Plan Review Details - Permit 02030183
Plan Review Stops For Permit 02030183
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-09-11 Cont ID  
Sent By hpiskura Date 2002-09-11 Time 10:57 Rev Time 0.00
Received By hpiskura Date 2002-09-11 Time 10:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-05-31 Cont ID  
Sent By hpiskura Date 2002-05-31 Time 13:17 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-14 Cont ID  
Sent By hpiskura Date 2002-05-14 Time 09:43 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-05 Cont ID  
Sent By hpiskura Date 2002-04-05 Time 09:00 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-05 00:00:00THE ADDITION OF A SECOND STORY WILL
 CAUSE THIS BUILDING TO EXCEED THE
 ALLOWABLE ARE FOR A TWO STORY GROUP F
 OCCUPANCY, TYPE IV, FS CONSTRUCTION AS
 PROVIDED FOR IN FBC TABLE 500.THIS
 PROPOSED WORK DOES NOT COMPLY WITH
 MEZZANINE REQUIREMENTS SO IT WAS NOT
 REVIEWED IN THAT CONTEXT.
  
 WHAT WILL THE USE OF THIS SPACE BE?SEE
 FBC 104.3.1.1 FOR THE MINIMUM REVIEW
 CRITERIA, AND ADDRESS THE ITEMS
 PERTINENT TO THIS WORK.SEE ALSO FBC
 1606.1.7 INFORMATION ON DRAWINGS.
  
 THIS BUILDING WAS CONSTRUCTED AS A
 FACTORY INDUSTRIAL OCCUPANCY, IT
 APPEARS THAT THE PROPORTION OF OFFICE
 USE, GROUP B, MAY RESULT IN A CHANGE OF
 OCCUPANCY.THE CHANGE MUST MEET THE
 BUILDING CODE RESQUIREMENTS FOR THAT
 USE AND IMPACT FEES ADJUSTED WITH THE
 COUNTY.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-08-29 Cont ID  
Sent By dpalmer Date 2002-08-29 Time 05:42 Rev Time 0.50
Received By dpalmer Date 2002-08-29 Time 05:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-06-05 Cont ID  
Sent By dpalmer Date 2002-06-05 Time 12:02 Rev Time 0.00
Received By dpalmer Date 2002-06-05 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-05-16 Cont ID  
Sent By dpalmer Date 2002-05-16 Time 06:36 Rev Time 0.00
Received By dpalmer Date 2002-05-16 Time 06:36 Sent To  
Notes
2002-05-16 00:00:00************ NOTE ***********
  
 PLEASE NOTE THAT ELECTRICAL PLANS SEEM
 TO BE OK. HOWEVER CONTRACTOR NEEDS TO
 COME IN AND TAKE ALL REVISED SHEETS OUT
 AND INSERT NEW REVISED SHEETS TO MAKE
 THE SETS REQUIRED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-15 Cont ID  
Sent By dpalmer Date 2002-03-15 Time 06:46 Rev Time 0.00
Received By dpalmer Date 2002-03-15 Time 06:46 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-03-12 Cont ID  
Sent By mamini Date 2002-03-12 Time 15:34 Rev Time 0.00
Received By mamini Date 2002-03-12 Time 15:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-08-29 Cont ID  
Sent By mcarsill Date 2002-08-29 Time 15:21 Rev Time 0.00
Received By mcarsill Date 2002-08-29 Time 15:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-06-06 Cont ID  
Sent By mcarsill Date 2002-06-06 Time 08:54 Rev Time 0.00
Received By mcarsill Date 2002-06-06 Time 08:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-05-14 Cont ID  
Sent By mcarsill Date 2002-05-14 Time 16:40 Rev Time 0.00
Received By mcarsill Date 2002-05-14 Time 16:40 Sent To  
Notes
2002-05-14 00:00:001) ANOTHER EXIT SIGN IS NEEDED IN
 WORK AREA # 2 TO DIRECT PERSONS TO
 WORK AREA # 1.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-02 Cont ID  
Sent By mcarsill Date 2002-04-02 Time 14:24 Rev Time 0.00
Received By mcarsill Date 2002-04-02 Time 14:24 Sent To  
Notes
2002-04-02 00:00:00A) PLEASE EXPLAIN EXITING RATIONALE FOR
 SECOND FLOOR. IT APPEARS THAT ONLY
 A SINGLE MEANS OF EGRESS IS PRESENT FROM
 THE SECOND FLOOR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-09-10 Cont ID  
Sent By pkrauss Date 2002-09-10 Time 11:04 Rev Time 0.35
Received By pkrauss Date 2002-09-10 Time 10:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-08-20 Cont ID  
Sent By ndenmark Date 2002-08-20 Time 11:41 Rev Time 0.25
Received By ndenmark Date 2002-08-20 Time 11:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-28 Cont ID  
Sent By pkrauss Date 2002-05-28 Time 14:28 Rev Time 0.40
Received By pkrauss Date 2002-05-28 Time 14:28 Sent To  
Notes
2002-05-28 00:00:00MECHANICAL PERMIT 02030186
 PLANS APPROVED PER NANCY DENMARK 3/25/02
  
