Plan Review Stops For Permit 02022248 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2002-09-19 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-10-30 |
Time |
11:33 |
Rev Time |
0.50 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-09-19 00:00:00 | SUPPLEMENTA DRAWING A2.3 DATED 9/9/02 | | APPROVEDBY HHP & BSTAPLES. PROCESSED P | | ER BSTAPLES 9/19/02 LS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2002-09-03 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-07-30 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-09-03 |
Time |
11:26 |
Sent To |
|
|
Notes |
2002-07-30 00:00:00 | PISKURA DID NOT REVIEW THIS PLAN, STAPLE | | S AND WITMER DID.THIS SOFTWARE ADDED M | | Y NAME AFTER VIEWING THEIR NOTES. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2002-05-14 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2002-05-14 |
Time |
14:19 |
Rev Time |
5.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-05-14 00:00:00 | PROVISO 5/14/02 | | 1. PLANS ARE TO BE SUBMITTED TO THE | | HEALTH DEPARTMENT FOR APPROVAL OF THE | | KITCHEN. NO WORK SHALL BE PERFORMED IN | | THE AREA OF THE KITCHEN UNTILL THE | | APPROVED PLANS HAVE BEEN SUBMITTED TO | | THE CITY. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-05-14 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2002-05-14 |
Time |
14:17 |
Rev Time |
5.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-05-03 00:00:00 | REVIEW NOTES STRUCTURAL 5/03/02 WILLIAM | | STAPLES 561-659-8096 EXT. 8315. | | | | 1. STRUCTURAL INSPECTION PLAN IS A | | FAX.NOT COMPLETELY FILLED OUT AND NOT | | SIGNED AND SEALED. | | | | 2. SPECIAL INSPECTOR FORMS SUBMITTED IS | | A FAX. AND NOT SIGNED AN SEALED AS | | REQUIRED BY FS 553. | | 3. SHEET S1.0 REVISE STRUCTURAL NOTE TO | | REQUIRE TERMITE PROTECTION OF SOIL. | | 4.SHEET S-3.1 DETAILS A&B PROVIDE STRUC | | TURAL CONNECTION DETAIL FOR TRUSS TO | | BEAMS. | | 5. SHEET S-4.0 | | SECTION A PROVIDE FLASHING DETAIL FOR | | ROOF TO WALL CONNECTION. | | SECTION B PROVIDE FLASHING DETAIL FOR | | METAL DECK AND TRUSS TO BEAM CONNECTION. | | | | SECTION C PROVIDE DETAIL FOR WOOD ROOF | | SHEATING CONNECTION AND FLASHING TO | | BLOCK WALL. PROVIDE FLASHING DETAIL FOR | | STEEL DECK TO BLOCK WALL AT BOTH ENDS. | | PROVIDE CONNECTION DETAIL FOR STEEL | | TRUSSES TO BEAMS. | | 6. SHEET S-5.0 | | SECTION D INDICATE CONNECTION DETAIL FOR | | ROOF SHEATING TO THE WALL FOR WOOD AND | | STEEL DECKING, PROVIDE FLASHING DETAILS. | | SECTIONS E, F AND G INDICATE THE | | CONNECTOR TO BE USED FOR TRUSS TO BEAM | | CONNECTION. | | 7. PROVIDE THE FOLLOWING: | | A. DESIGN LOADS FOR ALL WOOD AND STEEL | | TRUSSES. | | B. DESIGN PRESSURES FOR ALL OPENINGS, | | DOOORS AND WINDOWS, PROVIDE ELEVATIONS | | INDICATING DESIGN PRESSURES. | | C. PROVIDE STRUCTURAL INFORMATION ON | | LADDERS TO THREE MEZZANINE'S. | | D. SUBMIT STRUCTURAL CALCULATIONS. | | E. PROVIDE STRUCTURAL DESIGN FOR METAL | | AND BUILT UP ROOF SYSTEMS. | | 8. SEE REVIEW #1 FOR ADDITIONAL ITEMS | | NEEDING CLARIFICATION, FOR ITEMS NOT | | DUPLICATED TO REDUCE CONFUSION. | | 9. REVISE PLUMBING DRAWINGS IN | | COMFORMITY WITH CUT SHEET SECTION C ON | | 6.3 DATED 4/26/02. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-04-04 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-04-04 |
