENT UNDER FLORIDA BUILDING CODE | | 2001. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
42 |
Status |
P |
Date |
2002-10-31 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-31 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-31 |
Time |
16:13 |
Sent To |
|
|
Notes |
2002-10-31 00:00:00 | SUBMITTAL DATED 10-31-02 FOR ROOF | | FRAMING SHOP DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
41 |
Status |
P |
Date |
2002-10-31 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-31 |
Time |
16:12 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-31 |
Time |
16:12 |
Sent To |
|
|
Notes |
2002-10-31 00:00:00 | SUBMITTAL DATED 10-31-02 FOR STEEL TRUSS | | SHOP DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
40 |
Status |
P |
Date |
2002-10-31 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-31 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-31 |
Time |
16:10 |
Sent To |
|
|
Notes |
2002-10-31 00:00:00 | SUBMITTAL DATED 10-31-02 FOR ROOF | | FRAMING SHOP DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
39 |
Status |
P |
Date |
2002-10-31 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-31 |
Time |
16:09 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-31 |
Time |
16:09 |
Sent To |
|
|
Notes |
2002-10-31 00:00:00 | SUBMITTAL DATED 10-31-02 FOR ROOF LEVEL | | SLAB REINFORCEMENT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
38 |
Status |
P |
Date |
2002-10-29 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-29 |
Time |
10:59 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-29 |
Time |
10:59 |
Sent To |
|
|
Notes |
2002-10-29 00:00:00 | REVISION SUBMITTED 10-10-02. SKETCH | | SHEETS SK78-R1, SK78 THRU SK84 AND SK87 | | THRU SK91 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
37 |
Status |
P |
Date |
2002-10-29 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-29 |
Time |
10:57 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-29 |
Time |
10:57 |
Sent To |
|
|
Notes |
2002-10-29 00:00:00 | SUBMITTAL DATED 10-18-02 FOR CLADDING | | COLUMN ANCHOR BOLT LAYOUT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
36 |
Status |
P |
Date |
2002-10-29 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-29 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-29 |
Time |
10:55 |
Sent To |
|
|
Notes |
2002-10-29 00:00:00 | SUBMITTAL DATED 10-18-02 FOR SECOND FLR | | TRUSS CONNECTIOPN DRAWINGS AND CALCS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
35 |
Status |
P |
Date |
2002-10-29 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-29 |
Time |
10:53 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-29 |
Time |
10:53 |
Sent To |
|
|
Notes |
2002-10-29 00:00:00 | SUBMITTAL DATED 10-18-02 FOR CHANDELIER | | SUPPORT STEEL SHOP DRAWINGS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
34 |
Status |
P |
Date |
2002-10-29 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-29 |
Time |
10:51 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-29 |
Time |
10:51 |
Sent To |
|
|
Notes |
2002-10-29 00:00:00 | SUBMITTAL DATED 10-18-02 FOR VULCRAFT | | STEEL ROOF DECK SHOP DRAWINGS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
33 |
Status |
P |
Date |
2002-10-16 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-16 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-16 |
Time |
11:42 |
Sent To |
|
|
Notes |
2002-10-16 00:00:00 | DRG SUBMITTED 10-4-02 FOR TEMPORARY | | WALKWAY. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
32 |
Status |
P |
Date |
2002-10-16 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-16 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-16 |
Time |
11:31 |
Sent To |
|
|
Notes |
2002-10-16 00:00:00 | AS-BUILT SURVEY SUBMITTED 10-4-02 FOR | | RINKER PLAYHOUSE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
31 |
Status |
P |
Date |
2002-10-16 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-16 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-16 |
Time |
11:03 |
Sent To |
|
|
Notes |
2002-10-16 00:00:00 | STRUCTURAL SKETCHES SK-85 AND SK-86 | | SUBMITTED 10-2-02. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
30 |
Status |
P |
Date |
2002-10-16 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-16 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-16 |
Time |
10:40 |
Sent To |
|
|
Notes |
2002-10-16 00:00:00 | ENGINEERING LETTER DATED 9-19-02 FOR | | REVIEW AND REPAIRS PERFORMED ON THE | | RINKER LOBBY SOUTH STRIP FOOTING. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
29 |
Status |
P |
Date |
2002-10-16 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-16 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-16 |
Time |
10:24 |
Sent To |
|
|
Notes |
2002-10-16 00:00:00 | REINFORCEMENT DRGS SUBMITTED 9-26-02 FOR | | SLABS AT THE VALET RAMP. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
28 |
Status |
P |
Date |
2002-10-16 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-16 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-16 |
Time |
10:13 |
Sent To |
|
|
Notes |
2002-10-16 00:00:00 | REINFORCEMENT DRGS SUBMITTED 9-26-02 FOR | | THIRD LEVEL SLAB |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
27 |
Status |
P |
Date |
2002-10-15 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-15 |
Time |
16:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-15 |
Time |
16:45 |
Sent To |
|
|
Notes |
2002-10-15 00:00:00 | REINFORCEMENT DRGS SUBMITTED 9-26-02 FOR | | SECOND LEVEL SLAB. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
26 |
Status |
P |
Date |
2002-10-15 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-15 |
Time |
16:30 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-15 |
Time |
16:30 |
Sent To |
|
|
Notes |
2002-10-15 00:00:00 | STRUCTURAL STEELWORK DRG SUBMITTED | | 9-26-02 FOR CONNECTION DETAILS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
25 |
Status |
P |
Date |
2002-10-15 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-15 |
Time |
16:20 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-15 |
Time |
16:20 |
Sent To |
|
|
Notes |
2002-10-15 00:00:00 | REINFORCEMENT DRGS SUBMITTED 9-26-02 FOR | | MEZZANINE LEVEL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
24 |
Status |
P |
Date |
2002-10-15 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-15 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-15 |
Time |
15:55 |
Sent To |
|
|
Notes |
2002-10-15 00:00:00 | REINFORCEMENT DRG REVISION SUBMITTED | | 9-26-02 FOR VALET RAMP RETAINING WALL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
23 |
Status |
P |
Date |
2002-10-15 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-15 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-15 |
Time |
15:53 |
Sent To |
|
|
Notes |
2002-10-15 00:00:00 | STRUCTURAL STEEL SHOP DRG SUBMITTED | | 9/26/02 FOR STAIR #3. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
22 |
Status |
P |
Date |
2002-10-15 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-15 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-15 |
Time |
15:23 |
Sent To |
|
|
Notes |
2002-10-15 00:00:00 | STRUCTURAL REVISION SUBMITTED 9-13-02 | | FOR ROOF EDGE STEELWORK DETAIL, CMU WALL | | SECTION AND INTERIOR NON-LOADBEARING | | MASONRY NOTES. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
21 |
Status |
P |
Date |
2002-10-15 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-10-15 |
Time |
11:57 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-10-15 |
Time |
11:57 |
Sent To |
|
|
Notes |
2002-10-15 00:00:00 | SUBMITTAL DATED 9-26-02.STEEL SHOP | | DRAWINGS FOR THIRD FLOOR FRAMING. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
20 |
Status |
P |
Date |
2002-09-27 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-09-27 |
Time |
10:18 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-09-27 |
Time |
10:18 |
Sent To |
|
|
Notes |
2002-09-27 00:00:00 | SUBMITTAL DATED 9-27-02 FOR COVERED | | WALKWAY. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
19 |
Status |
P |
Date |
2002-09-27 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-09-27 |
Time |
09:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-09-27 |
Time |
09:45 |
Sent To |
|
|
Notes |
2002-09-27 00:00:00 | SUBMITTAL DATED 9-25-02 FOR RINKER LOBBY | | CURTAIN WALL FROM TRAINOR GLASS COMPANY |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
18 |
Status |
P |
Date |
2002-09-19 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-09-19 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-09-19 |
Time |
09:08 |
Sent To |
|
|
Notes |
2002-09-19 00:00:00 | SUBMITTAL, DATED 9-13-02, FOR ENTRANCE | | AREA SLAB ON GRADE EDGE REINFORCEMENT | | AND FILLED CELL REINFORCEMENT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
17 |
Status |
P |
Date |
2002-09-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-09-12 |
Time |
14:33 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-09-12 |
Time |
14:33 |
Sent To |
|
|
Notes |
2002-09-12 00:00:00 | REVISION SUBMITTED 9/6/02 FOR WIND LOAD | | PLAN |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
16 |
Status |
P |
Date |
2002-09-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-09-12 |
Time |
14:30 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-09-12 |
Time |
14:30 |
Sent To |
|
|
Notes |
2002-09-12 00:00:00 | REVISION SUBMITTED 9-3-02. SHEETS SK62 | | THRU' SK73 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
15 |
Status |
P |
Date |
2002-09-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-09-12 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-09-12 |
Time |
14:28 |
Sent To |
|
|
Notes |
2002-09-12 00:00:00 | SUBMITTAL DATED 9-3-02 FOR GROUND LEVEL | | SLAB REINFORCEMENT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
14 |
Status |
P |
Date |
2002-09-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-09-12 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-09-12 |
Time |
14:26 |
Sent To |
|
|
Notes |
2002-09-12 00:00:00 | SUBMITTAL DATED 8-30-02 FOR SECOND FLOOR | | STRUCTURAL STEEL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
13 |
Status |
P |
Date |
2002-09-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-09-12 |
Time |
14:23 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-09-12 |
Time |
14:23 |
Sent To |
|
|
Notes |
2002-09-12 00:00:00 | SUBMITTAL DATED 8-29-02 FOR VEHICLE RAMP | | AND VALET OFFICE |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
12 |
Status |
P |
Date |
2002-09-05 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-09-05 |
Time |
09:42 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-09-05 |
Time |
09:42 |
Sent To |
|
|
Notes |
2002-09-05 00:00:00 | SIGNED AND SEALED LETTER SUBMITTAL DATED | | RECEIVED 9-5-02 FROM ZEIDLER GRINNELL TO | | SUPPORT THE SUBMITTAL DATED 8-26-02 FOR | | TPO ROOF MEMBRANE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
11 |
Status |
P |
Date |
2002-08-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-08-30 |
Time |
11:10 |
Rev Time |
0.50 |
Received By |
rbrown |
Date |
2002-08-30 |
Time |
11:09 |
Sent To |
|
|
Notes |
2002-08-30 00:00:00 | SUBMITTAL DATED 8-28-02 FOR GROUND LEVEL | | BEAM REINF. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
10 |
Status |
F |
Date |
2002-08-29 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-08-29 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-08-29 |
Time |
11:09 |
Sent To |
|
|
Notes |
2002-08-29 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | SUBMITTAL DATED 8-26-02 FOR TPO ROOF | | MEMBRANE. | | | | 1) THE FACTORY MUTUAL TEST DATA IS NOTED | | BUT SITE-SPECIFIC DETAILS ARE REQUIRED. | | THE SUBMITTAL INCLUDES DETAILS FOR A | | NUMBER OF DIFFERENT MATERIAL AND SYSTEM | | COMBINATIONS BOTH ADHERED AND | | MECHANICALLY ATTACHED.SUBMIT COPIES OF | | A SIGNED AND SEALED LETTER FROM ZEIDLER | | GRINNELL OR WALTER P MOORE & ASSOCIATES | | SPECIFYING WHICH SYSTEM COMPONENTS AND | | THICKNESS ARE PROPOSED FOR THIS BUILDING | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
9 |
Status |
P |
Date |
2002-08-23 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-08-21 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-08-21 |
Time |
12:04 |
Sent To |
|
|
Notes |
