|
 |
 |
 |
 |
 |
Plan Review Details - Permit 02022274
Plan Review Stops For Permit 02022274 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-03-29 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-03-29 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-03-29 00:00:00 | PROVIDE DETAILS FOR HANDICAP | | ACCESSIBILITY TO THE SITE AND TO THE | | PRIMARY USE AREAS OF THE STRUCTURE.THE | | RAMP SHOWN DOES NOT APPEAR TO COMPLY | | WITH SECTION 4.8 OF THE FACBC INCLUDING | | LOCATION.SEE FACBC 4.1.6 (I) RE: | | RESIDENTIAL CONVERSION. | | | | SHOW THE DIMENSIONS OF ITEMS SUCH AS | | THEDOORS BEING REPLACED, STAIR WIDTH, | | RISE RUN RATIO, AND OTHER PERTINENT | | ITEMS. | | | | THERE APPEARS TO BE TYPOS IN SECTION | | 1/A2.0 AT THE HANDRAILS. | | | | THE EGRESS DOORS FROM THE BUILDING MUST | | HAVE LEVEL LANDINGS.SEE SBC 1012.1.3. | | | | SHOW THE SPECIFIC FIRE RATING FOR THE | | DOORS ENCLOSING THE STAIRS.SEE SBC | | TABLE 705.1.2. | | | | THE CONVERSION FROM RESIDENTIAL TO | | BUSINESS MAY BE SUBJECT TO IMPACT FEES | | COLLECTED BY THE COUNTY FOR THE CITY. | | THE PERMIT PLANS MUST BE STAMPED BY | | THAT OFFICEAND A COPY OF THE PAID | | RECEIPT ATTACHED TO THE PERMIT | | APPLICATION.CALL 233-5025 FOR MORE | | INFORMATION. | | | | PROVIDE DETAILED PLANS OR A DESCRIPTIVE | | WRITTEN NARRATIVE OF THE CONCRETE WORK | | TO BE INCLUDED WITH THE PERMIT | | APPLICATION.SEE SBC 104.2 | | | | THE DECLARED $2400 PERMIT VALUATION IS | | TOO LOW FOR THIS SCOPE OF WORK. | | PROVIDE A COPY OF THE SIGNED CONTRACT | | AND A DETAILED TAKEOFF INCLUDING | | EXTENSIONS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-03-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-27 |
Time |
05:41 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-27 |
Time |
05:41 |
Sent To |
|
|
Notes |
2002-03-27 00:00:00 | *************** UNSAT ****************** | | | | 1)NOTE: PLEASE SUBMIT INFORMATION FOR | | EXISTING SERVICE AND SIZE. PLEASE SUBMIT | | A LOAD CALCAULTION FOR USE AS COMMERCIAL | | OFFICE. 215-5/220-3/220-10/220-11/-13,, | | | | 2)NOTE: PLEASE SHOW ALL NEW CIRCUITING | | ON PLANS AND CORRELATE WITH SUBMITTED | | PANEL SCHEDULE. | | | | 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | LOADS ARE TO SHOWN AND FIGURED AT 125% | | 215-2,3. 230-42 ETC. | | | | 4)NOTE: PLEASE SHOW ALL EXISTING ELECTR- | | ICAL. NEED TO VERIFY LIGHTING. | | PLEASE SHOW LOCATION OF ELECTRICAL | | SERVICE/PANEL. | | | | 5)NOTE: PLEASE NOTE POSSIBLE MISSING | | EMLT AND EXIT LTS. PLEASE SEE FIRE | | REVIEW COMMENTS. | | | | 6)NOTE: PLEASE NOTE THAT PERMIT | | APPLICATION HAS A LISTED VALUE OF $2400, | | PLEASE NOTE THAT VALUE IS TO INCLUDE | | ALL LABOR AND MATERIALS. | | PLEASE NOTE VALUE WILL NEED TO BE | | ADJUSTED.ADMINISTRATIVE CODE 104.6.5. | | | | PLEASE SEE OTHER COMMENTYS FROM OTHER | | REVIEWERS. PLEASE SUBMIT THE ABOVE | | INFORMATION FOR REVIEW. IF THERE ARE | | ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-03-28 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-03-28 |
Time |
08:54 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-03-28 |
Time |
08:54 |
Sent To |
|
|
Notes |
2002-03-28 00:00:00 | A) STORAGE AREAS TO BE AT LEAST ONE HOUR | | FIRE RATED AND BE EQUIPPED WITH AT | | LEAST 45 MINUTE FIRE DOORS AND BE | | EQUIPPED WITH SELF-CLOSING DEVICES SINCE | | NO FIRE SPRINKLER SYSTEM IS PLANNED. | | B) SINGLE EXIT FROM SECOND FLOOR AS | | SHOWN CANNOT BE APPROVED. PLEASE SEE | | NFPA 101, 2000 EDITION, SECTION 38.2.4.2 | | C) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | D) PLEASE PROVIDE DETAILS ON EXISTING | | STAIR. PLEASE INDICATE RISE, RUN, | | AND TREAD DEPTH. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2002-04-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-04-01 |
Time |
09:25 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-01 00:00:00 | | | NO MECHANICAL PLANS SUBMITTED FOR | | REVIEW.PLEASE PROVIDE PLANS & OUTSIDE | | AIR CALCULATIONS AS PER ASHRAE 62-89 | | WITH MECHANICAL PERMIT APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-04-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-01 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-01 |
Time |
08:22 |
Sent To |
|
|
Notes |
2002-04-01 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) SHT 2.0 MINIMUM FACILITIES, PER TABLE | | 407 1 W/C - 1 LAV MALE, 2 W/C'S - 2 LAVS | | AND 1 DRINKING FOUNTAIN REQUIRED. | | 2) SHT 2.0 BATHROOM NOTES - W/C SHALL BE | | REPLACED WITH ADA APPROVED W/C. | | 3) SHT 2.0 GIVE DIMENSIONS FOR BATHROOM. | | 4) SHT 2.O SHOW CLEAR FLOOR SPACE FOR | | ALL HDCP FIXTURES. | | 5) SUBMIT DETAIL FOR LAVS - SHOW COMPLI- | | ANCE WITH SEC 4.19 AND ALL SUBSECTIONS. | | 6) SHT 2.0 W/C'S SHALL BE 1'6" TO CENTER | | OFF WALL. PLEASE SHOW ON PLANS | | 7) PROVIDE A SANITARY AND WATER RISER | | DIAGRAM. | | 8) INSPECTION FOR PLUMBING DEMO REQUIRED | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-03-21 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-03-21 |
Time |
11:41 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |