Plan Review Details - Permit 02030156
Plan Review Stops For Permit 02030156
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-06-19 Cont ID  
Sent By lsmith Date 2002-06-19 Time 09:04 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-05-13 Cont ID  
Sent By lsmith Date 2002-05-13 Time 11:09 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-05-13 00:00:00********************FAILED (2ND TIME)**
  
 THE FIRST REVIEW COMMENTS WERE NOT
 ADDRESSED.
  
 THE PLANS WERE RESUBMITTED WITH LOOSE
 PAGES & NOT IN ORDER.
  
 PLEASE REFER TO 1ST REVIEW NOTES AND
 CORRECT ITEMS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH: BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-20 Cont ID  
Sent By lsmith Date 2002-03-20 Time 13:45 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-03-20 00:00:00***************FAILED*************
  
 1. ALL RESIDENTIAL POOLS MUST COMPLY
 WITH THE FBC 2001,THE DRAWINGS MUST
 REFERENCE THE NEW CODE ON THE PLANS.
  
 3. EQUIPMENT SLAB DETAILS WITH ANCHORING
 DETAILS & TYPES OF ANCHORS SHOWN.
  
 4. ENGINEER OF RECORD MUST INCLUDE HIS T
 ITLE BLOCKON ALL DRFAWINGS SIGNED &
 SEALED BY HIM.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-11 Cont ID  
Sent By btrobaug Date 2002-03-11 Time 17:39 Rev Time 0.00
Received By btrobaug Date 2002-03-11 Time 17:26 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-18 Cont ID  
Sent By kstevens Date 2002-06-17 Time 10:43 Rev Time 0.00
Received By kstevens Date 2002-06-17 Time 10:43 Sent To  
Notes
2002-06-17 00:00:00PASSED/PROVISO
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 TWO MAIN DRAINS REQUIRED. SEE SPEC SHEET
 SHOWING DUAL MAIN DRAINS, AND SECTION
 424.2.6.6.4

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-06 Cont ID  
Sent By kstevens Date 2002-05-06 Time 17:40 Rev Time 0.00
Received By kstevens Date 2002-05-06 Time 17:40 Sent To  
Notes
2002-05-06 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. GENERAL NOTES
 STATES 424.A
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92. AND NSPI-5
 3) FBC-2001 SEC 424.2.6.3 WATER VELOCITY
 NOT TO EXCEED 10FT/SEC. (ADD TO NOTES)
 4) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)
 5) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 6) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 7) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 8) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 9) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 10) PLEASE NOTE THAT ALL SHEETS THAT ARE
 SIGNED AND SEALED SHALL HAVE A TITLE
 BLOCK INDICATING THEIR NAME, ADDRESS, &
 NUMBER.
 11) PLEASE NOTE THAT GENERAL NOTE SHEET
 IS NOT CLEAR AND READABLE. ALSO IT HAS
 THE TITLE BLOCK AND SIGNATURE OF ANOTHER
 ENGINEER.
 12) PLEASE NOTE THAT THERE ARE LOOSE
 PAGES THAT WERE SUBMITTED. PLEASE SUB-
 MIT 2 SETS OF POOL PLANS WITH ALL SHEETS
 FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-10 Cont ID  
Sent By btrobaug Date 2002-03-11 Time 17:39 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-03-10 00:00:00PLUMBING PLAN REVIEW,FBC 2001, DENIED.
 (1A)GENERAL NOTES #1 CURRENT CODE IN USE
 FBC 2001 SEC 424.2 PRIVATE SWIMMING POOL
 (1B) SEC 424.2.6 ENGINEERING DESIGN,
 PROVIDE A COPY OF CONTRACT.
 (2) SEC 424.2.6.3 WATER VELOCITY,NOT TO
 EXCEED 10FT/SEC.
 (3) SEC 424.2.6.6.2 SUCTION INLETS,
 PROVIDE CUT SHT ON TYPE OF COVER THAT
 HAS BEEN TESTED AND ACCEPTED.
 (4) SEC 424.2.6.6.5 CLEANER FITTING,
 SHOW LOCATION.
 (5) SEC 424.2.7.2 MOUNTING AND ANCHORING
 SWIMMING POOL EUIPMENT.
 (6) SEC 424.2.9 WATER SUPPLY, LOCAL ORD.
 #2853-95,BACKFLOW PREVENTER REQUIRED ON
 WATER SERVICE.
 (7) SEC 424.13.2,JOINTS AND CONNECTIONS
 FBC-2001 PLBG.SEC 605.21 PURPLE PRIMER
 REQUIRED ON PVC PIPING.
 (8) FL BUIILDING CODE, 2001 SEC 104.2.2
 DESIGN PROFESSIONAL, BLOCK STAMP IS
 REQUIRED WITH ENGINEERS SEAL.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-14 Cont ID  
Sent By sgraham Date 2002-05-14 Time 14:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***