2002-08-21 00:00:00 | BUILDING PLAN REVIEW | | ******PROVISO******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | SUBMITTAL DATED 8-20-02 FOR RINKER LOBBY | | CURTAIN WALL FROM TRAINOR GLASS COMPANY. | | | | --PROVISO-- | | THE SUBMITTED STOREFRONT DOOR PRODUCT | | APPROVAL (NOA NO. 00-0315.01) IS MISSING | | DRAWING SHEETS 1 TO 16 OF 16.SUBMIT A | | COMPLETE PRODUCT APPROVAL.ALSO, ITEM 8 | | ON TRAINOR GLASS' CALCULATION SHEET | | 2 OF 2 SPECIFICALLY REFERS TO 'KAWNEER | | SERIES 350 STOREFRONT DOORS'.THIS DOES | | NOT CORRESPOND TO THE PRODUCT APPROVAL | | SUBMITTED, FOR WHICH THE ALLOWABLE WIND | | PRESSURES CANNOT BE CHECKED DUE TO THE | | MISSING DRAWING SHEETS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
P |
Date |
2002-08-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-08-12 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-08-12 |
Time |
15:45 |
Sent To |
|
|
Notes |
2002-08-12 00:00:00 | RINKER LOBBY STRUCTURAL REVISION | | SKETCHES SK-03 TO SK-11 DATED 6-12-02 | | AND 6-24-02 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2002-08-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-08-12 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-08-12 |
Time |
10:55 |
Sent To |
|
|
Notes |
2002-08-12 00:00:00 | RINKER LOBBY REVISED SHEETS A-206, A-207 | | AND A-207A DATED 6-24-02 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2002-07-30 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2002-07-30 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-07-30 00:00:00 | SHUTTER FOR EMERGENCY USE ONLY AT FRONT | | DOORS AND NEW EMERGENCY EXIT DOOR 3'X7' | | IN LOBBY REVIEWED AND APPROVED BY | | BUILDING OFFICIAL . |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2002-07-16 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-07-16 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-07-16 |
Time |
11:24 |
Sent To |
|
|
Notes |
2002-07-16 00:00:00 | BUILDING PLAN REVIEW | | ******PROVISO******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | --PROVISO-- | | FBC* 104.2.1.1ROOF COVERING PRODUCT | | APPROVAL SHALL BE SUBMITTED FOR THE ROOF | | COVERING SYSTEM TO BE USED (FBC 1504.3) | | | | --PROVISO-- | | FBC 1606.1.4 SUBMIT WINDOW AND DOOR | | PRODUCT APPROVALS FOR THE EXTERIOR DOOR | | AND WINDOW SYSTEMS TO BE USED. | | | | --PROVISO-- | | FBC 11-4.9.4(2)STAIRWAY HANDRAILS. | | SHEET A-810, DETAIL 6.TO AVOID | | AMBIGUITY, THE DIMENSION LINE MARKERS | | SHALL POSITION THE ACTUAL INTERSECTION | | OF HORIZONTAL TO SLOPING HANDRAIL SO | | THAT THE HANDRAIL CONTINUES TO SLOPE | | BEYOND THE THE BOTTOM RISER FOR A | | DISTANCE EQUAL TO THE WIDTH OF ONE TREAD | | AND THEN EXTENDS HORIZONTALLY FOR 12" | | (FIG. 19C) | | | | --PROVISO-- | | FBC 11-4.31PUBLIC TELEPHONES. | | | | EACH ACCESSIBLE TELEPHONE, AND 25% (BUT | | NOT LESS THAN ONE) OF THE REMAINING | | TELEPHONES SHALL BE EQUIPPED WITH VOLUME | | CONTROL (REF: FBC 11-4.1.3(17)(B)) | | | | ONE PUBLIC TEXT TELEPHONE IS REQUIRED | | (REF: FBC 11-4.1.3(17)(C)(I)) |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2002-06-14 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-06-14 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-06-14 |
Time |
12:51 |
Sent To |
|
|
Notes |
2002-06-14 00:00:00 | BUILDING PLAN REVIEW | | ******PROVISO******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | --PROVISO-- | | THE COMMENTS FROM THE BUILDING PLAN | | REVIEW DATED 6/5/02 WILL BE ADDRESSED BY | | REVISED PLANS SUBMITTED AT THE TIME OF | | PERMIT ISSUANCE, SUBJECT TO SUBSEQUENT | | REVIEW. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2002-06-05 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-06-05 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-06-05 |
Time |
16:21 |
Sent To |
|
|
Notes |
2002-06-05 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | ARE NUMBERED AS PER THE BUILDING PLAN | | REVIEW OF 5/28/02: | | | | 2) RESPONSE LETTER OF 5/31/02 IS NOTED. | | IMPACT FEES MUST BE PAID TO PALM BEACH | | COUNTY, THE PLANS STAMPED BY THEM AND A | | COPY OF THE RECEIPT SUBMITTED TO CITY OF | | WEST PALM BEACH BUILDING DEPARTMENT, | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | 4) RESPONSE LETTER OF 5/31/02 IS NOTED. | | FBC* 104.2.1.1 ROOF COVERING PRODUCT | | APPROVAL SHALL BE SUBMITTED FOR THE ROOF | | COVERING SYSTEM TO BE USED (FBC 1504.3) | | | | 7) RESPONSE LETTER OF 5/31/02 IS NOTED. | | FBC 1606.1.4SUBMIT WINDOW AND DOOR | | PRODUCT APPROVALS FOR THE EXTERIOR DOOR | | AND WINDOW SYSTEMS TO BE USED. | | | | 9) FBC 13-103THE SUBMITTED ENERGY CODE | | COMPLIANCE FORMS SHALL BE AMENDED TO | | SHOW THE PERMITTING OFFICE AS 'WEST PALM | | BEACH' AND THE JURISDICTION NO. AS | | 604700. | | | | 11) THE ADDITION OF PAINTED STRIPES AND | | EGRESS WARNING ON SHEETS LS-103 AND | | A-103 ARE NOTED.THE ADDITION OF | | PAINTED STRIPES ON SHEET LS-105, SECOND | | LEVEL, WAS NOT REQUIRED AND IS NOT | | NECESSARY. | | | | 21) FBC 104.2.1EXTERIOR ALUMINUM | | CLADDING PANELS.THE ADDITION OF | | EXPANSION FASTENERS IS NOTED, BUT THEY | | ARE SHOWN ONLY DIAGRAMMATICALLY. | | ANNOTATE THE DETAIL TO STATE THE TYPE, | | SIZE AND SPACING OF THE FASTENERS.ALSO | | STATE WHETHER THE FASTENING DETAIL IS | | 'TYPICAL ', OR IS IT APPLICABLE ONLY TO | | THE 'MEDALLION AND APPLIQUES'? | | | | 23) FBC 11-4.1.2(5)ACCESSIBLE PARKING. | | THE NOTE ADDED TO SHEETS LS-101, LS-102, | | A-101 AND A-102 DOES NOT REFER TO | | ACCESSIBILTY, AND SHOULD BE AMENDED TO | | START, "ACCESSIBLE PARKING:IT IS THE | | OWNERS INTENTION......" | | | | 24) FBC 11-4.8.3THE LEVEL 1 PARKING | | RAMP UP TO THE ELEVATOR LOBBY SHALL HAVE | | A MINIMUM CLEAR WIDTH OF 36".AMEND THE | | PLAN TO DEMONSTRATE COMPLIANCE.ALSO | | THE LENGTH OF THE RAMP SHALL BE ADDED | | TO ENSURE A MAXIMUM SLOPE OF 1 IN 12. | | | | 27) FBC 11-4.9.4(2)STAIRWAY HANDRAILS. | | THE RESPONSE LETTER OF 5/31/02 IS NOTED, | | BUT THE DIMENSION LINE MARKERS SHALL | | POSITION THE ACTUAL INTERSECTION OF | | HORIZONTAL TO SLOPING HANDRAIL TO AVOID | | AMBIGUITY. | | | | 29) FBC 11-4.31PUBLIC TELEPHONES. | | THE RESPONSE LETTER OF 5/31/02 DOES NOT | | ADDRESS THE TELEPHONES WHICH ARE REMOTE | | FROM THE VICINITY OF THE TOILETS AND | | DRESSING ROOM (EG. PREFUNCTION HALL, | | G-09 TELEPHONE ALCOVE,AND CORRIDOR 2.03) | | ARCHITECT HAS ADVISED THAT REVISED | | SHEETS ARE BEING PREPARED. | | | | 30) FBC 11-4.15DRINKING FOUNTAINS. | | THE PLANS SHALL BE AMENDED TO SHOW | | COMPLIANCE WITH THE SPOUT HEIGHT AND | | VERTICAL CLEARANCE REQUIREMENTS | | (FIG. 27A).ARCHITECT HAS ADVISED THAT | | REVISED SHEETS ARE BEING PREPARED. | | | | 31) FBC 11-4.19 LAVATORIES. THE REVISION | | TO 11/A-208 IS NOTED.ADD DIMENSIONS TO | | DEMONSTRATE COMPLIANCE WITH THE KNEE | | CLEARANCE DIMENSIONS OF 8" MINIMUMAND | | 27" MINIMUM (FIG. 31) | | | | 34) FBC 11-4.35 DRESSING ROOMS.THE | | MIRRORS ARE TOO FAR TO AFFORD VIEW TO | | A PERSON ON THE BENCH. ADDITIONAL | | MIRRORS ARE REQUIRED.A SUGGESTED | | LOCATION ON THE 6' HIGH STUD WALLS SHOWN | | ON SECTION 1B/A-209. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-05-28 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-05-28 |
Time |
19:04 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-05-28 |
Time |
19:04 |
Sent To |
|
|
Notes |
2002-05-29 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | ARE NUMBERED AS PER THE BUILDING PLAN | | REVIEW OF 4/12/02: | | | | 1) RESPONSE LETTER OF 4/22/02 IS NOTED. | | A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) RESPONSE LETTER OF 4/22/02 IS NOTED. | | IMPACT FEES MUST BE PAID TO PALM BEACH | | COUNTY, THE PLANS STAMPED BY THEM AND A | | COPY OF THE RECEIPT SUBMITTED TO CITY OF | | WEST PALM BEACH BUILDING DEPARTMENT, | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | 3) FBC* 104.2.4CONTRARY TO THE LETTER | | OF RESPONSE, DATED 4/22/02, NO SIGNED | | AND SEALED SITE SURVEY DRAWING WAS | | SUBMITTED. | | | | 4) RESPONSE LETTER OF 4/22/02 IS NOTED. | | FBC* 104.2.1.1 ROOF COVERING PRODUCT | | APPROVAL SHALL BE SUBMITTED FOR THE ROOF | | COVERING SYSTEM TO BE USED (FBC 1504.3) | | | | 7) RESPONSE LETTER OF 4/22/02 IS NOTED. | | FBC 1606.1.4 WINDOW AND DOOR PRODUCT | | APPROVALS.SUBMIT PRODUCT APPROVALS FOR | | THE EXTERIOR DOOR AND WINDOW SYSTEMS TO | | BE USED. | | | | 9) FBC 13-103THREE COPIES OF THE HVAC | | LOAD ANALYSIS WERE RECEIVED BUT ENERGY | | CODE COMPLIANCE FORMS SHALL BE SUBMITTED | | TO DEMONSTRATE COMPLIANCE WITH THE CODE. | | | | 11) FBC 1019.1.1EXIT FROM ASSEMBLY RMS | | SHEET LS-105, SECOND FLOOR.ADD PAINTED | | STRIPES AND WARNING: FIRE EGRESS, KEEP | | CLEAR, ON SHEETS LS-103 AND A-103, | | BETWEEN DOOR G22 AND THE EXTERNAL RAMP | | AND STEPS. | | | | 16) FBC 1003.1 OCCUPANCY OF 'UNASSIGNED' | | ROOM, SHEET LS-106.IF, AS STATED IN | | THE LETTER OF RESPONSE, THE EGRESS | | CAPACITY HAS BEEN ASSESSED BASED ON | | OFFICE USE, CHANGE THE ROOM DESIGNATION | | FROM 'UNASSIGNED' TO 'OFFICE' ON | | SHEETS LS-106 AND A-106. | | | | 17) IT IS NOTED FROM THE LETTER OF | | RESPONSE, DATED 4/22/02, THAT STAIR #3 | | IS NOT INTENDED FOR USE AS AN EXIT. | | THEREFOR THE COMMON PATH OF TRAVEL | | (FBC 202 AND FBC 1020.6) FROM COMMUNITY | | CONFERENCE ROOM 3-003 AND RECEPTION | | 3-002 MAY EXCEED 100 FT.SHOW THE | | PROPOSED FURNITURE LAYOUT FOR THESE | | ROOMS ON THE LIFE SAFETY PLAN AND SHOW | | THAT THE COMMON PATH OF TRAVEL TO THE | | NORTH SECTION OF CORRIDOR 3-010 DOES NOT | | EXCEED 100 FT.ALTERNATIVELY, AMEND THE | | EGRESS SIGNS AND DOOR LOCKS TO PROVIDE A | | SEPARATE ROUTE VIA CORRIDOR 3-024. | | | | 21) FBC 104.2.1 EXTERIOR ALUMINUM | | CLADDING PANELS.THE REVISED DETAIL | | 8/A-705 STILL DOES NOT SHOW THE MEANS OF | | ATTACHING THE ALUMINUM FACED PLYWOOD | | PANELS TO THE BUILDING FACADE. | | | | 23) FBC 11-4.1.2(5)ACCESSIBLE PARKING. | | ADD A NOTE, TO THE PARKING LEVEL PLANS, | | STATING THAT THE VALET PARKING SERVICE | | WILL BE THE MEANS OF SATISFYING THE | | REQUIREMENT FOR ACCESSIBLE PARKING. | | | | 24) FBC 11-4.8LEVEL 1 PARKING, SHEET | | LS-101.CONTRARY TO THE LETTER OF | | RESPONSE, THE ELEVATOR LOBBY IS SHOWN AS | | EL 80'-6", NOT EL 80'-0", SO THERE IS AN | | ELEVATION CHANGE.SHOW/ANNOTATE THE | | RAMP FROM THE PARKING LEVEL UP TO THE | | ELEVATOR LOBBY LEVEL FOR ACCESSIBILITY. | | | | 27) FBC 11-4.9.4(2)STAIRWAY HANDRAILS. | | SHEET A-810, DETAIL 6 RAIL AT WALL. | | WITH REFERENCE TO THE LETTER OF RESPONSE | | DATED 4/22/02, THE QUOTATION FROM THE | | CODE IS INCOMPLETE.THE PARAGRAPH GOES | | ON TO REQUIRE THAT THE HANDRAIL CONTINUE | | TO SLOPE BEYOND THE BOTTOM RISER FOR A | | DISTANCE EQUAL TO THE WIDTH OF ONE TREAD | | AND THEN EXTEND HORIZONTALLY FOR 12" | | (FIG. 19C).ON SHEET A810, NEITHER THE | | SLOPED OR HORIZONTAL EXTENSIONS ARE | | DIMENSIONED INDIVIDUALLY TO DEMONSTRATE | | COMPLIANCE. | | | | 29) FBC 11-4.31PUBLIC TELEPHONES.THE | | RESPONSE RELATING TO 'FOOTPRINT'IS NOTED | | BUT COMPLIANCE SHALL BE DEMONSTRATED BY | | ADDING DIMENSIONS TO THE PLANS, | | INCLUDING SHEET A103 (AT G-03 AND G-09) | | AND SHEET A105 (AT 2-03, TEL. ALCOVE). | | THE PLANS SHALL ALSO BE AMENDED TO SHOW | | THE INSTALLATION HEIGHT AND FACILITIES | | PROVISION GIVEN IN FBC 11-4.1.3(17). | | | | 30) FBC 11-4.15DRINKING FOUNTAINS. THE | | RESPONSE RELATING TO 'FOOTPRINT'IS NOTED | | BUT THE PLANS SHALL BE AMENDED TO | | DEMONSTRATE COMPLIANCE WITH THE SPOUT | | HEIGHT AND VERTICAL CLEARANCE | | REQUIREMENTS (FIG. 27A) | | | | 31) FBC 11-4.19LAVATORIES.AMEND THE | | PLANS TO SHOW THE LAVATORY LEGROOM | | CLEARANCES AND A MAXIMUM HEIGHT OF 40" | | TO THE BASE OF THE MIRROR (FIG. 31) | | | | 32) FBC 11-4.16WATER CLOSET.THE | | REVISIONS TO SHEETS A-208, A-209 AND | | A-210 ARE NOTED, BUT NORTH AND WEST | | ELEVATIONS, 3/A-208, STILL SHOW TOILET | | SEATS AT 20" ABOVE FLOOR.AMEND TO 18". | | | | 34) FBC 11-4.35 DRESSING ROOMS, SHEET | | A-209.THE AMENDMENTS MADE ARE NOTED, | | BUT THE PLANS SHALL BE AMENDED TO | | DEMONSTRATE COMPLIANCE WITH 11-4.35.5 | | WHICH REQUIRES THE PROVISION OF A | | COMPLIANT FULL LENGTH MIRROR. | | | | 35) FBC 403.1.4.1BARS TO COMPLY WITH | | FBC 11-4.5.2.THE PROPOSAL TO PROVIDE | | BAR SERVICE AT ACCESSIBLE SEATING | | ADJACENT EACH BAR IS NOTED.ADD A NOTE | | TO THE PLANS, AT EACH BAR LOCATION, TO | | DEMONSTRATE THE PROVISION OF ACCESSIBLE | | SEATING AND ASSOCIATED BAR SERVICE. | | | | NOTE: COMMENTS 2, 3, 5, 6, 7, 14 AND 17 | | FROM THE FIRE DEPARTMENT PLAN REVIEW #2, | | DATED 5/21/02, SHALL ALSO BE ADDRESSED. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-04-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-04-12 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-04-12 |
Time |
16:40 |
Sent To |
|
|
Notes |
2002-04-12 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | 1) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT WILL BE REQUIRED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | COPY OF RECEIPT SUBMITTED TO CITY OF | | WEST PALM BEACH BUILDING DEPARTMENT, | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | 3) FBC* 104.2.4SITE SURVEY.A SIGNED | | AND SEALED SURVEY DRAWING PREPARED BY A | | QUALIFIED SURVEYOR IS REQUIRED. | | | | 4) FBC* 104.2.1.1ROOF COVERING PRODUCT | | APPROVAL SHALL BE SUBMITTED FOR THE ROOF | | COVERING SYSTEM TO BE USED (FBC 1504.3). | | | | 5) FBC* 1804.2.2SUBMIT A GEOTECHNICAL | | REPORT. | | | | 6) INFORMATIVE: | | FBC* 104.4.5 SPECIAL FOUNDATION PERMIT | | THE BUILDING OFFICIAL MAY, AT HIS | | DISCRETION, ISSUE A SPECIAL PERMIT | | FOR THE FOUNDATION ONLY, UPON WRITTEN | | REQUEST BY THE OWNER AND CONTRACTOR. THE | | HOLDER OF SUCH SPECIAL PERMIT IS PROCEED | | ING AT HIS/HER OWN RISK AND WITHOUT | | ASSURANCE THAT A PERMIT FOR THE | | REMAINDER OF THE WORK WILL BE GRANTED | | AND THAT CORRECTIONS WILL NOT BE | | REQUIRED IN ORDER TO MEET THE PROVISIONS | | OF THE TECHNICAL CODES. | | | | 7) FBC 1606.1.4WINDOW AND DOOR PRODUCT | | APPROVALS.SUBMIT PRODUCT APPROVALS FOR | | THE EXTERIOR DOOR AND WINDOW SYSTEMS TO | | BE USED. | | | | 8) FBC 11-4.1.2ACCESSIBILITY TO THE | | EXISTING KRAVIS CENTER BUILDING SHALL BE | | MAINTAINED THROUGHOUT THE CONSTRUCTION. | | | | 9) FBC 13-103COMPLIANCE SHALL BE | | DEMONSTRATED BY SUBMITTAL OF APPROPRIATE | | ENERGY CODE COMPLIANCE FORMS. | | | | 10) FBC 1003.3EGRESS CAPACITY OF | | STAIRWAYS.SHEET LS-105 'FLOOR AREA/ | | OCCUPANCY CALCS'.THE CALCULATED | | COMBINED STAIRWAY WIDTH REQUIRED IS | | 275.1".WHILST SHEETS A-201 TO A-204 DO | | NOT GIVE DIMENSIONS FOR THE FLIGHT WIDTH | | IT WOULD APPEAR THAT THE FOUR STAIRWAYS | | DO NOT HAVE THE REQUIRED COMBINED EXIT | | WIDTH.ADD DIMENSIONS TO SHOW THE WIDTH | | OF EACH FLIGHT AND AMEND/JUSTIFY THE | | STAIRWAYS FOR THE REQUIRED EXIT CAPACITY | | | | 11) FBC 1019.1.1EXIT FROM ASSEMBLY RMS | | SHEET LS-105, SECOND FLOOR.AS THIS IS | | NOT THE LEVEL OF EXIT DISCHARGE, EACH OF | | THE ASSEMBLY OCCUPANCY ROOMS SHALL BE | | PROVIDED WITH A MAIN ENTRANCE/EXIT THAT | | CONNECTS TO A STAIRWAY OR RAMP LEADING | | TO A STREET (AND CAN ACCOMMODATE 50% OF | | OF THE OCCUPANT LOAD).STAIR NO. 3 AND | | STAIR NO. 4 DISCHARGE , AT GROUND LEVEL, | | VIA A LOBBY AND LOADING DOCK | | RESPECTIVELY, NOT DIRECTLY TO A STREET | | OR OPEN SPACE LEADING TO A STREET. | | SHOW HOW THIS REQUIREMENT WILL BE MET. | | | | 12) FBC 1004.1.2EGRESS FROM 'PROJECTS' | | OFFICE SUITE. SHEET LS-105, SECOND FLOOR | | THE TRAVEL DISTANCE TO THE EXIT ACCESS | | DOOR FROM THE MOST REMOTE CORNER OF THE | | OFFICE EXCEEDS 75FT (APPROX. 88FT).ADD | | A SECOND EGRESS DOOR FROM THIS AREA. | | | | 13) FBC 1004.1.2EGRESS FROM 'PROGRAM.' | | OFFICE SUITE.SHEET LS-106, THIRD FLOOR | | THE TRAVEL DISTANCE TO THE EXIT ACCESS | | DOOR FROM THE MOST REMOTE CORNER OF THE | | OFFICE EXCEEDS 75FT (APPROX. 84FT).ADD | | A SECOND EGRESS DOOR FROM THIS AREA. | | | | 14) FBC 1004.1.4EGRESS FROM 'TRAINING | | SPACE/RECORDING STUDIO', SHEET LS-105. | | THIS SPACE CAN ACCOMMODATE MORE THAN 50 | | PEOPLE SO BOTH EXIT ACCESS DOORS ARE | | REQUIRED.THE TWO EXIT ACCESS DOORS | | CURRENTLY HAVE A SEPARATION OF 24FT | | WHICH IS LESS THAN THE MINIMUM REQUIRE- | | MENT OF 'HALF OF THE MAXIMUM OVERALL | | DIAGONAL (APPROX. 28FT).REPOSITION THE | | DOORS TO COMPLY. | | | | 15) FBC* 104.2.1.2THEATRE LAB A AND B, | | SHEET LS-105.AMEND THE PLANS TO | | DESCIBE THE OCCUPANCY OF THESE ROOMS. | | ARE THEY ASSEMBLY OCCUPANCY?IF THEY | | HAVE AN OCCUPANCY OF MORE THAN 50 PEOPLE | | THEN TWO EXIT ACCESS ARE REQUIRED | | (FBC 1004.1.2) AND THE DISTANCE BETWEEN | | THESE SHALL BE NO LESS THAN HALF THE | | MAXIMUM OVERALL DIAGONAL (FBC 1004.1.4). | | | | 16) FBC 1003.1 OCCUPANCY OF 'UNASSIGNED' | | ROOM, SHEET LS-106.THE OCCUPANCY FOR | | THIS ROOM SHALL BE SPECIFIED.IF IT IS | | STILL UNASSIGNED, THEN SPECIFY THE MOST | | HEAVILY OCCUPIED OF THE POTENTIAL USES. | | TO COMPLY WITH FBC 1012.12, OUTWARD | | OPENING DOORS MAY BE REQUIRED. | | | | 17) FBC 1012.1.2THE FOLLOWING DOORS | | SHALL BE REVERSED TO OPEN IN THE | | DIRECTION OF ESCAPE: | | -DOOR G26 (SHEET A-103) BETWEEN THE | | PREFUNCTION HALL AND SERVICE CORRIDOR | | -DOOR 253 (SHEET A-105) BETWEEN | | CORRIDORS 2-03 AND 2-02 | | -DOOR 340 (SHEET A-106) BETWEEN | | CORRIDORS 3-010 AND 3-001A | | | | 18) FBC 704.1PARKING GARAGE OCCUPANCY | | SEPARATION.THE AUTOMOBILE PARKING | | SHALL BE SEPARATED FROM THE LEVEL 1 | | ELECTRICAL AND ELEVATOR MACHINE ROOMS | | AND THE LEVEL 2 STORAGE, ELECTRICAL AND | | TEL/DATA ROOM BY ONE HOUR FIRE RESISTANT | | CONSTRUCTION, MINIMUM. | | | | 19) FBC 403.3PROJECTION ROOM.NORTH- | | SOUTH SECTION THROUGH BANQUETING HALL, | | SHEET A-411.CLARIFY THE USE OF THIS | | ROOM.IF CELLULOSE NITRATE FILM OR | | CELLULOSE ACETATE OR OTHER SAFETY FILM | | IS TO BE USED, COMPLIANCE WITH THIS | | REQUIREMENT MUST BE DEMONSTRATED. | | | | 20) FBC 2405.2IN ALL LOCATIONS WHERE | | GLAZING IS IN A 'HAZARDOUS LOCATION' IT | | SHALL BE SAFETY GLASS, SATISFYING THE | | REQUIREMENTS OF THE CONSUMER PRODUCT | | SAFETY COMMISSION 16, CODE OF FEDERAL | | REGULATIONS, PART 1201 (CPSC 16-CFR, | | PART 1201).SUBMIT DETAILS TO | | DEMONSTRATE COMPLIANCE. | | | | 21) FBC 104.2.1EXTERIOR ALUMINUM | | CLADDING PANELS.AMEND THE PLANS TO | | DESCRIBE THE ATTACHMENT OF THE ALUMINUM- | | FACED PLYWOOD TO THE BUILDING FACADE. | | | | 22) FBC 3003.4STRETCHER REQUIREMENTS | | FOR ELEVATORS.ANNOTATE THE PLANS TO | | DEMONSTRATE COMPLIANCE WITH THE | | REQUIREMENT FOR AT LEAST ONE PASSENGER | | ELEVATOR TO ACCOMMODATE AN AMBULANCE | | STRETCHER 76" LONG AND 24" WIDE IN THE | | HORIZONTAL POSITION.ALSO, THE ELEVATOR | | SHALL BE IDENTIFIABLE. | | | | 23) FBC 11-4.1.2(5)ACCESSIBLE PARKING. | | WITH A TOTAL OF 116 SPACES PROVIDED, AT | | LEAST 5 MUST BE ACCESSIBLE. SHEET LS-101 | | LEVEL 1 PARKING, DOES NOT SHOW ANY | | DESIGNATED ACCESSIBLE PARKING.THE | | 'ACCESSIBLE' PARKING SHOWN ON | | SHEET LS-102, LEVEL 2 PARKING, IS NOT | | COMPLIANT IN RESPECT OF AN ACCESSIBLE | | ROUTE (FBC 11-4.6.2(1)), AND WIDTH OF | | PARKING SPACE AND ACCESSIBLE AISLES | | (FBD 11-4.6.3).REF FIGURE 9A | | | | 24) FBC 11-4.8LEVEL 1 PARKING, | | SHEET LS-101.SHOW/ANNOTATE THE RAMP | | FROM PARKING LEVEL UP TO ELEVATOR LOBBY | | LEVEL FOR ACCESSIBILITY. | | | | 25) FBC 1015.3WALKWAY GUARDRAILS. | | SHEET A-708 SHOWS THE WALKWAY GUARDRAIL | | ON THE WEST ELEVATION (SHEET A-403) AS | | HAVING A RAIL SPACING OF 4" CLEAR.THIS | | WILL BE SUBJECT TO FIELD VERIFICATION BY | | THE INSPECTOR.NOTE THAT THE CURRENT | | PROPOSAL MAKES NO ALLOWANCE FOR | | CONSTRUCTION TOLERANCES, AS THE CODE | | REQUIREMENT IS FOR A MAXIMUM SPACING OF | | 4" CLEAR.THE POTENTIAL FOR CODE | | VIOLATION WILL BE HIGH IF THE SPACING IS | | NOT REDUCED TO ACCOUNT FOR CONSTRUCTION | | TOLERANCES.THE SAME COMMENT APPLIES TO | | THE 4" VERTICAL GAPS ON SHEET A-708, | | DETAIL 4. | | | | 26) FBC 11-4.8.5RAMP HANDRAILS.THE | | RAMP AT THE LOADING BAY DOCK SHALL BE | | PROVIDED WITH HANDRAILS THAT COMPLY WITH | | THIS REQUIREMENT IN ADDITION TO THE | | PROPOSED GUARDRAIL. | | | | 27) FBC 11-4.9.4(2)STAIRWAY HANDRAILS. | | SHEET A-810, DETAIL 6 RAIL AT WALL.THE | | LOWER HANDRAIL EXTENSION DIMENSIONS | | MARKED 'ONE TREAD' AND 1'-0" SHALL BE | | SWAPPED TO COMPLY WITH THE CODE | | REQUIREMENT. | | | | 28) FBC 11-4.1.3(5) ACCESSIBLE ELEVATORS | | THE PASSENGER ELEVATORS SHALL BE IN | | ACCORDANCE WITH FBC 11-4.10.ANNOTATE | | THE PLANS TO DEMONSTRATE COMPLIANCE. | | | | 29) FBC 11-4.31PUBLIC TELEPHONES.THE | | CLEARANCES AND FACILITIES SHALL BE IN | | ACCORDANCE WITH THIS REQUIREMENT.AMEND | | THE PLANS TO DEMONSTRATE COMPLIANCE | | (REF. FIG 44) | | | | 30) FBC 11-4.15DRINKING FOUNTAINS. THE | | CLEARANCES AND SPOUT HEIGHT SHALL BE IN | | ACCORDANCE WITH THIS REQUIREMENT.AMEND | | THE PLANS TO DEMONSTRATE COMPLIANCE | | (REF. FIG 27) | | | | 31) FBC 11-4-19LAVATORIES.SUBMIT | | DETAILS TO SHOW COMPLIANCE WITH THE | | HEIGHT AND CLEARANCE REQUIREMENTS | | (FIGURES 31 AND 32) | | | | 32) FBC 11-4.16WATER CLOSET. | | SHEET A-208, DETAIL 11.THE HEIGHT OF | | THE TOILET SEAT SHALL BE 17" TO 19" | | ABOVE THE FLOOR.AMEND DETAIL 11 AND | | THE RELEVANT TOILET ELEVATIONS TO | | DEMONSTRATE COMPLIANCE. | | | | 33) FBC 11.4.21SHOWER SEAT. | | SHEET A-208, DETAIL 10.THE SHOWER SEAT | | SHALL BE MOUNTED 17' TO 19' ABOVE THE | | BATHROOM FLOOR.THE HEIGHT SHOWN ON | | DETAIL 10 DOES NOT COMPLY, BUT THE | | HEIGHTS SHOWN ON SHEET A-209 DO COMPLY. | | AMEND SHEET A-208, DETAIL 10.ALSO, | | THE PLANS SHALL BE AMENDED TO SHOW THAT | | THE SHOWER CONTROLS AND SPRAY UNIT | | COMPLY WITH THE FBC 11-4.21.5 AND 4.21.6 | | | | 34) FBC 11-4.35DRESSING ROOMS, | | SHEET A-105.THE MEN'S AND WOMEN'S | | DRESSING ROOMS SHALL BE ACCESSIBLE, | | INCLUDING THE PROVISION OF BENCHES. | | AMEND THE PLANS TO DEMONSTRATE | | COMPLIANCE. | | | | 35) FBC 403.1.4.1BARS.TO COMPLY WITH | | FBC 11-4.5.2 THE NEW BARS SHALL EACH | | INCORPORATE A PORTION AT LEAST 60" LONG | | WHICH IS AT A HEIGHT OF 28" TO 34" ABOVE | | THE FINISH FLOOR WITH KNEE CLEARANCES IN | | ACCORDANCE WITH FBC 11-4.32.3. | | ALTERNATIVELY, SERVICE MUST BE MADE | | AVAILABLE AT ACCESSIBLE SEATING IN THE | | SAME AREA.AMEND THE PLANS TO | | DEMONSTRATE COMPLIANCE. | | | | 36) FBC* 104.2.1SHEET A-402, EAST AND | | SOUTH ELEVATIONS.AMEND THE KEY PLANS | | TO SHOW THE CORRECT VIEW DIRECTIONS. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
10 |
Status |
P |
Date |
2003-09-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-09-12 |
Time |
09:19 |
Rev Time |
1.50 |
Received By |
dpalmer |
Date |
2003-09-12 |
Time |
09:19 |
Sent To |
|
|
Notes |
2003-09-12 00:00:00 | OWES REV FEES |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
9 |
Status |
P |
Date |
2003-07-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-07-08 |
Time |
13:47 |
Rev Time |
3.00 |
Received By |
dpalmer |
Date |
2003-07-08 |
Time |
13:47 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
P |
Date |
2003-06-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-06-13 |
Time |
12:53 |
Rev Time |
3.00 |
Received By |
dpalmer |
Date |
2003-06-13 |
Time |
10:36 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2003-04-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-04-15 |
Time |
10:48 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2003-04-15 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2003-04-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-04-09 |
Time |
14:22 |
Rev Time |
1.50 |
Received By |
dpalmer |
Date |
2003-04-09 |
Time |
14:22 |
Sent To |
|
|
Notes |
2003-04-09 00:00:00 | ************** UNSAT *************** | | | | 1)NOTE: PLANS WERE SUBMITTED TO | | NEIL MELICK (BLDG OFFICIAL) FOR PROPOSED | | WORK AND ENERGIZING OF SERVICE FOR | | ELEVATORS. | | PER DIRECTION OF THE BUILDING OFFICIAL, | | PLEASE SEE LETTER ATTACHED FOR OPERATING | | POLICY. DATED JULY 28, 1997 | | | | PLEASE SEE REQUIREMENTS AND NOTES FOR | | POWER RELEASE. | | | | 2)NOTE: PLEASE NOTE AS PER CONVERSATION | | WITH FRED CHESNEY, ALL PLANS SUBMITTED | | FOR REVIEW AND RECORD MUST BE SIGNED, | | DATED AND SEALED BY ENGINEER OF RECORD. | | PER FS. 471.025, FAC 61G15-23.002 | | | | PLEASE CALL BLDG OFFICIALS ADMIN ASST | | TO SET UP ANY DESIRED MEETINGS. | | | | IF THERE ARE NAY QUESTIONS, OR IF I CAN | | BE OF ASSISTANCE, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2003-02-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-02-14 |
Time |
14:44 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2003-02-14 |
Time |
14:44 |
Sent To |
|
|
Notes |
2003-02-14 00:00:00 | REV FOR 101,203,204 MEZZANINE LIGHTING. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2002-07-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-07-17 |
Time |
09:55 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-07-17 |
Time |
09:55 |
Sent To |
|
|
Notes |
2002-07-17 00:00:00 | ELECTRICAL GFI LOCATIOND SHOWNON A- | | SHEETS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2002-06-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-06-04 |
