Plan Review Details - Permit 02030623
Plan Review Stops For Permit 02030623
Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-04-23 Cont ID  
Sent By pkrauss Date 2002-04-23 Time 16:25 Rev Time 0.30
Received By pkrauss Date 2002-04-23 Time 16:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-03-15 Cont ID  
Sent By pkrauss Date 2002-03-15 Time 14:03 Rev Time 0.35
Received By pkrauss Date 2002-03-15 Time 14:03 Sent To  
Notes
2002-03-15 00:00:00 
 HISTORICAL O.A. NOT REQUIRED DUE TO
 CONTRUCTION OF BUILDING.
  
 AS PER 2001 FBC, MECHANICAL 601.4,
 PROVISIONS SHALL BE MADE IN RESIDENTIAL
 BUILDINGS TO AVOID UNBALANCED AIR FLOWS
 & PRESSURE DIFFERENTIALS CAUSED BY
 RESTRICTED AIR RETURN.PRESSURE
 DIFFERENTIALS ACROSS CLOSED DOORS WHERE
 RETURNS ARE CENTRALLY LOCATED SHALL BE
 LIMITED TO .001" WC OR LESS.PROVIDE
 AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-08 Cont ID  
Sent By pkrauss Date 2002-03-08 Time 07:47 Rev Time 0.30
Received By pkrauss Date 2002-03-08 Time 07:40 Sent To  
Notes
2002-03-08 00:00:00 
 3 SETS OF ENERGY CALCS SUBMITTED - NO
 PLANS CALLED CONTRACTOR...BRINGING IN
 PLANS.