Plan Review Stops For Permit 02030131 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2002-06-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-06-18 |
Time |
10:34 |
Rev Time |
0.25 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-06-18 00:00:00 | REVISION WIRE MESH SLAB SUPPORT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2002-05-16 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-05-16 |
Time |
14:09 |
Rev Time |
0.50 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-05-16 00:00:00 | ANY QUESTIONS PLEASE CALL, | | JIM WITMER | | BUILDING PLAN REVIEW | | DEPARTMENT OF CONSTRUCTION SERVICES | | CITY OF WEST PALM BEACH | | (561) 659-8096 EXT. 8412 | | FL BLDG 1909.3 (EXEPTION# 2) | | CONCRETE SLABS ON GRADE CONTAINING 6X6/ | | W1.4XW1.4 WELDED WIRE REINFORCEMENT | | FABRIC LOCATED IN THE MIDDLE TO THE | | UPPER 1/3RD OF THE SLAB SHALL BE SUP- | | PORTED BY APPROVED MATERIALS OR SUPPORTS | | AT SPACING NOT TO EXCEED 3 FT OR IN | | ACCORDANCE WITH MANUFACTURER'S SPEC. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-04-29 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-04-29 |
Time |
12:30 |
Rev Time |
2.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-29 00:00:00 | ******BUILDING PROVISO******* | | 1)- FL BLDG 1909.3 (EXEPTION# 2) | | CONCRETE SLABS ON GRADE CONTAINING 6X6/ | | W1.4XW1.4 WELDED WIRE REINFORCEMENT | | FABRIC LOCATED IN THE MIDDLE TO THE | | UPPER 1/3RD OF THE SLAB SHALL BE SUP- | | PORTED BY APPROVED MATERIALS OR SUPPORTS | | AT SPACING NOT TO EXCEED 3 FT OR IN | | ACCORDANCE WITH MANUFACTURER'S SPEC. | | ANY QUESTIONS PLEASE CALL, | | JIM WITMER | | BUILDING PLAN REVIEW | | DEPARTMENT OF CONSTRUCTION SERVICES | | CITY OF WEST PALM BEACH | | (561) 659-8096 EXT. 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-04-10 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-04-10 |
Time |
16:25 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-10 00:00:00 | BUILDING PLAN REVIEW | | PERMIT# 02030131 | | 9573 LANTERN BAY CI | | CONT: ENGLE HOMES | | TEL: 968-5671 | | | | FL BLDG CODE= 2001 FLORIDA BUILDING CODE | | | | | | SEE COMMENTS UNDER PREMIT # 02030113 | | SAME MODEL. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-08-12 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-08-12 |
Time |
17:10 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-08-12 |
Time |
16:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-03-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-22 |
Time |
06:47 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-22 |
Time |
06:47 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-06-20 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-06-20 |
Time |
08:39 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2002-06-20 |
Time |
08:00 |
Sent To |
|
|
Notes |
2002-06-20 00:00:00 | REVISION MECHANICAL PERMIT 02030143 | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | SMOKE DETECTORS SHALL BE INSTALLED | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | AIR DUCT. 2001 FBC(M) 606.2.1OR | | UPON ACTIVATION, THE SMOKE DETECTORS | | SHALL SHUTDOWN THE AIR DISTRIBUTION | | SYSTEM. 2001 FBC(M) 606.4 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-03-21 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-03-21 |
Time |
19:03 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2002-03-21 |
Time |
19:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-07-15 00:00:00 | REVISION OK - SANT. RISER DIAGRAM. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2002-03-09 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-03-09 |
Time |
11:12 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2002-03-09 |
Time |
11:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
N |
Date |
2002-04-10 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-04-10 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-03-04 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2002-03-04 |
Time |
15:15 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|