Time |
20:39 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-06-04 |
Time |
20:00 |
Sent To |
|
|
Notes |
2002-06-04 00:00:00 | ********* NOTE******* | | | | ELECTRICAL PLANS HAVE BEEN STAMPED FOR | | ELECTRICAL PLAN REVIEW. | | FIRE REVIEW OF ELECTRICAL SHEETS STILL | | NEED TO BE DONE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2002-05-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-05-22 |
Time |
07:08 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-05-22 |
Time |
07:08 |
Sent To |
|
|
Notes |
2002-05-22 00:00:00 | ****************** UNSAT ************ | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE IN | | GOOD SHAPE BUT STILL NEEDS TO HAVE | | ISSUE WITH DISCONNECTING MEANS LOCATIONS | | TO BE WORKED OUT. | | GROUPING OF MAINS/TRAVEL DISTANCE IS | | STILL A CONCERN. 230-72 | | | | PLEASE NOTE IF THERE ARE ANY QUESTIONS, | | ON THE ABOVE INFORMATION, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-03-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-26 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-26 |
Time |
11:56 |
Sent To |
|
|
Notes |
2002-03-26 00:00:00 | ****************** UNSAT ************** | | | | 1)NOTE: PLEASE CLARIFY LIGHTING FOR | | FOOD STORAGE M-20 ON PAGE E-204. | | | | 2)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | LOADS (LIGHTING) ETC ARE TO BE FIGURED | | AND SHOWN AT 125%. 215-2/215-3 /230-42.. | | .... | | | | 3)NOTE: PLEASE CLARIFY PANEL SCHEDULE | | FOR EP4P2. SHOWS SF 1P- SF 6P? PLEASE | | CLARIFY WHAT THESE LOADS ARE? | | | | 4)NOTE: PLEASE CLARIFY GROUPING OF MAINS | | FOR EMERGENCY POWER. PLEASE NOTE MAIN | | ELECTRICAL COMING FROM ORIG BLDG AND | | GENERATOR POWER COMING FROM NEW BLDG | | OUTSIDE AND UP A LEVEL. PLEASE SEE | | FIRE PLAN REVIEW COMMENTS FOR THIS. | | PLEASE NOTE CONCERNS OVER SHUTTING MAIN | | OFF AND HAVINGGENERATOR START UP AND | | STILL FEEDING POWER INTO NEW BLDG. | | PLEASE NOTE FIREDEPT CONCERNS OVER | | THE DISTANCE OF TRAVEL FOR SHUTTING OF | | EM POWER IN 2-LEVEL GARAGE, THEN MCB | | ON THE INSIDE OF GENERATOR, (IF OUTSIDE) | | PLEASE SEE 230-72 FOR GROUPING OF MAINS, | | AND 230-76/230-79 FOR RATING OF MAINS | | FOR ELEC POWER. | | | | 5)NOTE: PLEASE SHOW LOAD CALCULATIONS | | FOR ADDING NEW SERVICE LOAD TO EXISTING | | SERVICE. | | | | 6)NOTE: PLEASE SUBMIT ALL PANEL SCHEDULE | | S, SCDP2? PLEASE CHECK FOR ANY OTHERS. | | | | 7)NOTE: PLEASE CLARIFY GROUNDING ATTACH- | | MENT FOR TRANSFORMERS.250-30 | | | | PLEASE SEE FIRE REVIEW COMMENTS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE NAY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
4 |
Status |
P |
Date |
2002-08-19 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-08-19 |
Time |
15:31 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2002-08-19 |
Time |
15:31 |
Sent To |
|
|
Notes |
2002-08-19 00:00:00 | PASSED WITH PROVISOS: | | 1. REVISION FOR TEMPORARY PARKING LOT, | | MUST RESTORE SITE PER APPROVED SITE | | PLANS FILED UNDER PERMIT NUMBER 02051858 | | AFTER THE SAID PARKING NO LONGER NEEDED. | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMD R. AMINI |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
N |
Date |
2002-06-05 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-06-05 |
Time |
08:13 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2002-06-05 |
Time |
08:13 |
Sent To |
|
|
Notes |
2002-06-05 00:00:00 | N/A | | 1. SEE PERMIT # 02051858 FOR CIVIL/SITE | | REVIEW AND PERMITTING . | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
F |
Date |
2002-05-06 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-05-06 |
Time |
10:33 |
Rev Time |
4.00 |
Received By |
mamini |
Date |
2002-05-06 |
Time |
10:33 |
Sent To |
|
|
Notes |
2002-05-06 00:00:00 | FAILED : | | 1. PLEASE SUBMIT THE LATEST CIVIL /SITE | | PLANS APPROVED BY THE PUBLIC UTILITIES | | ENGINEERING SERVICES DEPARTMENT FOR OUR | | REVIEW AND PERMITTING. | | 2. PLEASE LOCATE THE PROPOSED OIL /WATER | | SEPARATOR AS SUCH THAT IS EASILY | | ACCESSIBLE FOR SERVICE AND INSPECTIONS. | | 3. PLEASE VERIFY, IS THE EXISTING | | GREASE TRAP AS SHOWN ON SHEET C1 GOING | | TO BE REMOVED /RELOCATED? | | 4. PLEASE VERIFY, IS THE SANITARY 3 A | | DROP MANHOLE? | | 5. A SEPARATE PERMIT APPLICATION AND FEE | | AT THE TIME OF ACTUAL WILL BE REQUIRED. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2002-03-14 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-03-14 |
Time |
09:30 |
Rev Time |
3.00 |
Received By |
mamini |
Date |
2002-03-14 |
Time |
09:30 |
Sent To |
|
|
Notes |
2002-03-14 00:00:00 | FAILED : | | 1. PLEASE PROVIDE STORM WATER | | CALCULATIONS SHOWING PRE-CONSTRUCTIONS | | VS POST-CONSTRUCTION DISCHARGE RATE FOR | | THE SITE. | | 2. PLEASE PROVIDE HYDRAULIC CALCULATIONS | | SHOWING THE REQUIRED RCP SIZES. | | 3. PLEASE SHOW ALL THE EXISTING FIRE HYD | | ON SITE/NEARBY, ADDITIONAL FIRE HYD MAY | | BE REQUIRED. | | 4. PLEASE VERIFY, IF CONSTRUCTIONS OF | | 18" RCPS FROM S-8 TO S-9 AND TO S-10 AS | | SHOWN WOULD BE IN CONFLICT WITH | | CONSTRUCTION OF AUGER CAST PILES AND THE | | PROPOSED BUILDING'S FOUNDATION. | | 5. PLEASE SHOW CONNECTION FOR DOMESTIC | | WATER. | | 6. PLEASE SHOW CONNECTION FOR THE | | PROPOSED OIL/WATER SEPARATOR. | | 7. CONTRACTOR MUST CALL RODNEY COMPO, | | 837-4051 EXT. 4074 FOR APPROVAL, | | INSPECTIONS OF BOTH GREASE/WATER, OIL/ | | WATER SEPARATOR. | | 8. ANY WORK WITHIN PUBLIC R.O.W WILL | | REQUIRE A SEPARATE PERMIT FROM THE CITY | | ENGINEER'S OFFICE, 659-8040. | | 9. A SEPARATE PERMIT APPLICATION AND | | FEES FOR UNDERGROUND /SITE WORKS WILL BE | | REQUIRED AT THE TIME OF ACTUAL | | PERMITTING. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
12 |
Status |
P |
Date |
2003-09-05 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-09-05 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-09-05 |
Time |
16:04 |
Sent To |
|
|
Notes |
2003-09-05 00:00:00 | APPROVED PROVISO: | | | | 1) SECURITY DEVICES INSTALLED ON EXIT | | DOORS SHALL NOT INTERFERE WITH ANY | | REQUIRED EXITING. PERSONS WITHOUT | | CARDS FOR THE CARDREADERS SHALL STILL | | BE ABLE TO EXIT THE BUILDING. | | | | 2) ONLY CODE ALLOWED DEVICES ARE ALLOWED | | IN THE STAIRWELLS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
11 |
Status |
P |
Date |
2003-07-16 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-07-16 |
Time |
17:04 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-07-16 |
Time |
17:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
10 |
Status |
P |
Date |
2003-07-16 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2003-07-16 |
Time |
13:35 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-07-16 00:00:00 | AS-BUILTS OK BY MIKE CARSILLO |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
9 |
Status |
P |
Date |
2003-05-08 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-05-08 |
Time |
14:23 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-05-08 |
Time |
14:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
8 |
Status |
P |
Date |
2002-08-21 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-08-21 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-08-21 |
Time |
11:36 |
Sent To |
|
|
Notes |
2002-08-21 00:00:00 | 1) ALL UNDERGROUND FIRE LINES ARE TO | | BE INSTALLED IN ACCORDANCE WITH | | NFPA 24. | | | | 2) NO CONTROL VALVES ARE ALLOWED TO BE | | INSTALLED IN THE FIRE DEPARTMENT | | CONNECTION. | | | | 3) A CHECK VALVE IS REQUIRED IN THE | | FIRE DEPARTMENT CONNECTION. | | | | 4) UNDERGROUND FIRE LINES ARE TO BE | | PROPERLY RESTRAINED IN ACCORDANCE WITH | | NFPA 24. | | | | 5) ALL LINES ARE TO BE PRESSURE TESTED | | IN ACCORDANCE WITH NFPA 24. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
7 |
Status |
P |
Date |
2002-08-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-08-09 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-08-09 |
Time |
16:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
P |
Date |
2002-07-30 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-07-30 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-07-30 |
Time |
14:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
F |
Date |
2002-07-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-07-02 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-07-02 |
Time |
10:34 |
Sent To |
|
|
Notes |
2002-07-02 00:00:00 | 1) CO PIPING NOTED IN STAIR # 4. NOT | | PERMITTED WITHIN STAIRWELL. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2002-06-14 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-06-14 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-06-14 |
Time |
13:08 |
Sent To |
|
|
Notes |
2002-06-14 00:00:00 | PLAN REVIEW COMMENTS SHALL BE | | ADDRESSED BY REVISION AND SUBMITTED | | WHEN PERMIT IS ISSUED AND PICKED | | UP. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2002-06-07 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-06-07 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-06-07 |
Time |
14:52 |
Sent To |
|
|
Notes |
2002-06-07 00:00:00 | 1) PLAN REVIEW COMMENT RESPONSE 27 | | LOCATED ON PAGE 7 OF PERMIT REVIEW | | COMMENTS, 2ND REVIEW SUBMITTAL, APRIL | | 22,2002 IS CONFUSING. THE PORTION | | THAT INDICATES "NETS WILL BE ADDED" | | IS NOT VERY CLEAR. | | | | 2) EXIT SIGN INFORMATION THAT WAS | | PROVIDED IS ACCEPTABLE. THANK YOU. | | | | 3) PLANS STILL INDICATE IMPROPER | | OCCUPANT LOAD FOR ANCILLARY SPACE | | ON PAGE LS-103. | | | | 4) THE OCCUPANT LOAD FOR THE MEZZANINE | | IS STILL INCORRECT. | | | | 5) DOOR M-17 SHOULD BE SHIFTED IN | | CORRIDOR M-16. | | | | 6) PARKING SPACE # 55 AND THE BIKE AREA | | NOTED ON LEVEL 2, PARKING APPEARS TO | | POSE A PROBLEM. PLEASE SCALE THIS AREA | | TO DETERMINE IF THE MINIMUM WIDTH | | REQUIREMENTS ARE MET ESPECIALLY AT THE | | NORTHWEST CORNER OF THE PARKING SPACE. | | | | 7) ALL SHAFTS THAT PERSONS CAN FALL INTO | | MUST BE MARKED "SHAFTWAY IN RED LETTERS | | AT LEAST 6 INCHES HIGH ON A WHITE | | BACKGROUND. | | | | 8) PLEASE PROVIDE TACTILE SIGNAGE AT | | ALL EXIT DOORS. | | | | 9) EXIT SIGNS STILL SHOWN DIRECTING | | AND IMMEDIATELY IN FRONT OF VALET | | RAMP ON LS-102. | | | | 10) WITH REGARDS TO THE MAG LOCKS | | PLANNED FOR USE IT WAS INDICATED THAT | | THESE DEVICES WILL BE TIED INTO THE | | FIRE ALARM SYSTEM. PLEASE BE ADVISED | | THAT THERE ARE OTHER CODE REQUIREMENTS | | FOR THESE DEVICES UNDER DELAYED EGRESS | | OR ACCESS CONTROLLED EGRESS. | | | | 11) STILL CONFUSED ABOUT "USING THE | | ESCUTHEON ONLY AND CONCEALING THE EYE | | WITH THE COVER NOTES". | | | | 12) STRIPING NOTED OUTSIDE OF EXIT DOORS | | ARE NOT NECESSARY UNLESS THE OWNER | | MANDATES THEM, SEE PAGE LS-105. | | | | 13) PLEASE SHADE EXIT ACCESS AREAS ON | | THE PLAN FOR EXITS THAT ARE OPPOSITE OF | | PARKING SPACES. THIS APPEARS TO BE A | | PROBLEM ON MORE THAN ONE LOCALE. PLEASE | | SEE LS-101 AND LS-102. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2002-05-21 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-05-21 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-05-21 |
Time |
16:00 |
Sent To |
|
|
Notes |
2002-05-21 00:00:00 | 1) PLEASE EXPLAIN NON-ILLUMINATED EXIT | | SIGNS NOTED ON PAGE LS-103. PLEASE | | REVIEW "ILLUMINATIONS OF SIGNS" SECTION | | 7.10.5.1, LIFE SAFETY CODE 2000 EDITION. | | | | 2) THE OCCUPANT LOAD FOR THE ANCILLARY | | SPACE LOCATED ON PAGE LS-103 IS NOT | | CORRECT. IT SHOULD READ 52 PERSONS NOT | | 523 PERSONS. | | | | 3) THE OCCUPANT LOAD FOR MEZZANINE LEVEL | | ON LS-104 IS NOT CORRECT. SHOULD READ | | 4 OR 5 NOT 45. THE TOTAL OCCUPANT LOAD | | SHOULD APPROXIMATELY 7 NOT 48. | | | | 4) IS THE ELEVATION EQUAL ON BOTH SIDES | | OF THE EXIT DOORS FROM THE PREFUNCTION | | AREA ADJACENT TO STAIR # 2. | | | | 5) DOORS FROM STORAGE M-02 APPEAR TO | | SWING TOO FAR INTO CORRIDOR M-03. | | | | 6) DOORS ARE NEARLY OPPOSING ONE ANOTHER | | IN CORRIDOR M-16. | | | | 7) ARE GUARDS SHOWN ON RAILING AT | | REHEARSAL HALL WALKWAY. | | | | 8) THE BUILDING ADDRESS IS REQUIRED TO | | BE INSTALLED ON IT. A MINIMUM OF 6" HIGH | | NUMBERS ARE REQUIRED. | | | | 9) VEHICLE PARKING SPACE # 55 APPEARS TO | | INTERFERE WITH EXIT ACCESS TO STAIR. | | | | 10) DOES THE ROLL-UP SECURITY GRILL | | SHOWN ON LEVEL 2 INTERFERE WITH ANY | | EXITING. | | | | 11) PLEASE EXPLAIN 6" STEP NEAR FOYER | | B-004. | | | | 12) THE EXITING FOR THE BUILDING STILL | | APPEARS TO BE CONFUSING. BY TOTALING | | THE OCCUPANT LOAD EXIT CAPACITIES FOR | | STAIRS 1,2,AND 4, IT INDICATES 548 | | PERSONS. ACCORDING TO LS-105 AN EXIT | | CAPACITY OF 706 PERSONS IS AVAILABLE | | FOR THE WEST SIDE. WHEN STAIRS 1,AND 4 | | ARE TOTALED IT INDICATES 382 PERSONS. | | EAST EXIT CAPACITY ACCORDING TO THE | | INFORMATION PROVIDED INDICATES 382 | | PERSONS. WHEN EXAMINING STAIR 2, IT HAS | | AN EXIT CAPACITY OF 166 PERSONS. IT IS | | NOT CLEAR IF STAIR 3 IS USED FOR EXITING | | AS EXIT SIGNS APPEAR TO BE MISSING. THE | | CONCERN IS THE ABILITY TO EXIT PERSONS | | FROM THE FLOOR THAT THEY ARE ON, | | IRRESPECTIVE OF ANY HORIZONTAL EXITS | | THAT ARE PROVIDED. | | | | 13) STAIR 2 HAS AN EXIT CAPACITY OF 166 | | NOT 66.7 AS NOTED. | | | | 14) PLEASE EXPLAIN GALLERIES A AND B. | | | | 15) ADDITIONAL EXIT SIGNS MAY BE NEEDED | | IN CORRIDOR 3-001A. | | | | 16) THE STAIRS NEAR THE LOADING DOCK | | APPEARS TO HAVE A CAPACITY OF 220 | | PERSONS. A REVIEW WITH ROBERT BROWN, | | BUILDING PLANS EXAMINER TOOK PLACE. BY | | USING A CONSERVATIVE FIGURE, THE EXIT | | CAPACITY GOING THRU DOORS G-22 WAS 401 | | PERSONS. HOW DOES EXIT DISCHARGE WORK. | | | | 17) STAIR 4 EXIT DOOR AT GRADE LEVEL AND | | DOUBLE DOORS DIRECTLY ADJACENT TO IT | | OPPOSE ONE ANOTHER. | | | | 18) THE FIRE HYDRANT ON A-103 MUST BE | | PROVIDED WITH 7'- 6" CLEARANCE TO THE | | FRONT AND SIDES. A MINIMUM OF 4' MUST | | BE PROVIDED TO THE REAR OF IT. | | | | 19) A KNOX-BOX WILL BE REQUIRED. | | | | 20) IT WAS NOTED THAT MAG-LOCKS ARE | | PRESENT ON THE PLANS FOR EXIT DOORS. | | PLEASE REVIEW DELAYED EGRESS OR ACCESS | | CONTROLLED EGRESS DOORS OF THE LIFE | | SAFETY CODE 2000 EDITION. | | | | 21) EXIT SIGNS OBSERVED NEAR VALET | | RAMP. PLEASE SEE PARKING STRUCTURES | | OF THE LIFE SAFETY CODE, 2000 EDITION. | | USE OF THE RAMPS FOR EXITING MAY NOT | | BE APPLICABLE. | | | | 22) A NOTE STILL REMAINS ON THE PLANS | | THAT INDICATES "150LB PICK-UP POINT | | RECESSED INTO SPRINKLER HEAD ESCUTHEONS | | WITH COVER". NO ITEMS ARE TO BE | | CONNECTED TO FIRE SPRINKLER PIPING OR | | FIRE SPRINKLER HEADS. | | | | 23) MIRRORS ARE NOT TO BE PLACED | | ADJACENT TO EXIT DOORS. | | | | 24) STAIR 1 AND STAIR 3 HAVE A TOTAL | | EXIT CAPCITY OF 292 PERSONS. | | | | 25) WHEN LEAVING CONFERENCE ROOM 3-003 | | AND RECEPTION 3-002 ONLY ONE DIRECTION | | OF EXIT TRAVEL HAS BEEN IDENTIFIED. | | PLEASE VERIFY COMMON PATH OF TRAVEL | | AND DEAD-END REQUIREMENTS. | | | | 26) ALL SHAFTWAYS THAT CONNECT TWO OR | | MORE FLOORS ARE TO BE IDENTIFIED WITH | | SIGNS STATING "SHAFTWAY" IN RED | | LETTERS IN RED LETTERS AT LEAST SIX | | INCHES HIGH ON A WHITE BACKGROUND. | | | | 27) WATER CURTAIN SHOWN ON PAGE FP203 | | DOES NOT PROVIDE PRESCRIPTIVE CODE | | REQUIREMENT NOTES. | | | | 28) PLEASE EXPLAIN NOTES ON PAGE FP203 | | "EXIST SPRINKLER PIPING AND SPRINKLERS | | TO BE REMOVED". | | | | 29) DOES NOT APPEAR THAT FIRE HOSE | | VALVE LOCATIONS HAVE BEEN REVISED ON | | FIRE PROTECTION DRAWINGS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-03-26 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-03-26 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-03-26 |
Time |
15:11 |
Sent To |
|
|
Notes |
2002-03-26 00:00:00 | 1) CONSTRUCTION FENCE SHOWN ON SITE PLAN | | G-02 MUST NOT INTERFERE WITH ANY | | EXISTING EXITING FACILITIES OR ANY | | FIRE PROTECTION EQUIPMENT OR DEVICES. | | 2) PLEASE PROVIDE EXISTING FIRE HYDRANT | | LOCATIONS ON SITE PLAN. | | 3) NEW CONSTRUCTION MUST NOT INTERFERE | | WITH FIRE RESCUE ACCESS TO THE | | EXISTING BUILDINGS LOCATED ON THE SITE. | | 4) PRIOR TO STARTING CONSTRUCTION A | | SITE INSPECTION IS TO BE PERFORMED BY | | FIRE RESCUE TO ENSURE THAT TEMPORARY | | BARRIERS, ETC., DO NOT INTERFERE WITH | | ANY EXITING. | | 5) TEMPORARY BARRIER AT EXISTING STAIR | | # 4 TO BE NON-COMBUSTIBLE. | | 6) THE REMOVAL OF ANY COVERED WALKS OR | | PAVERS ARE NOT TO CREATE ANY HAZARDS TO | | PERSONS UNSING THE EXISTING BUILDINGS. | | 7) IT APPEARS THAT FIRE DEPT. VALVE | | BOX IN BLOCKED BY PARKING SPACE # 8 ON | | LEVEL 1-PARKING. | | 8) THE SAME CONDITION APPEARS TO EXIST | | FOR FIRE DEPT. VALVE BY PARKING SPACE | | # 12 ON LEVEL 2-PARKING. | | 9) STAIR # 1 AND STAIR # 3 SHOULD BE | | EQUIPPED WITH FIRE DEPT. VALVES. STAIRS | | # 1 AND STAIR # 3 PROVIDE COVERAGE FOR | | OTHER PARTS OF THE BUILDING. | | 10) PANIC HARDWARE REQUIRED ON ALL EXIT | | DOORS SUBJECT TO AN OCCUPANCY OF 100 | | OR MORE PERSONS. | | 11) ADDITIONAL EXIT SIGNS NEEDED TO | | DESIGNATE SECOND MEANS OF EGRESS FROM | | BANQUET ROOMS LOCATED ON THE GROUND | | LEVEL. | | 12) PLEASE INDICATE OCCUPANT LOADS FOR | | ASSEMBLY ROOMS LOCATED ON THE SECOND | | LEVEL. | | 13) PLEASE EXPLAIN RATIONALE FOR SINGLE | | EXIT ARRANGEMENT FOR OFFICE AREA NEAR | | PROG OFFICE 3-PO3. | | 14) PLEASE VERIFY THAT EXIT DOOR SWING | | IS CORRECT IN RECEPTION, WAITING 3-XO1. | | 15) IDENTIFICATION SIGNS REQUIRED FOR | | THE STAIR TOWERS. | | 16) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | 17) PLEASE EXPLAIN THE FOLLOWING NOTE | | " 50LB PICK UP POINT 1/4 X 1 DIA EYE | | BOLTS AT EVERY CROSSING (168 TOTAL) | | RECESSED INTO SPRINKLER HEAD | | ESCUTCHEONS WITH COVER" ON PAGE A-307. | | 18) BUILDING ADDRESS REQUIRED. | | 19) GUARDS ARE REQUIRED TO PREVENT A | | SPHERE OF FOUR INCHES TO PASS THROUGH | | THEM. | | 20) ARCHITECTURAL PLANS SHOULD INDICATE | | THE NUMBER OF AIR CHANGES AND THE CFM | | OF EXHAUST THAT WILL OCCUR IN THE | | UNDERGROUND PARKING AREA. | | 21) ARE THE F1E ITEMS IN THE PARKING | | AREAS EMERGENCY LIGHTING EQUIPMENT. | | 22) PLEASE SEE NOTE # 4 ON ELECTRICAL | | PLAN REVIEW. | | 23) ROOF MANIFOLD(S) ARE REQUIRED. | | 24) PLEASE EXPLAIN DESIGN FOR WATER | | CURTAIN SHOWN ON PAGE FP-203. | | 25) SEPARATE PLANS AND PERMITS REQUIRED | | FOR HOOD, DUCT AND EXTINGUISHING SYSTEMS | | 26) SEPARATE PLANS AND PERMITS REQUIRED | | FOR FOR FIRE ALARM SYSTEM INSTALLATION. | | 27) ELEVATORS TO COMPLY WITH FLORIDA | | ELEVATOR CODE 61C-5. | | 28) PLEASE INDICATE ON PLANS SMOKE | | DETECTORS FOR ELEVATOR RECALL. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
58 |
Status |
N |
Date |
2003-09-15 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-09-15 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-09-15 |
Time |
09:56 |
Sent To |
B |
|
Notes |
2003-09-15 00:00:00 | TO RB DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
57 |
Status |
N |
Date |
2003-08-27 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-08-27 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-08-27 |
Time |
16:19 |
Sent To |
|
|
Notes |
2003-08-27 00:00:00 | TO COMM BD #53 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
56 |
Status |
N |
Date |
2003-08-27 |
|
|
Cont ID |
|
Sent By |
dbaxter |
Date |
2003-08-27 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
dbaxter |
Date |
2003-08-27 |
Time |
14:58 |
Sent To |
B |
|
Notes |
2003-08-27 00:00:00 | TO RBROWN DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
55 |
Status |
N |
Date |
2003-08-12 |
|
|
Cont ID |
|
Sent By |
dbaxter |
Date |
2003-08-12 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
dbaxter |
Date |
2003-08-12 |
Time |
14:12 |
Sent To |
B |
|
Notes |
2003-08-12 00:00:00 | TO RB DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
54 |
Status |
N |
Date |
2003-08-12 |
|
|
Cont ID |
|
Sent By |
dbaxter |
Date |
2003-08-12 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
dbaxter |
Date |
2003-08-12 |
Time |
14:05 |
Sent To |
B |
|
Notes |
2003-08-12 00:00:00 | TO RBROWN DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
53 |
Status |
N |
Date |
2003-07-21 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-21 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-07-21 |
Time |
10:38 |
Sent To |
B |
|
Notes |
2003-07-21 00:00:00 | RB DESK 2 REVISIONS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
52 |
Status |
N |
Date |
2003-07-15 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-15 |
Time |
13:15 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-07-15 |
Time |
13:15 |
Sent To |
B |
|
Notes |
2003-07-15 00:00:00 | RBROWN DESK, 3 SUBMITTALS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
51 |
Status |
N |
Date |
2003-07-08 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-08 |
Time |
09:46 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-07-08 |
Time |
09:46 |
Sent To |
B |
|
Notes |
2003-07-08 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
50 |
Status |
N |
Date |
2003-07-07 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-07 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-07-07 |
Time |
16:55 |
Sent To |
B |
|
Notes |
2003-07-07 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
49 |
Status |
N |
Date |
2003-07-07 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-07 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-07-07 |
Time |
16:55 |
Sent To |
B |
|
Notes |
2003-07-07 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
48 |
Status |
N |
Date |
2003-07-01 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-01 |
Time |
12:52 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-07-01 |
Time |
12:52 |
Sent To |
B |
|
Notes |
2003-07-01 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
47 |
Status |
N |
Date |
2003-06-27 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-27 |
Time |
08:06 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-27 |
Time |
08:06 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
46 |
Status |
N |
Date |
2003-06-25 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-25 |
Time |
16:57 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-25 |
Time |
16:57 |
Sent To |
E |
|
Notes |
2003-06-25 00:00:00 | DP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
45 |
Status |
N |
Date |
2003-06-23 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-23 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-23 |
Time |
10:27 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
44 |
Status |
N |
Date |
2003-06-12 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-12 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-12 |
Time |
15:16 |
Sent To |
B |
|
Notes |
2003-06-12 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
43 |
Status |
N |
Date |
2003-06-04 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-04 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-04 |
Time |
13:56 |
Sent To |
B |
|
Notes |
2003-06-04 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
42 |
Status |
N |
Date |
2003-06-03 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-06-03 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-06-03 |
Time |
09:27 |
Sent To |
B |
|
Notes |
2003-06-03 00:00:00 | RBROWN DESK, 2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
41 |
Status |
N |
Date |
2003-05-30 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-30 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-30 |
Time |
16:35 |
Sent To |
E |
|
Notes |
2003-05-30 00:00:00 | BT DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
40 |
Status |
N |
Date |
2003-05-28 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-28 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-28 |
Time |
14:02 |
Sent To |
B |
|
Notes |
2003-05-28 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
39 |
Status |
N |
Date |
2003-05-27 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-27 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-27 |
Time |
16:13 |
Sent To |
B |
|
Notes |
2003-05-27 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
38 |
Status |
N |
Date |
2003-05-27 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-27 |
Time |
15:57 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-27 |
Time |
15:57 |
Sent To |
B |
|
Notes |
2003-05-27 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
37 |
Status |
N |
Date |
2003-05-27 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-27 |
Time |
15:56 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-27 |
Time |
15:56 |
Sent To |
B |
|
Notes |
2003-05-27 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
36 |
Status |
N |
Date |
2003-05-14 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-14 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-14 |
Time |
15:48 |
Sent To |
E |
|
Notes |
2003-05-14 00:00:00 | DP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