 RESUB 5/2/02 - DELETED SECOND FLOOR

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-25 Cont ID  
Sent By ndenmark Date 2002-03-25 Time 15:04 Rev Time 0.33
Received By ndenmark Date 2002-03-25 Time 15:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-08-31 Cont ID  
Sent By kstevens Date 2002-08-31 Time 09:25 Rev Time 0.00
Received By kstevens Date 2002-08-31 Time 09:25 Sent To  
Notes
2002-08-31 00:00:00REVISION OK - MOVED SINK IN COUNTER -
 MOVED DRINKING FOUNTAIN ACROSS CORRIDOR
 AND CHANGED FROM HIGH/LOW TO SINGLE. -
 CUP DISP REQD. A-1 - P2.1 - P3.1 - P5.1

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-12 Cont ID  
Sent By kstevens Date 2002-06-12 Time 14:46 Rev Time 0.00
Received By kstevens Date 2002-06-12 Time 14:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-25 Cont ID  
Sent By kstevens Date 2002-05-25 Time 13:11 Rev Time 0.00
Received By kstevens Date 2002-05-25 Time 13:02 Sent To  
Notes
2002-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) FROM PREVIOUS REVIEW, SHOWER STALL,
 SECTIONS 4.21.3, 4.21.5, 4.21.6, (60"
 MINIMUM - 59" SHOWN), & 4.21.7 HAVE NOT
 BEEN ADDRESSED.
 2) FROM PREVIOUS REVIEW, SHTS P2.1 AND
 P5.1 STILL SHOW FLOOR DRAINS AT WATER
 HEATER. PLEASE CHANGE PLANS TO SHOW A
 FLOOR SINK FOR INDIRECT WASTE.
 3) WHEN SUBMITTING PLANS PLEASE REMOVE
 ALL SHEETS THAT HAVE BEEN REVISED AND
 INSERT NEW SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-04 Cont ID  
Sent By kstevens Date 2002-04-04 Time 11:10 Rev Time 0.00
Received By kstevens Date 2002-04-04 Time 11:09 Sent To  
Notes
2002-04-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FACBC-97
  
 1) SHT PO.1 PLUMBING NOTES #13, REMOVE
 ALL REFERENCES TO AIR CHAMBERS. AIR
 CHAMBERS ARE NOT APPROVED IN FBC-2001
 2) SHOWER STALL ROOM NOT WIDE ENOUGH.
 SEE SECTIONS 4.21, 4.21.2, 4.21.3,
 4.21.4, 4.21.5, 4.21.6 AND 4.21.7.
 3) SUBMIT DETAIL FOR SHOWER STALL. SEE
 FIGS 35(A) & 35(B). COMPLY WITH FACBC
 SECTIONS 4.23,4.23.2, & 4.23.3.
 4) WATER HEATER. PROVIDE DETAIL FOR
 RELIEF OUTLET WASTE. IF DISCHARGE IS BE-
 ING DRAINED INTO FLOOR DRAIN, ALL IN-
 DIRECT WASTE SHALL BE DRAINED TO A FLOOR
 SINK. PLEASE CLAIRFY. FBC-2001 SECS
 504.7 & 504.7.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-06-12 Cont ID  
Sent By kstevens Date 2002-06-12 Time 14:46 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***