Time |
12:53 |
Rev Time |
4.50 |
Received By |
hpiskura |
Date |
2002-04-04 |
Time |
12:53 |
Sent To |
|
|
Notes |
2002-04-04 00:00:00 | BUILDING PLAN REVIEW | | PERMIT# 02022248 | | 345 SUMMA STREET | | CONT: WHITING - TURNER | | TEL: 832-4995 | | | | SBC= 1997 STANDARD BUILDING CODE | | SBC*= AMENDMENTS TO THE STANDARD BUILD- | | ING CODE | | FL ACC= 1997 FLORIDA ACCESSIBILITY CODE | | | | NOTE: FLORIDA STATE STATUTE 553.80 2(B) | | THE LOCAL GOVERNMENT SHALL IMPOSE, EACH | | TIME AFTER THE THIRD SUCH REVIEW THE | | PLANS ARE REJECTED FOR THE SAME CODE | | VIOLATION, A FEE OF FOUR TIMES THE | | AMOUNT OF THE PROPORTION OF THE PERMIT | | FEE ATTRIBUTED TO PLAN REVIEW. | | | | THESE PLANS ARE INCOMPLETE, NO STRUCTUR- | | AL REFRENCES, ARCHETECT HAS NOT GIVEN | | ANY INFORMATION TO FOOTING SIZE, COLUMN | | OR BEAM SIZE. | | | | THE ARCHETECT OF RECORD DOESN'T GIVE THE | | ANY INFORMATION AS TO HOW THE BUILDING | | WAS DESIGNED! IMPORTANCE FACTOR,MEAN | | ROOF HEIGTH, ETC. THESE PLAN ARE ONLY | | A CONCEPTUAL RENDERING. | | | | 1)- SBC 1804.2.7.2(3) A COMPLETE SOILS | | REPORT IS REQUIRED, 3 COPIES. | | 2)- SBC 104.2.2* A SURVEY LESS THAN A | | YEAR OLD. | | 3)- SBC 1606.2.6.2COMPONENTS & CLADDING | | THE CONTRACTOR IS TO SUPPLY THE PRODUCT | | TESTING REPORTS FOR THE FOLLOWING ITEMS: | | ALL GLAZED OPENINGS, WINDOWS, EXT. | | DOORS, SKYLIGHTS & ROOFING ASSEMBLIES | | AND STORM SHUTTERS. | | 4) TO INDICATE THE POSITIVE & NEGATIVE | | WIND ZONES ON THE ELEVATIONS FOR ALL | | OPENINGS. | | 5) MISSING TRUSS LAYOUT SHEET, INDICATE | | THE TRUSS & GIRDER LOADS, VERTICAL, HOR- | | IZONTAL & GRAVITY LOADS THAT ARE TO | | BE RESISTED. | | 6) MISSING ANCHOR SCHEDULE WITH TYPE | | OF ANCHOR, ALLOWABLE LOADS.(TRUSSES) | | 7) SHEET A-5 SECTION 2 & 3 ONE INDICATES | | WOOD TRUSSES THE OTHER METAL TRUSSES. | | WITHOUT KNOWING HOW THE ARCHETECT | | DESIGNED THIS BUILDING WHICH IS RIGHT? | | TYPE IV OR TYPE V BUILDING? | | 8) SAME SECTIONS, SECTION 2 DOES NOT | | INDICATE THE TYPE OF ROOF SHEATHING ON | | WOOD TRUSSES, WHERE AS SECTION 3 INDICAT | | ES METAL TRUSSES, METAL DECKING, 3" | | INSULATION AND PLYWOOD SHEATHING, WHAT | | TYPE OF ATTACHMENT AND WHAT FREQUENCY? | | 9) SHEET A-5 INDICATES A VENEERED EXT. | | WALL? TO COMPLY WITH 1403.2.6. FOR | | ANCHORING. | | 10) THE PLANS AARE NOT THOROUGH ENOUGH | | TO COMPLETE A REVIEW OF THE BUILDING, | | ALTHOUGH A FOUNDATION PERMIT IS APPLIED | | FOR THE STRUCTURAL PLANS SHALL ALSO | | ACCOMPANY THE ARCHETECTURAL PLANS FOR | | DISCREPANCIES, AND VARIFICATION AS TO | | THE ARCH. & ENGINEER HAVE THE SAME | | CONCEPT FOR THIS PROJECT. | | 11) SHEET A-5 DETAIL 3 INDICATES A | | PLASTER SOFFIT AND CEILING ON AN UNDIS- | | CLOSED FRAMING MEMBER? DETAILS, STEEL | | STUDS, EXPANDED WIRE LATH OR ROCK LATH | | HOW IS THE STRUCTURE SUPPORTED? | | THE SAME DETAIL INDICATES A RAISED STUC- | | CO BAND, IS THIS A SOLID STUCCO