35 |
Status |
N |
Date |
2003-05-12 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-12 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-12 |
Time |
09:14 |
Sent To |
B |
|
Notes |
2003-05-12 00:00:00 | RBROWN DESK, BUILDING SUBMITTAL. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
34 |
Status |
N |
Date |
2003-04-25 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-25 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-04-25 |
Time |
11:06 |
Sent To |
B |
|
Notes |
2003-04-25 00:00:00 | RBROWN DESK | | RFI 356. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
33 |
Status |
N |
Date |
2003-04-25 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-25 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-04-25 |
Time |
10:58 |
Sent To |
B |
|
Notes |
2003-04-25 00:00:00 | RB DESK. SUBMITTAL | | ` |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
32 |
Status |
N |
Date |
2003-04-15 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-15 |
Time |
09:29 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-04-15 |
Time |
09:29 |
Sent To |
B |
|
Notes |
2003-04-15 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
31 |
Status |
N |
Date |
2003-04-15 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-15 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-04-15 |
Time |
09:27 |
Sent To |
E |
|
Notes |
2003-04-15 00:00:00 | DP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
30 |
Status |
N |
Date |
2003-04-10 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-10 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-04-10 |
Time |
08:56 |
Sent To |
|
|
Notes |
2003-04-10 00:00:00 | COMM BOARD #17 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
29 |
Status |
N |
Date |
2003-04-09 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-04-09 |
Time |
10:59 |
Rev Time |
0.00 |
Received By |
sthyng |
Date |
2003-04-09 |
Time |
10:59 |
Sent To |
E |
|
Notes |
2003-04-09 00:00:00 | TO DP DESK | | ELEVATOR TEMPORARY PLAN |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
28 |
Status |
N |
Date |
2003-04-07 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-07 |
Time |
13:47 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-04-07 |
Time |
13:46 |
Sent To |
B |
|
Notes |
2003-04-07 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
27 |
Status |
N |
Date |
2003-04-07 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-07 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-04-07 |
Time |
13:25 |
Sent To |
B |
|
Notes |
2003-04-07 00:00:00 | RBROWN DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
26 |
Status |
N |
Date |
2003-03-31 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-03-31 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
sthyng |
Date |
2003-03-31 |
Time |
15:24 |
Sent To |
B |
|
Notes |
2003-03-31 00:00:00 | SUBMITTALS TO RB DESK | | | | 1.)SK118- SK 122 | | 2.)RFC 246 S&S |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
25 |
Status |
N |
Date |
2003-03-25 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-03-25 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
sthyng |
Date |
2003-03-25 |
Time |
13:19 |
Sent To |
B |
|
Notes |
2003-03-25 00:00:00 | TO RB DESK | | 1.) SHOP DRAWINGS, SK 116 & SK117 | | 2.) SHOP DRAWINGS, ENTRY CANOPY STEEL | | SHOP DRAWINGS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
24 |
Status |
N |
Date |
2003-03-24 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-03-24 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
sthyng |
Date |
2003-03-24 |
Time |
09:39 |
Sent To |
B |
|
Notes |
2003-03-24 00:00:00 | TO RB DESK | | REVISIONS TO STAIR #4 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
23 |
Status |
N |
Date |
2003-03-19 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-03-19 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
sthyng |
Date |
2003-03-19 |
Time |
11:02 |
Sent To |
B |
|
Notes |
2003-03-19 00:00:00 | REVISION TO RB DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
22 |
Status |
N |
Date |
2003-03-19 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-03-19 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
sthyng |
Date |
2003-03-19 |
Time |
10:14 |
Sent To |
M |
|
Notes |
2003-03-19 00:00:00 | SHOP DRAWING SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
21 |
Status |
N |
Date |
2003-03-11 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-03-11 |
Time |
09:36 |
Rev Time |
0.00 |
Received By |
sthyng |
Date |
2003-03-11 |
Time |
09:36 |
Sent To |
B |
|
Notes |
2003-03-11 00:00:00 | SENT TO ROBERT BROWN'S DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
20 |
Status |
N |
Date |
2003-03-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-03-07 |
Time |
12:32 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-03-07 |
Time |
12:32 |
Sent To |
B |
|
Notes |
2003-03-07 00:00:00 | TWO SETS OF SUBMITTIALS TO ROBERT BROWN' | | S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
19 |
Status |
N |
Date |
2003-02-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-02-27 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-02-27 |
Time |
12:53 |
Sent To |
B |
|
Notes |
2003-02-27 00:00:00 | TO ROBERT BROWN |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
18 |
Status |
N |
Date |
2003-02-27 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-02-27 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2003-02-26 |
Time |
08:52 |
Sent To |
|
|
Notes |
2003-02-27 00:00:00 | TO COMM.BOARD #13./WRT |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
17 |
Status |
N |
Date |
2003-02-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-02-20 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-02-20 |
Time |
14:36 |
Sent To |
B |
|
Notes |
2003-02-20 00:00:00 | SUBMITTAL TO ROBERT BROWN'S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
16 |
Status |
N |
Date |
2003-02-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-02-20 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-02-20 |
Time |
14:36 |
Sent To |
B |
|
Notes |
2003-02-20 00:00:00 | SUBMITTAL TO ROBERT BROWN`S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
15 |
Status |
N |
Date |
2003-02-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-02-12 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-02-12 |
Time |
16:19 |
Sent To |
B |
|
Notes |
2003-02-12 00:00:00 | TO ROBERT BROWN'S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
14 |
Status |
N |
Date |
2003-02-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-02-12 |
Time |
16:18 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-02-12 |
Time |
16:18 |
Sent To |
B |
|
Notes |
2003-02-12 00:00:00 | TO RB"S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
13 |
Status |
N |
Date |
2003-02-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-02-06 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2003-02-06 |
Time |
11:48 |
Sent To |
B |
|
Notes |
2003-02-06 00:00:00 | TO RB./WRT |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
12 |
Status |
N |
Date |
2003-01-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-30 |
Time |
12:42 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-01-30 |
Time |
12:42 |
Sent To |
B |
|
Notes |
2003-01-30 00:00:00 | TO ROBERT BROWN'S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2003-01-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-23 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-01-23 |
Time |
10:54 |
Sent To |
B |
|
Notes |
2003-01-23 00:00:00 | TO ROBERT BROWN'S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2003-01-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-15 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-01-15 |
Time |
13:19 |
Sent To |
B |
|
Notes |
2003-01-15 00:00:00 | TO ROBERT BROWN'S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2003-01-14 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-01-14 |
Time |
17:27 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2003-01-13 |
Time |
17:27 |
Sent To |
B |
|
Notes |
2003-01-14 00:00:00 | ROBERT B./WRT |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2003-01-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-14 |
Time |
14:09 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-01-14 |
Time |
14:08 |
Sent To |
B |
|
Notes |
2003-01-14 00:00:00 | TO ROBERT BROWN'S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2003-01-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-14 |
Time |
14:08 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-01-14 |
Time |
14:08 |
Sent To |
B |
|
Notes |
2003-01-14 00:00:00 | TO ROBERT BROWN'S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2002-12-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-12-27 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-12-27 |
Time |
10:47 |
Sent To |
M |
|
Notes |
2002-12-27 00:00:00 | TO MECH IN BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2002-12-13 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-12-13 |
Time |
18:04 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-12-13 |
Time |
18:03 |
Sent To |
B |
|
Notes |
2002-12-13 00:00:00 | ROBERT B./WRT. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2002-12-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-12-06 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-12-06 |
Time |
16:53 |
Sent To |
B |
|
Notes |
2002-12-06 00:00:00 | TO ROBERT B./WRT. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2002-12-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-12-02 |
Time |
08:38 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-11-27 |
Time |
08:37 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2002-11-14 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-11-14 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-11-14 |
Time |
16:15 |
Sent To |
B |
|
Notes |
2002-11-14 00:00:00 | TO ROBERT BROWN./WRT |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2002-11-07 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-11-07 |
Time |
18:16 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
|
Time |
|
Sent To |
B |
|
Notes |
2002-11-07 00:00:00 | TO"B"ROBERT BROWN./WRT |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
16 |
Status |
P |
Date |
2003-07-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-07-03 |
Time |
12:48 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2003-07-03 |
Time |
12:33 |
Sent To |
|
|
Notes |
2003-07-03 00:00:00 | SUBMITTAL LETTER - IN LEIU OF A FLOOR | | DRAIN IN A FLOAT SWITCH TO BE INSTALLED | | IN THE DRAIN PAN. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
15 |
Status |
P |
Date |
2003-04-24 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-04-24 |
Time |
08:23 |
Rev Time |
1.25 |
Received By |
pkrauss |
Date |
2003-04-24 |
Time |
08:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
14 |
Status |
P |
Date |
2003-03-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-03-03 |
Time |
10:37 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2003-03-03 |
Time |
10:37 |
Sent To |
|
|
Notes |
2003-03-03 00:00:00 | MECH REV PERMIT 02060887 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
13 |
Status |
F |
Date |
2003-02-27 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-02-27 |
Time |
12:11 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2003-02-27 |
Time |
12:11 |
Sent To |
|
|
Notes |
2003-02-27 00:00:00 | REVISION DENIED: | | | | PLAN IS TAPED ONTO TITLE BLOCK PAGE. | | PLEASE SIGN, SEAL & DATE THE ACTUAL | | DRAWING. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
12 |
Status |
P |
Date |
2003-02-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-02-03 |
Time |
13:57 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2003-02-03 |
Time |
13:57 |
Sent To |
|
|
Notes |
2003-02-03 00:00:00 | MECHANICAL PERMIT 02060887 | | MECH REV - DUCT SIZE PLAN SHEET M-205 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
11 |
Status |
P |
Date |
2003-01-30 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-01-30 |
Time |
09:54 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2003-01-30 |
Time |
09:54 |
Sent To |
|
|
Notes |
2003-01-30 00:00:00 | MECHANICAL REV M-205 PERMIT 02060887 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
10 |
Status |
P |
Date |
2002-12-30 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-12-30 |
