Plan Review Details - Permit 02030087
Plan Review Stops For Permit 02030087
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-08 Cont ID  
Sent By pkrauss Date 2002-03-19 Time 16:11 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-08 Cont ID  
Sent By btrobaug Date 2002-03-08 Time 12:54 Rev Time 0.00
Received By btrobaug Date 2002-03-08 Time 14:23 Sent To M
Notes
2002-03-08 00:00:00NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-19 Cont ID  
Sent By btrobaug Date 2002-03-08 Time 12:54 Rev Time 0.35
Received By pkrauss Date 2002-03-19 Time 16:00 Sent To B
Notes
2002-03-19 00:00:00 
 PROVISO:MECHANICAL PERMIT 02030101
  
 A ROOM, ATTIC, VOID, HOLLOW OR CONCEALED
 SPACE SHALL NOT BE USED AS AN INTEGRAL
 PART OF A DUCT SYSTEM OR PLENUM.1997
 SMC 609.1.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop Z ZONING
Rev No 1 Status N Date 2002-03-01 Cont ID  
Sent By lsmith Date 2002-03-01 Time 09:13 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***