BAND? | | INDICATE ATTACHMENT HI RIB / HORIZ FRAM? | | 12) FL ACC CODE 4.33.3 BLEACHERS EXCEP- | | TION ALLOWS FOR BLEACHER SEATING <300 TO | | HAVE ACCESSIBLE VIEWING AREAS MAY BE | | CLUSTERED, EQUIVALENT ACCESSIBLE VIEWING | | POSITIONS MAY BE ON LEVELS HAVING | | ACCESSIBLE EGRESS. SHOW COMPLIANCE. | | 13 THE SAME COMMENTS AS THE FOUNDATION | | PERMIT.WHAT CODE DESIGNED BY? | | 14) THRESHOLD BUILDING, THRESHOLD INSP | | REQUIRED, ENGINEER TO COMPRISE THRESHOLD | | INSPECTION PLAN! | | 15) MEET WITH DON NEELY ASSISTANT | | BUILDING OFFICIAL. | | 16) 3 SETS OF PLANS | | 17) PLANS TO COUNTY IMPACT FEES | | 18) RADON FEES DUE UNDER FOUNDATION | | BUILDING PLAN REVIEW | | JIM WITMER | | (561)659-8096X8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2002-08-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2002-08-28 |
Time |
09:26 |
Rev Time |
4.00 |
Received By |
jleahy |
Date |
2002-08-28 |
Time |
09:25 |
Sent To |
|
|
Notes |
2002-08-28 00:00:00 | RISER SHOWS #1 IN A PARALLEL RUN MUST BE | | 1/0 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2002-08-13 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-08-13 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-08-13 |
Time |
08:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
N |
Date |
2002-08-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-08-06 |
Time |
06:57 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-08-06 |
Time |
06:34 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-05-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-05-02 |
Time |
10:43 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-05-02 |
Time |
10:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-03-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-20 |
Time |
12:54 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-20 |
Time |
07:49 |
Sent To |
|
|
Notes |
2002-03-20 00:00:00 | ************** UNSAT ****************** | | | | 1)NOTE: PLEASE NOTE THAT THE ELECTRICAL | | SECTION IN THE SPEC BOOKS REFERENCE ALL | | THE OLD CODES. BLDG/FIRE/ELEC/ACCESS,ECT | | PLEASE CHECK FOR ALL CURRENT CODES THAT | | ARE IN AFFECT AT TIME OF APPLICATION. | | PLEASE NOTE; WE ARE UNDER "99" NEC, | | "96" NFPA-72. AND LOCAL AMENDMENTS. | | | | 2)NOTE: PLEASE NOTE THAT PER ART 215 | | OF CITY-WIDE ELECTRICAL AMENDMENTS. | | COLOR CODING OF 277V/480V STANDS AT | | BROWN/PURPLE/ YELLOW. PLEASE CORRECT. | | | | 3)NOTE: PLEASE NOTE THAT NOTE #1 ON E-3 | | SAYS MAIN RATED AT 65AIC. PLEASE NOTE | | THAT E-4 MDP IS SHOWN AT 22,000 AIC? | | PLEASE CORRELATE. 110-9/215-5 | | PLEASE ALSO NOTE E-3 SHOWS 10,000 AIC | | FOR BRANCH BRKLRS. | | | | 4)NOTE: PLEASE NOTE THAT NOTE 12 ON E-3 | | SAYS "EQUIPMENT GROUND" PLEASE CLARIFY | | AS "GROUNDING ELECTRODE". | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | 'REVIEW. PLEASE MAKE CORRECTIONS AS | | NOTED. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2002-03-07 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-03-07 |
Time |
09:56 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2002-03-07 |
Time |
09:55 |
Sent To |
|
|
Notes |
2002-03-07 00:00:00 | N/A | | 1. SEE PERMIT # 02020236 FOR UNDERGROUND | | UTILITIES/SITE WORKS. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2002-09-05 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-09-05 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-09-05 |
Time |
09:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2002-05-14 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-05-14 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-05-14 |
Time |
14:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2002-05-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-05-02 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-05-02 |
Time |
16:35 |
Sent To |
|
|
Notes |
2002-05-02 00:00:00 | NEED OLD SETS OF PLANS TO COMPARE WITH | | NEW ONES. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-03-26 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-03-26 |
Time |
08:20 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-03-26 |
Time |
08:20 |
Sent To |
|
|
Notes |
2002-03-26 00:00:00 | A) SEPARATE PLANS AND PERMITS REQUIRED | | FOR FIRE ALARM SYSTEM. THE FIRE ALARM | | SYSTEM TO BE CLASS A OR FULLY | | ADDRESSABLE. CUT SHEETS, WIRING DIAGRAM | | AND BATTERY CALCULATIONS REQUIRED. | | B) SEPARATE PLANS AND PERMITS REQUIRED | | FOR ANY HOOD,DUCT, AND FIRE SUPPRESSION | | SYSTEMS PLANNED FOR USE. | | C) PLEASE PROVIDE MORE DETAILS ON | | PROPOSED KILN. | | D) OCCUPANT LOAD TO BE DETERMINED BY | | FIRE RESCUE. | | E) PANIC HARDWARE REQUIRED ON ALL EXIT | | DOORS SUBJECT TO AN OCCUPANCY LOAD OF | | 100 OR MORE PERSONS. | | F) PLEASE INDENTIFY MAIN INGRESS AND | | EGRESS FOR THE BUILDING THAT IS CAPABLE | | OF PROVIDING EXITING FOR AT LEAST 50 % | | OF THE OCCUPANT LOAD FOR THE BUILDING. | | G) ANY COVERED WALKWAYS, IF COMBUSTIBLE | | OVER FOUR FEET WIDE ARE TO BE FIRE | | SPRINKLER PROTECTEDC. | | H) NO FIRE DEPARTMENT CONNECTION SHOWN | | ON FIRE SPRINKLER DRAWINGS. THIS | | CONNECTION MUST BE NO MORE THAN 150 FEET | | FROM A FIRE HYDRANT. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2002-10-30 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-10-30 |
Time |
11:33 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-10-29 |
Time |
11:33 |
Sent To |
B |
|
Notes |
2002-10-30 00:00:00 | TO HAROLD P./WRT. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2003-04-14 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2003-04-14 |
Time |
07:53 |
Rev Time |
0.50 |
Received By |
hmoser |
Date |
2003-04-14 |
Time |
07:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2002-09-18 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-09-18 |
Time |
16:53 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2002-09-18 |
Time |
16:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2002-08-22 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-08-22 |
Time |
14:01 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2002-08-22 |
Time |
12:56 |
Sent To |
|
|
Notes |
2002-08-22 00:00:00 | REVSIONS ARE APPROVED - ONLY 1 SET OF | | PLANS SUBMITTED FOR MECHANICAL & | | PLUMBING. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-05-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-08-06 |
Time |
06:57 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-05-02 |
Time |
12:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-03-28 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-03-28 |
Time |
10:17 |
Rev Time |
1.00 |
Received By |
pkrauss |
Date |
2002-03-28 |
Time |
09:52 |
Sent To |
|
|
Notes |
2002-03-28 00:00:00 | *******************DENIED*************** | | | | PLAN REVIEW UNDER 1997 SMC | | | | 1.FIRE DAMPERS REQUIRED AT WHERE DUCTS | | PENETRATE A WALL WITH A RATING 1 HR | | OR GREATER.INDICATE LOCATIONS OF | | ALL FIRE DAMPERS ON PLAN AS PER 1997 | | SMC 610.6. | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS AS | | PER AHSRAE 62-1989. | | | | 3.INDICATE WHERE EMERGENCY DRAIN LINE | | WILL TERMINATE - AS PER 1997 SMC | | 304.8.6.1, DRAIN LINE NOTE LESS THAN | | 3/4" PIPE SIZE SHALL EXTEND FROM PAN | | AND TERMINATE AT A CONSPICUOUS POINT | | TO SERVE AS AN ALARM THAT PRIMARY | | DRAIN IS RESTRICTED. | | | | 4.PROVIDE DETAIL FOR THE ATTACHMENT | | OF THE CONDENSER UNIT STAND TO THE | | ROOF.PLEASE NOTE AS PER COUNTWIDE | | AMENDMENTS, 18" MINIMUM BETWEEN THE | | ROOF SURFACE AND THE BOTTOM OF THE | | SUPPORT RAIL. | | | | 5.PROVIDE MANUFACTURER SUBMITTAL DATA | | FOR THE KILN. | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | FIRE SUPRESSION AND WALK-IN COOLERS OR | | FREEZERS.PROVIDE MANUFACTURER | | SUBMITTAL DATA & PLANS WITH PERMIT | | APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
10 |
Status |
P |
Date |
2002-11-09 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-11-09 |
Time |
06:44 |
Rev Time |
0.25 |
Received By |
kstevens |
Date |
2002-11-09 |
Time |
06:44 |
Sent To |
|
|
Notes |
2002-11-09 00:00:00 | SUMBITTALS FOR IRRIGATION SYSTEM |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
9 |
Status |
P |
Date |
2002-08-31 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-08-31 |
Time |
07:47 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-08-31 |
Time |
07:47 |
Sent To |
|
|
Notes |
2002-08-31 00:00:00 | SPECIFICATIONS OK - WATER - SANT - | | GUTTERS/DOWNSPOUTS - TOILET ACCESSORIES |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
8 |
Status |
F |
Date |
2002-08-31 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-08-31 |
Time |
07:03 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-08-31 |
Time |
07:03 |
Sent To |
|
|
Notes |
2002-08-31 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 - SGC-97 | | | | 1) SHT A2.0 TOILET ROOM NEAR OFFICE AND | | DANCE ROOM DOES NOT MEET CODE PER SEC | | 4.22 | | 2) SHT P-1 RELIEF VENTS REQUIRED ON ALL | | CONDENSATE LINES AS THEY EXIT BLDG. | | 3) SHT P-1 BACKFLOW PREVENTOR REQUIRED | | ON WATER SERVICE LINE TO WET PLAY AREA. | | 4) SHT P-3 DISHWASHER SHALL DRAIN INTO | | THE SANITARY DRAIN NOT GREASE SYSTEM PER | | UTILITY ORD. | | 5) GAS PERMIT REQUIRED. FOLLOWING INFOR- | | MATION REQUIRED AT TIME OF GAS PERMIT | | APPLICATION. | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER STANDARD | | GAS CODE. | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. | | 3. TYPE OF GAS, (LP OR NATURAL) | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER THE STANDARD GAS | | CODE SECS. 402.4 THRU 402.4.4.7. | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | PER STANDARD GAS CODE SEC. 305.2. IF | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | 8. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER THE STANDARD GAS CODE SECS | | 602 THRU 612. | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | STANDARD GAS CODE SEC. 402. | | 10. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | 11. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND | | APPURTENANCES PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | 6) SHT P-3 GAS RISER - UNION REQUIRED | | BETWEEN THE MANUAL SHUT OFF VALVE AND | | THE AUTOMATIC SHUT OFF VALVE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
7 |
Status |
F |
Date |
2002-08-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-08-28 |
Time |
17:51 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-08-28 |
Time |
17:51 |
Sent To |
|
|
Notes |
2002-08-28 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | FBC-2001 PLUMBING | | | | 1) AFTER HAVING READ YOUR LETTER DATED | | 09 AUGUST 2002, SUBMITTED 23 AUGUST 2002 | | I MUST DISAGREE WITH YOUR INTENTION THAT | | THE TOILET ROOM BE CONSIDERED A "PRIVATE | | TOILET". IT WAS THE INTENTION OF THE | | CONSTRUCTION SERVICES DEPT. THAT THE | | TOILET ROOM IN QUESTION SHALL BE A UNI- | | SEX ACCESSIBLE TOILET ROOM PROVIDING | | MINIMUM FACILITIES AS REQUIRED BY CODE. | | FURTHERMORE TO BE A PRIVATE TOILET ROOM | | IT WOULD HAVE TO BE A TOILET ROOM FOR | | ONE INDIVIDUAL OFFICE. OFFICE STAFF | | TOILETS SHALL BE ACCESSIBLE. | | | | PLEASE SUBMIT A REVISION SHOWING ALL | | DETAILS FOR THIS TOILET ROOM PER SECT. | | 11-4.22 AND ALL SUBSECTIONS. | | | | IF YOU HAVE ANY QUESTIONS | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
P |
Date |
2002-08-16 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-08-16 |
Time |
08:13 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-08-16 |
Time |
08:13 |
Sent To |
|
|
Notes |
2002-08-16 00:00:00 | SUBMITTAL OK - W.C. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
F |
Date |
2002-08-05 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-08-05 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-08-05 |
Time |
13:56 |
Sent To |
|
|
Notes |
2002-08-05 00:00:00 | DENIED | | | | SHEET SD-1 NOT APPROVED. TOILET ROOM NOT | | ACCESSIBLE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2002-05-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-14 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-14 |
Time |
14:26 |
Sent To |
|
|
Notes |
2002-05-14 00:00:00 | OK PER NEIL MELICK |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2002-05-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-03 |
Time |
10:46 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-03 |
Time |
10:46 |
Sent To |
|
|
Notes |