Time |
15:51 |
Rev Time |
1.00 |
Received By |
hmoser |
Date |
2002-12-30 |
Time |
15:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
9 |
Status |
P |
Date |
2002-12-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-12-12 |
Time |
14:27 |
Rev Time |
1.00 |
Received By |
pkrauss |
Date |
2002-12-12 |
Time |
14:27 |
Sent To |
|
|
Notes |
2002-12-12 00:00:00 | MECH REV PERMIT 02060887 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
8 |
Status |
F |
Date |
2002-12-09 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-12-09 |
Time |
11:09 |
Rev Time |
1.40 |
Received By |
pkrauss |
Date |
2002-12-09 |
Time |
10:52 |
Sent To |
|
|
Notes |
2002-12-09 00:00:00 | DENIED: | | | | PLANS SUBMITTED HAVE TO BE APPROVED BY | | THE ENGINEER OF RECORD.PLEASE HAVE | | PLANS SIGNED, DATED, & RAISED SEAL | | AFFIXED ON PLAN AS PER FAC 61G15-23.002 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
7 |
Status |
P |
Date |
2002-08-19 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-08-19 |
Time |
08:12 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2002-08-19 |
Time |
07:53 |
Sent To |
|
|
Notes |
2002-08-19 00:00:00 | REVISION 11 & 12 - EXHAUST FOR THE MECH | | RM. REFRIGERANT PURGE EXHAUST. | | SUBMITTAL LTR FROM ENG OF RECORD | | CHILLERS REFRIGERANT CHARGE IS 850 LBS | | NOT 1250 LBS AS ORIGINALLY SUBMITTED. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2002-07-26 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-07-26 |
Time |
06:44 |
Rev Time |
0.25 |
Received By |
ndenmark |
Date |
2002-07-26 |
Time |
06:44 |
Sent To |
|
|
Notes |
2002-07-26 00:00:00 | REVISION 6/24/02 RINKER LOBBY | | AHU LOCATION REQUIRES ACCESS FOR SERVICE | | AND REPLACEMENT OF EQUIPMENT WITHOUT | | AFFECTING COMPONENTS OF PERMANENT | | BUILDING CONSTRUCTION. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
F |
Date |
2002-07-18 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-07-18 |
Time |
12:04 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2002-07-18 |
Time |
12:04 |
Sent To |
|
|
Notes |
2002-07-18 00:00:00 | CORRECTIONS NOT COMPLETE | | | | ADD FIRE DAMPERS TO TWO DUCTS LEAVING | | SHAFT BY OFFICE M-18 ON SHT M-2.04. | | | | NOTE ON M-301 RELIEF TO BE 20 FEET ABOVE | | GRADE ALSO NEEDS TO BE MIN. 15 FEET | | FROM ANY AIR INTAKE OPENING. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2002-06-14 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-06-14 |
Time |
11:46 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2002-06-14 |
Time |
11:45 |
Sent To |
|
|
Notes |
2002-06-14 00:00:00 | PROVISO: | | | | COMMENTS BY NANCY DENMARK (6-7-02), | | SHALL BE ADDRESSED BY REVISION AND | | SUBMITTED WHEN PERMIT IS ISSUED & | | PICKED UP. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2002-06-07 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-06-07 |
Time |
04:53 |
Rev Time |
2.00 |
Received By |
ndenmark |
Date |
2002-06-07 |
Time |
04:53 |
Sent To |
|
|
Notes |
2002-06-07 00:00:00 | DENIED: | | | | 1. M-2.01 NO F/D AT 10X10 DUCT INTO VEST | | SB-004. | | 2. M-2.04 NO F/D AT 24X24 DUCT INTO FEC | | SURFACE RM. | | 3. M-2.04 NO F/D (X2) AT DUCTS LEAVING | | SHAFTS BY OFFICE M-18. | | 4. M1.02 NOTE #9 SHOWS .588 IPLV FLORIDA | | ENERGY CODE MINIMUM IS 5.3 IPLV | | | | PROVISO ITEMS BELOW: | | 1. SIGNAGE AT DOORS TO CHILLER ROOM PER | | FBC(M) 1105.1 PROHIBITING ACCESS BY | | OTHERS WILL BE REQUIRED. | | 2. EXISTING AHU IN CHILLER ROOM TO BE | | SEALED FBC(M) 1105.4. | | 3. TERMINATION OF CHILLER RELIEF PIPING | | SHALL BE PER FBC(M) 1105.9- MINIMUM 15 | | FEET ABOVE ADJOINING GRADE AND NOT LESS | | THAN 20 FEET FROM ANY WINDOW, | | VENTILATION OPENING, OR EXIT. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2002-05-16 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-05-16 |
Time |
14:19 |
Rev Time |
3.00 |
Received By |
ndenmark |
Date |
2002-05-16 |
Time |
14:19 |
Sent To |
|
|
Notes |
2002-05-16 00:00:00 | ***********DENIED*********************** | | | | THE FOLLOWING ITEMS HAVE NOT BEEN | | CORRECTED FROM THE FIRST REVIEW. | | | | 1. M-2.01 NO F/D AT 12X8 AND 10X10 DUCTS | | INTO VEST SB-004 | | 2. M-2.03 NO F/D AT 18X18 DUCT | | PENETRATION ABOVE RATED DOORS SERVICE | | CORRIDOR G-22 NEAR COLUMN LINES A AND | | 2A. | | 3. M-2.04 NO F/D (X2) AT 24X24 DUCT INTO | | FEC SURFACE ROOM. | | 4. M-2.04 NO F/D (X2) AT DUCTS LEAVING | | SHAFT BY OFFICE M-18. | | 5. M-2.04 NO F/D AT SHAFT BY ELEVATOR | | NO. 3. | | 6. M-2.04 NO F/D AT (DUCT SIZE COVERED | | BY F/D SYMBOL) PENTRATION INTO STORAGE | | ROOM M-02. | | 7. M-2.04 NO F/D (X2) AT 36X20 AND 60X18 | | DUCTS INTO STORAGE RM M-02. | | 8. M-2.05 NO F/D AT 12X6 DUCT INTO | | VISITORS OFFICE 2-46. | | 9. M-2.06 NO F/D AT 12X10 DUCT BY ELEC | | RM 3-017. | | 10. M-2.06 NO F/D AT 70X24 DUCT INTO | | MECH SPACE 3-016. | | 11. M-2.06 NO F/D AT 30X20 DUCT | | PENETRATION OF SHAFT WALL IN MECH SPACE | | 3-020. | | 12. M-2.06 NO F/D AT 12X6 DUCT INTO | | RESTROOM 3-020 | | 13. M-2.06 NO F/D AT 60X18 DUCT INTO | | CONFERENCE ROOM 3 F05. | | 14. M-2.06 NO F/D AT 50X20 DUCT INTO | | FINANCE CUBICLES RM 3 F06. | | 15. M-2.06 NO F/D AT 24X8 DUCT (X2 | | PLACES) EAST SIDE OF CORRIDOR 3-010. | | 16. M-2.06 NO F/D AT 20X14 DUCT INTO | | WOMEN'S VESTIBULE 3-006. | | 17. M-2.06 NO F/D AT 18X8 DUCT INTO | | MEN'S VESTIBULE 3-005. | | 18. M-3.01 SHOW LOCATIONS OF REQUIRED | | HORN AND STROBE FOR REFRIGERANT LEAK | | DETECTION INSIDE AND OUTSIDE OF | | MACHINERY ROOM. | | 19. M-3.01 WHAT AREA DOES EXISTING AHU | | SERVICE? | | 20. M-2.06 2 VCV MARKED #14 | | 21. M-2.06 NO VCV MARKED #25. | | 22. M-2.06 NO VCV MARKED #27M-2.06 VCV | | #5 DISTRIBUTION EXCEEDS SCHEDULE. | | 23. M-2.06 FCU#8 STIIL SHOWS TWO SUPPLY | | DROPS AND NO RETURN. | | 24. FLORIDA ENERGY CODE REQUIRES | | CHILLERS TO COMPLY WITH TABLE 4-5 (IPLV | | MIN. 5.3 DOES NOT SHOW NPLV) | | 25. FLORIDA ENERGY CODE REQUIRES FCU TO | | COMPLY WITH APPROPRIATE TABLE 4-3 OR | | 4-4. | | 26. FBC(M) 306.1 REQUIRES CLEARANCE | | AROUND EQUIPMENT TO PERMENT | | CONTRUCTION SHALL BE SUFFICIENT TO | | ALLOW INSPECTION, SERVICE, REPAIR OR | | REPLACEMENT WITHOUT REMOVING ELEMENTS | | OF PERMANENT CONSTRUCTION. PROVIDE SUCH | | CLEARANCES BY ALL EQUIPMENT. | | 27. M-2.05 NO VCV#3 , NO VCV #1 TWO | | VCV'S LABELED #14. | | 28. PLAN SHOWS COIL PULL, NOT ELECTRICAL | | SERVICE ACCESS OR ACCESS TO FAN | | SECTION | | 29. M-2.06 FCU-8 HAS NO | | CLEARANCE SHOWN SHOW COMPLIANCE WITH | | 306.1 | | 30. LAYOUT AND COIL PULL FOR AHU 1 AND 2 | | UNCLEAR, IT APPEARS COIL PULL FOR AHU 2 | | IS ON TOP OF DUCT FOR AHU 1. PLEASE | | CLARIFY SERVICE ACCESS AND COMPLIANCE | | WITH 306.1 | | 31. CHILLER RELIEF PIPING SHALL COMPLY | | WITH FBC(M) 1105.9. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-04-05 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-04-05 |
Time |
13:16 |
Rev Time |
5.00 |
Received By |
ndenmark |
Date |
2002-04-05 |
Time |
13:16 |
Sent To |
|
|
Notes |
2002-04-05 00:00:00 | **************DENIED******************** | | | | 1. AHU # 7 HAS NO OUTSIDE AIR VALUE ON | | SCHEDULE. | | 2. THE LOCATION AND INSTALLATION DETAILS | | OF ALL FIRE DAMPERS SHALL BE LOCATED ON | | THE PLANS BY THE DESIGNER PER | | 2001FBC(M). PLEASE INDICATE ALL FIRE | | DAMPERS IN DUCTS PENETRATING RATED | | WALLS. | | 3. M 203 VCV 2 PLAN CFM = 2275. SCHEDULE | | ONLY CALLS FOR 1875 CFM. | | 4. M 205 VAV 9 PLAN CFM = 1350. SCHEDULE | | ONLY CALLS FOR 1275 CFM. | | 5. M 206 VAV 5 DISTRUIBUTION EXCEEDS | | SCHEDULE | | 6. M 206 VAV 15 2 MARKED ON PLAN, NO 14 | | INDICATED. | | 7. M206 VAV 15 PLAN CFM= 2000. SCHEDULE | | CALLS FOR 1200 CFM. | | 8. M 206 (2) VAV 26 SHOWN W/ DIFFERENT | | TOTAL CFM ON PLAN | | 9. VAV IN CONFERENCE RM 3-X04 NOT | | MARKED. | | 10. DEFINE FUNCTION OF FCU 8 BOTH DROPS | | SHOW SUPPLY AIR, NO PIPING TO UNIT, NO | | CFM. | | 11. INDICATE EQUIPMENT ENERGY RATING ON | | SCHEDULE. | | 12. BALANCED AIR RETURN PER FBC(M) | | 406.1REQUIRED FOR ALL SPACES. | | 13. PROVIDE MECHANICAL ROOM DRAWING FOR | | AHU INSTALATION DETAILS AND CLARITY TO | | SHOW SERVICE ACCESS REQUIREMENTS | | INCLUDING COIL PULL AND OTHER REQUIRED | | FLOOR AREA TO BE LEFT OPEN FOR SERVICE. | | 14. M 301. PROVIDE INFORMATION ON RELIEF | | PIPING TERMINATION FOR CHILLER | | EQUIPMENT. | | 15. PROVIDE REFRIGERANT INFORMATION | | INCLUDING QUANTITIES AND VENTILATION | | CALCULATIONS FOR COMPLIANCE WITH FBC(M) | | CH 11. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
14 |
Status |
F |
Date |
2003-09-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-09-29 |
Time |
11:56 |
Rev Time |
2.25 |
Received By |
kstevens |
Date |
2003-09-29 |
Time |
11:56 |
Sent To |
|
|
Notes |
2003-09-29 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FLORIDA ADMIN. CODE | | FBC-2001 CHAPTER 1 | | | | 1) SHT P-201 REVISION SHOWS REVISION #9 | | AS LAST REVISION. THE LATEST REVISION, | | SIGNED AND SEALED 8-14-02 HAS REVISIONS | | #'S 10, 11, 12, AND 13. PLEASE CLAIRFY. | | NUMEROUS REVISIONS NOT CLOUDED. ALSO | | TRIANGLE WITH REVISION NUMBER REQUIRED | | AT EACH REVISION. COL. LINE NUMBER AND | | LETTERS REQUIRED FOR REFERENCE. | | 2) SHT P-202 SHEET REVISIE HAS INFORMAT- | | ION DELETED THAT WAS APPROVE ON PRIOR | | REVIEWS. WATER LINES, CONDENSATE, RWL'S | | ECT HAVE BEEN DELETED. PLEASE CLAIRFY. | | COL. LINE TO BE SHOWN FOR REFERENCE. | | CLOUD ALL REVISIONS AND INDICATE WITH A | | TRIANGLE NUMBER. | | 3) SHT P-202 PIPING FROM PREVIOUS REV- | | IEWS HAS BEEN DELETED. NEW REVISIONS | | HAVE NOT BEEN CLOUDED OR INDICATED. | | 4) ALL SHEETS REVISIONS FROM PREVIOUS | | REVISIONS SHALL BE SHOWN AND ALL NEW | | REVISIONS SHALL BE INDICATED WITH CLOUDS | | AND NUMBERED. UNABLE TO FINISH REVISION | | REVIEW. | | 5) FEE DUE FOR REVISION - $50 PLUS $60 | | FOR SIX SHEETS SUBMITTED FOR REVISION | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
13 |
Status |
P |
Date |
2003-06-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-06-30 |
Time |
10:32 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2003-06-30 |
Time |
10:32 |
Sent To |
|
|
Notes |
2003-06-30 00:00:00 | REVISIONS SHTS P-203, P-204, & P-403 | | AREA DRAINS TO STORM - PIPING LOCATIONS |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
12 |
Status |
P |
Date |
2003-04-25 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-04-25 |
Time |
07:18 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2003-04-24 |
Time |
18:49 |
Sent To |
|
|
Notes |
2003-04-25 00:00:00 | REVISION OK - ADD 4 LAVS 3RD FLOOR | | CHNG TO FLOOR PLAN, SANT. RISER & WATER | | RISER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
11 |
Status |
P |
Date |
2002-11-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-11-01 |
Time |
18:10 |
Rev Time |
1.50 |
Received By |
kstevens |
Date |
2002-11-01 |
Time |
18:10 |
Sent To |
|
|
Notes |
2002-11-01 00:00:00 | REVISION OK - SHTS P203, P205, P206, | | P401, & P402 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
10 |
Status |
P |
Date |
2002-09-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-09-06 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-09-06 |
Time |
15:15 |
Sent To |
|
|
Notes |
2002-09-06 00:00:00 | REVISION OK - NEW TRENCH DRAIN TO STORM | | SHTS SKP-12/SKP-13 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
9 |
Status |
P |
Date |
2002-08-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-08-28 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-08-28 |
Time |
09:12 |
Sent To |
|
|
Notes |
2002-08-28 00:00:00 | REVISION - AS BUILT - SHTS P201/P203 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
8 |
Status |
P |
Date |
2002-07-26 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-07-26 |
Time |
09:05 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-07-26 |
Time |
09:05 |
Sent To |
|
|
Notes |
2002-07-26 00:00:00 | REVISION OK - CHANGE BLDG DRAIN FROM 4" | | TO 8", EXISTING 6" NOT EXISTING. - RE- | | ROUTE EAST BAR AND GANG BATHS TO NEW | | BLDG DRAIN - MOVE RISER LOCATION - SHOW | | CANOPY DRAINS TO STORM DRAIN OUT OF BLDG |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
7 |
Status |
P |
Date |
2002-07-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-07-20 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-07-20 |
Time |
13:48 |
Sent To |
|
|
Notes |
2002-07-20 00:00:00 | REVISION OK - CHANGE IN LOBBY. MOVE | | FAMILY TOILES - ICE MACHINE DRAIN MOVED. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
P |
Date |
2002-07-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-07-06 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-07-06 |
Time |
16:51 |
Sent To |
|
|
Notes |
2002-07-06 00:00:00 | REVISION OK - STORM CHANGES - WATER | | RISER CHANGES - SPEC FOR HDCP W/C'S | | 1'6" TO CENTER - CONDENSATE CHANGE - | | ECT. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2002-06-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-06-18 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-06-18 |
Time |
14:56 |
Sent To |
|
|
Notes |
2002-06-18 00:00:00 | SUBMITTAL OK - OFFSET WATER LINES (FIRE | | & DOMESTIC) |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2002-06-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-06-14 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-06-14 |
Time |
15:45 |
Sent To |
|
|
Notes |
2002-06-14 00:00:00 | PASSED/PROVISO | | | | THE COMMENTS FROM THE PLUMBING PLAN RE- | | VIEW DATED 6-11 WILL BE ADDRESS BY RE- | | VISED LANS SUBMITTED AT THE TIME OF PER- | | MIT ISSUANCE, SUBJECT TO SUBSEQUENT RE- | | VIEW. | | DISHWASHER SHALL DRAIN INTO SANITARY | | NOT GREASE LINE. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2002-06-11 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-06-11 |
Time |
13:18 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-06-08 |
Time |
17:21 |
Sent To |
|
|
Notes |
2002-06-13 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | FBC-2001 PLUMBING | | FBC-2001 FUEL GAS | | | | 1) PLANS TO BE ROUTED TO DBPR HOTEL AND | | RESTURANT DIVISION FOR PLAN REVIEW BE- | | FORE PLUMBING PLAN REVIEW. (RESPONSE NO- | | TED) | | 2) SANITARY PIPE SIZE NOT CORRECT. ONLY | | 180 FU FOR 4" PIPE @ 1/8" PER FOOT FALL. | | PLEASE ADJUST PIPE SIZE.(TALKED TO ENG.) | | 3) SHT P-401 SANT RISER DIAGRAM FLOOR | | DRAIN AT WATER TO REFLECT FLOOR PLAN & | | SHOW AS FLOOR SINK. (DISCUSSED WITH ENG) | | 4) SHT P-402 WATER RISER DIAGRAM, ALL | | WATER HAMMER ARRESTORS NOT LOCATED NEAR | | FIXTURES. PLEASE CHANGE (DISCUSSED WITH | | ENG.) | | 5) GAS REVIEW NOT DONE - ENGINEER SAYS | | INFORMATION SHALL BE SUBMITTED WITH GAS | | PERMIT APPLICATION. | | 6) CONDENSATE SHALL BE PIPED SEPARATE | | FROM BLDG. SHT P-201 COLS. B/11 EXCEPT- | | ION. (DISCUSSED WITH ENG.) | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-05-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-21 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-21 |
Time |
10:28 |
Sent To |
|
|
Notes |
2002-05-21 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | FBC-2001 PLUMBING | | FBC-2001 FUEL GAS | | | | 1) SHT P-101 ICE MACHINE DETAIL - FILTER | | SHALL BE NSF COMPLIANT. SUBMIT MANUF. IN | | FORMATION. | | 2) SHT P-101 SUBMERSIBLE SUMP PUMP, MAN- | | UFACTURE INFO SHOWING LISTING REQD. | | 3) SHTS P-202, 203, ALL | | CONDENSATE SHALL BE PIPED SEPARATELY TO | | THE OUTSIDE OF BLDG AND TIED INTO STORM | | OR DRYWELL. SEE COLS. 14-A/B, 11-B/C | | SHT P-202. SEE RM #G-05 SHT P-203. | | 4) SHT P-201, ELEVATOR #1 DRAINS TO RAIN | | WATER CATCH BASIN AND HAS NO BACKWATER | | VALVE. ELEVATOR #3 HAS AN AREA DRAIN | | WITH A BACKWATER VALVE IN LINE AND DIS- | | CHARGES TO AN OIL AND SAND INTERCEPTOR. | | PLEASE CHECK WITH ELEVATOR COMPANY TO | | SEE IF THIS IS ACCEPTABLE TO HOOK UP | | DIRECTLY IN ELEVATOR PIT. | | 5) PLEASE ROUTE PLANS THROUGH DEPT OF | | BUSINESS HOTEL AND RESTURANT DIVISION | | FOR PLAN REVIEW BEFORE RESUBMITTING FOR | | PLAN REVIEW. | | 6) SHT P-302 ITEMS #82/115 FILTERS, NSF | | APPROVAL REQUIRED. SUBMIT MANUF. INFO | | 7) PLEASE SHOW FIXTURE UNITS AS THEY | | ACCUMULATE ON THE SANITARY RISER DIAGRAM | | 8) SHT P-401 MECH ROOM M-13 FLOOR DRAIN | | NOT SHOWN ON SANT RISER DIAGRAM. | | 9) SHT P-401 SANT RISER FOR MECH ROOMS | | M-13, 2-28, 3-016 NOT SHOWN ON SANT RIS- | | ER DIAGRAM. PLEASE SHOW RISER AS SHOWN | | ON FLAT DRAWING IN WOMENS ROOM G-39 & | | MENS ROOM G-40, PICKING UP ALL MECH RMS | | AND VENT THROUGH ROOF. | | 10) SHT P-401 FLOOR DRAIN ON SANT RISER | | DIAGRAM SHOULD BE CHANGED TO FLOOR SINK | | AT WATER HEATER. (CHANGED ON FLOOR PLAN) | | 11) SHT P-402 KITCHEN EQUIP PLMG SCHED., | | SHOWS 1 FRYER, GAS RISER SHOWS 2. PLEASE | | CLAIRFY. | | 12) SHT P-402 WATER RISER DIAGRAM, ALL | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | NEAR FIXTURES IN AN "EFFECTIVE RANGE" | | NOT AT TOP OF DROP. LOCATE PER MANUFACT- | | URE INSTALLATION INSTRUCTIONS AND PDI- | | WH 201. (SOME CHANGED NOT ALL) | | 13) ALL GAS PERMIT APPLICATION REQUIRE- | | MENTS FROM PREVIOUS REVIEW HAVE NOT BEEN | | ADDRESSED. PLEASE SUBMIT INFORMATION. | | 14) SHT A-106 & A-210 CEO TOILET ROOM | | CAN NOT CHANGE FLOOR PLANS TO COMPLY | | WITH ADAPTABILITY. STRUCTURAL CHANGES | | FOR ADAPTABILITY IS NOT APPROVED. | | PLEASE SHOW DETAILS FOR ADAPTABILITY. | | SHOWER CURB TO BE NO MORE THAN 1/2", | | BACKING FOR ALL GRAB BARS, SPACING FOR | | W/C ECT. | | 15) TO WHERE DOES THE RAIN WATER FROM | | THE CANOPY DRAIN? | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-04-09 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-09 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-09 |
Time |
11:13 |
Sent To |
|
|
Notes |
2002-04-09 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 FUEL GAS | | | | 1) SHT P-101 ICE MACHINE DETAIL-ALL IN- | | DIRECT WASTE SHALL DRAIN TO FLOOR SINK, | | NOT FLOOR DRAIN AS SHOWN | | 2) SHT P-101 ICE MACHINE DETAIL - FILTER | | SHALL BE NSF COMPLIANT. SUBMIT MANUF. IN | | FORMATION. | | 3) SHT P-101 SUBMERSIBLE SUMP PUMB - | | MANUFACTURE INFORMATION WITH LISTING REQ | | 4) SHT P-101 PLMG FIXTURE SCHED AND SPEC | | FUNNEL FLOOR DRAIN NOT APPROVED. DELETE | | 5) SHT P-201 SEPARATE PERMIT REQUIRED | | FOR OIL AND SAND INTERCEPTOR - TO BE | | SIZED BY RODNEY COMPO ENVIRONMENTAL | | COMPLIANCE (561) 837-4074. | | 6) SHT P-201 SEPARATE PERMIT REQUIRED | | FOR GREASE TRAP - TO BE SIZED BY RODNEY | | COMPO, ENVIRONMENTAL COMPLIANCE (561) | | 837-4074 WASTE ORD. #2938-96 | | 7) SHTS P-201, 202, 203, 204, & 205 - | | ALL CONDENSATE FROM A/C SHALL BE PIPED | | SEPARATE TO OUTSIDE OF BLDG AND BE TIED | | INTO SANITARY OR DRYWELL WITH A RELIEF | | VENT INSTALLED AS PIPE EXITS BLDG. (SEE | | COL'S 14-B/C, 14-A/B, 11-B/C - P-202 COL | | 2-B/C, 11-B FUNNEL DRAIN NOT APPROVED, | | P-203 COL 11-B CONDENSATE TO JANITOR | | ROVED, 2-A CONDENSATE TO HUB DRAIN NOT | | APPROVED, RM# G-05 COND TO SANT NOT APP- | | ROVED - P-204 COL 1/2 - B/C COND. TO | | SANT NOT APPROVED, COL 2-D CONDENSATE | | FROM WALK IN COOLER SHALL DRAIN TO FLOOR | | SINK, FUNNEL FLOOR DRAIN NOT APPROVED, | | COL 12-C, SHT P-205 COL 1/2 - B/C, SHT | | P-206 IN MECH ROOM, SHT P-207 ELEV ROOM) | | 8) SHT P-201, ELEVATOR #1 DRAINS TO RAIN | | WATER CATCH BASIN AND HAS NO BACKWATER | | VALVE. ELEVATOR #3 HAS AN AREA DRAIN | | WITH A BACKWATER VALVE IN LINE AND DIS- | | CHARGES TO AN OIL AND SAND INTERCEPTOR. | | PLEASE CHECK WITH ELEVATOR COMPANY IF | | THIS WILL BE EXCEPTABLE TO HOOK THESE | | UP DIRECTLY TO ELEVATOR PIT. | | 9) SHT P-204 WATER HEATER DETAIL, P/T | | RELIEF DISCHARGE SHALL NOT DRAIN TO | | FLOOR DRAIN. FLOOR SINK REQUIRED FOR ALL | | INDIRECT WASTE. FBC 2001 SEC 802.3 | | 10) SHT P-204 WATER HEATER DETAIL, SHUT | | OFF VALVE REQUIRED ON EACH SIDE OF CIRC. | | PUMP. | | 11) SHT P-206 SAFE WASTE DETAIL, NOT | | APPROVED - DELETE | | 12) SHT P-301 #'S 24, 25, 26 FUNNEL | | FLOOR DRAIN NOT APPROVED, FLOOR SINK RE- | | QUIRED FOR INDIRECT WASTE. SEC 802.3 | | 13) ROUTE PLANS THROUGH DEPT OF BUSINESS | | HOTEL AND RESTURANT DIVISION FOR PLAN RE | | VIEW BEFORE RESUBMITTING FOR CONST PLAN | | REVIEW. | | 14) PROVIDE CALCULATIONS FOR MINIMUM | | FACILITIES PER FBC-2001 PLUMBING TABLE | | 403.1 AND SEC 403. | | 15) SHT P-302 ITEMS #82/115 FILTERS, NSF | | APPROVAL REQUIRED. SUBMIT MANUF. INFO. | | 16) SHT P-302 ITEM #84 ICE MACHINE W/BIN | | NOT FOUND. | | 17) SHT P-302 ITEM #105 PLEASE CALL OUT | | 2ND DRAIN BOARD. | | 18) SHT P-302 ITEMS #134 & 136 NOT FOUND | | 19) PLEASE SUBMIT A SANITARY RISER DIA- | | GRAM WITH ALL THE PIPE SIZES AND SHOW | | FIXTURE UNITS AS THEY ACCUMULATE IN SYS- | | TEM. | | 20) SHT P-401 ROOM G-20 FLOOR DRAIN NOT | | SHOWN ON SANT RISER DIAGRAM. | | 21) SHT P-401 ROOM G-17 MENS FLOOR DRAIN | | NOT SHOWN ON SANT RISER DIAGRAM. | | 22) SHT P-401 MECH ROOM FLOOR DRAIN NOT | | SHOWN ON SANT RISER DIAGRAM. NOT FOR CON | | 23) SHT P-401 2" WASTE UP BETWEEN ROOM | | 2-E11 & #1 ELEVATOR NOT SHOWN ON SANT. | | RISER DIAGRAM. | | 24) SHT P-402 KITCHEN EQUIP PLMG SCHED. | | SHOWS 1 FRYER, GAS RISER SHOWS 2. ?? | | 25) SHT P-402 WATER RISER DIAGRAM, ALL | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | NEAR FIXTURE IN AN "EFFECTIVE RANGE" NOT | | AT TOP OF DROP AS SHOWN ON PLANS. LOCATE | | PER MANUFACTURE INSTALLATION INSTRUCTION | | AND PDI-WH 201. | | 26) SHT P-403, SHOW PIPE SIZES FOR ALL | | PIPING TO AREA DRAINS. SHOW SQUARE FOOT- | | AGE FOR ALL AREA DRAINS IN SYSTEM. COND. | | TO RUN SEPARATELY OUT OF BLDG AND TIE | | INTO STORM OUTSIDE. SUBMIT CONDENSATE | | RISER, SHOW RELIEF VENT AS COND. EXITS | | BLDG. | | 27) SHT P-403 STORM RISER DIAGRAM, PLEA- | | SE PROVIDE SQ FT OF GUTTER DRAINS ADDED | | TO ROOF DRAINS. | | 28) SHT P-403 STORM RISER DIAGRAM, UN- | | DERGROUND PIPE AT COLS 14-B/C SHOWS 6", | | THEN 8". PLEASE CLAIRFY | | 29) FOLLOWING INFORMATION REQUIRED FOR | | GAS PERMIT APPLICATION. | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | GAS CODE. | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. | | 3. TYPE OF GAS, (LP OR NATURAL) | | 5. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2001 FUEL GAS CODE. | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2001 FUEL GAS CODE IF NATURAL | | GAS SPECIFY .5 PSI OR 2 PSI. | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND FBC-2001 | | FUEL GAS CODE. | | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | 30) SHT A-206 FAMILY TOILETS G-14, G-31, | | AND DETAIL #12. SHOW CLEAR FLOOR SPACE | | FOR HDCP FIXTURES. DOOR SWING SHALL NOT | | OPEN INTO CLEAR FLOOR SPACE OR UNOBSTRUC | | TED TURNING RADIUS. SHOW ON DETAIL. | | 31.SHT A-209 DETAIL #8 SHOWS 4 W/C'S | | WEST OF HDCP STALL, DETAIL #3 SHOWS 3 | | W/C'SWEST OF HDCP STALL AND 1 EAST IN | | WOMENS TOILET. PLEASE CLAIRFY. ALSO GIVE | | DIMENSIONS FOR 2ND HDCP STALL WITH GRAB | | BARS IN IT. | | 32) SHT A-210 DETAIL #11 LAV CAN NOT BE | | ON WALL OPPOSITE OF W/C IN UNISEX TOILET | | 66" CLEAR FLOOR SPACE REQUIRED FIG. 28 | | 33) SHT A-210 DETAILS #1, 5, 8 SHOW | | CLEAR FLOOR SPACE FOR HDCP FIXTURES. | | DOOR CAN NOT OPEN INTO CLEAR FLOOR SPACE | | FOR FIXTURES. ROOMS #3-020, 3-021, AND | | 3-009. | | 34) SHT A-210 DETAIL #9 SOUTH ELEVATION, | | LAV NOT SHOWN. | | 35) SHT A-209 DETAILS #4 & 5 SHOW CONT- | | ROL AREA FOR SHOWER ON DETAILS. 4.21.5 | | 36) SHT A-209 DETAIL #1 MENS/WOMENS | | DRESSING ROOMS - BENCH REQUIRED SEC | | 4.35.4 | | 37) SHT A-210 DETAILS #6 & 7 SHOW CONT- | | ROL AREA FOR SHOWER ON DETAILS. 4.21.5 | | 38) SHTS A-106 & A-210 CEO TOILET SHALL | | BE ADAPTABLE PER SEC 4.1.3(11) PROVIDE | | DETAILS | | 39) SHT C-8 SEE ATTACHED SHEET FOR APP- | | ROVED GREASE TRAP DETAIL. CITY OF W.P.B | | UTILITY APPROVED. | | 40) WHERE DOES RAIN WATER FROM CANOPY | | DRAIN TO? | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
P |
Date |
2002-08-19 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-08-19 |
Time |
11:44 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
F |
Date |
2002-08-15 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-08-15 |
Time |
08:39 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-08-15 00:00:00 | DENIED,NEED LETTER FROM KRAVIS OWNERS | | STATING TEMP PARKING LOT TO BE REMOVED | | BEFOREC/O |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2002-06-14 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-06-14 |
Time |
15:21 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2002-06-14 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-06-14 |
Time |
15:52 |
Rev Time |
0.21 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2002-04-05 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-04-05 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-05 00:00:00 | DENIED, KRAVIS MUST TAKE OWNERSHIP OF | | PARKING GARAGE BEFORE ANY BULDING | | PERMITS CAN BE APPROVED. | | LANDSCAPE PLAN WAS APPROVED BY JM |
|
|