2002-05-03 00:00:00 | DENIED | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | 1) PLANS TO BE ROUTED TO HEALTH DEPT. | | 2) SHT A2.0 SHOWER BATH BY DANCE CLASS | | SHALL BE ACCESSIBLE. | | 3) SHT FS-1.1 EQUIP SCHED. #29 NO SANT. | | 0R WATER SHOWN FOR THIS EQUIP. | | 4) COMPLETE PLANS REQUIRED FOR FURTHER | | REVIEW. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-05-02 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-02 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-02 |
Time |
13:20 |
Sent To |
|
|
Notes |
2002-05-02 00:00:00 | DENIED | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | 1) PLANS SHALL BE ROUTED TO THE PALM | | BEACH COUNTY HEALTH UNIT, DIVISION OF | | ENVIRONMENTAL HEALTH, 901 EVERNIA STREET | | WPB FLA 33401. 3RD NOTICE | | 2) SHT P-2, SANT RISER DIAG., JANITOR | | MOP SINK SHALL BE ON GREASE LINE, BUT | | THE MEZZININE FLOOR DRAIN SHALL BE ON | | THE SANITARY SYSTEM. | | 3) SHT A2.0 SHOWER BATH BY DANCE CLASS | | SHALL BE ACCESSIBLE PER FACBC SEC 4.1.3 | | (11). PLEASE SHOW 5' TURNING RADIUS, | | CLEAR FLOOR SPACE, W/C 1'6" OFF WALL, | | HEIGHT FOR LAV., DOOR SHALL NOT OPEN IN- | | TO CLEAR FLOOR SPACE OF LAV. | | 4) SHT A2.3 SECONDARY DRAIN (SCUPPER) | | MISSING FOR ROOF ABOVE MEN'S REST ROOM. | | 5) SHT FS-1.1 EQUIP SCHED. #10 WATER | | FILTER SHALL BE NSF APPROVED. SUBMIT | | MANUFACTURE INFORMATION. (FS SHEETS NOT | | FOUND) | | 6) SHT FS-1.1 EQUIP SCHED. #29 NO SANT. | | OR WATER SHOWN FOR THIS EQUIP. | | 7) SHT FS-1.2 MECH NOTES #6 IS THERE A | | WASH DOWN FOR HOOD? | | 8) SHT P-1 GREASE TRAP, RODNEY COMPO NOT | | CONTACTED TO SIZE GREASE TRAP. CALLED | | HIM MYSELF AND HE SAID HE WOULD CONTACT | | ARCHITECT OR ENGINEER. | | 9) SHT P-2 WATER RISER, 1" COLD OUT OF | | WOMEN'S ROOM "TO PLAY AREA" BUT SHT P-1 | | SHOWS IT SUPPLING A DRINKING FOUNTAIN. | | PLEASE CLAIRFY. ALSO A SHUT OFF VALVE IS | | REQUIRED FOR THIS LINE. | | 10) ALL GAS FOR KITCHEN TO BE ON SEPAR- | | ATE PERMIT. PLANS SHALL BE SUBMITTED | | WITH PERMIT APPLICATION. | | 11) SHT L2 WATER PLAY BY VORTEX, PUMP | | VAULT (FOR WATER PLAY) & ENCLOSURE BY | | VORTEX. - SUBMIT MANUFACTURE SHEETS AND | | INFORMATION WITH LISTED APPROVAL. SHOW | | DETAILS OF SYSTEM. SUBMIT INFORMATION TO | | HEALTH DEPT. FOR APPROVAL BEFORE RESUB- | | MITTING TO CITY FOR REVIEW. 2ND NOTICE, | | THESE SHEETS NOT RESUBMITTED. | | 12) PLANS ARE NOT COMPLETE, PLEASE IN- | | CLUDE ALL SHEETS FOR REVIEW WHEN RESUB- | | MITTING. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-04-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-01 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-01 |
Time |
11:02 |
Sent To |
|
|
Notes |
2002-04-01 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 - SGC-97 | | | | 1) PLEASE ROUTE PLANS PALM BEACH COUNTY | | HEALTH UNIT DIVISION OF ENVIRONMENTAL | | HEALTH 901 EVERNIA STREET FOR PLAN RE- | | VIEW PRIOR TO RESUBMITTING. | | 2) PROVIDE CALCULATIONS FOR MINIMUM FAC- | | ILITIES PER TABLE 407 AND SEC 407.1.3 | | 3) SHT A2.3PROVIDE CALCULATIONS FOR | | PRIMARY AND SECONDARY ROOF DRAINS PER | | SEC 1108 & 1109. ADD AREAS FROM ROOFS | | DRAINING ON TO ROOFS AND 1/2 OF AREA OF | | ALL VERTICAL WALLS. | | 4) SUBMIT A STORM RISER DIAGRAM. SHOW | | ALL PIPE SIZES AND SHOW AREA DRAINED FOR | | EACH DRAIN. | | 5) SHT A2.3 ROOF ABOVE COMPUTER ROOM/ | | GAME ROOM, NO SECONDARY DRAIN SHOWN. | | 6) SHT A6.3 DETAIL #1 W/C TO BE 1'6" TO | | CENTERLINE OFF WALL - SHOW ON DETAIL | | 7) SHT A6.3 DETAIL #2 W/C TO BE 1'6" TO | | CENTERLINE OFF WALL - SHOW ON DETAIL | | 8) SHT A6.3 DETAIL #3 ROLL IN SHOWER | | SHALL COMPLY WITH FIG 57 AND SECTION | | 4.21. SHOW DETAILS FOR CONTROL HEIGHT, | | SEAT PLACEMENT (ADJACENT TO CONTROLS), | | GRAB BARS ECT. | | 9) SHT FS-1.1 EQUIP SCHED. #10 WATER | | FILTER SHALL BE NSF APPROVED. SUBMIT | | MANUFACTURE INFORMATION. | | 10 SHT FS-1.1 EQUIP SCHED. #29 NO SANT. | | OR WATER SHOWN FOR THIS EQUIP. | | 11) SHT FS-1.2 MECH NOTES #6 IS THERE A | | WASH DOWN FOR HOOD? | | 12) SHT P-1 GREASE TRAP, CONTACT RODNEY | | COMPO ENVIRONMENTAL COMPLIANCE FOR SIZE- | | ING OF GREASE TRAP. WASTE ORD #2938-96 | | (561) 837-4074. | | 13) SHTS P-1/P-2 RPZ BACKFLOW REQUIRED | | ON WATER SERVICE. | | 14) SHT P-2 WATER RISER - VALVE REQUIRED | | FOR 3/4" HOT TO 3 COMP. SINK IN KITCHEN. | | 15) SHT P-2 WATER RISER - W/C'S IN WOMEN | | ROOM FED BY HOT WATER/HOT & COLD TO | | DOUBLE COMP SINK REVERSED. | | 16) SHT P-2 WATER RISER - 1" COLD OUT OF | | WOMENS ROOM "TO PLAY AREA" BUT SHT P-1 | | SHOWS IT SUPPLYING A DRINKING FOUNTAIN. | | PLEASE CLAIRFY. ALSO A SHUT OFF VALVE IS | | REQUIRED FOR THIS LINE. | | 17) SHT P-2 WATER RISER - 1" COLD WATER | | TO PLAY AREA REQUIRES A SHUT OFF VALVE, | | AND A BACKFLOW PREVENTER. | | 18) SHT P-2 GAS RISER, THE FOLLOWING IN- | | FORMATION IS REQUIRED FOR GAS PERMIT | | APPROVAL. SEPARATE GAS PERMIT REQUIRED. | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER STANDARD | | GAS CODE. | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. | | C. TYPE OF GAS, (LP OR NATURAL) | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | PER STANDARD GAS CODE SEC. 305.2. IF | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | STANDARD GAS CODE SEC. 402. | | F). EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | 19) SHT P-3 WATER HEATER DETAIL SHOWS | | RELIEF LINE & PAN DRAIN DRAINING INTO A | | FLOOR DRAIN, BUT SHT P-1 & SHT P-2 FIX- | | TURE SCHED. SHOW LINES PIPED OUTSIDE- 6" | | ABOVE GRADE. PLEASE CLAIRFY. | | 20) SHT L2 WATER PLAY BY VORTEX, PUMP | | VAULT (FOR WATER PLAY) & ENCLOSURE BY | | VORTEX. - SUBMIT MANUFACTURE SHEETS AND | | INFORMATION WITH LISTED APPROVAL. SHOW | | DETAILS OF SYSTEM. SUBMIT INFORMATION TO | | HEALTH DEPT. FOR APPROVAL BEFORE RESUB- | | MITTING TO CITY FOR REVIEW. | | 21) SHT P-2 SANITARY RISER DIAGRAM, | | FLOOR DRAIN IN MENS ROOM NOT SHOWN OR | | RISER DIAGRAM. | | 22) SHT P-2 2 FLOOR DRAINS SHOWN ON SHT | | P-1 FLOOR PLAN AND ONLY 1 SHOWN ON RISER | | DIAGRAM. PLEASE CLAIRFY. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-03-06 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2002-03-06 |
Time |
11:06 |
Rev Time |
0.75 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-03-06 00:00:00 | DUMPSTER DOES NOT MEET CODE AND BUILD | | SQUARE FOOTAGE DOES NOT MATCH APPLICATIO | | CALLED MAT 832-4995 |
|
|