Plan Review Details - Permit 02022248
Plan Review Stops For Permit 02022248
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-09-19 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 11:33 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2002-09-19 00:00:00SUPPLEMENTA DRAWING A2.3 DATED 9/9/02
 APPROVEDBY HHP & BSTAPLES. PROCESSED P
 ER BSTAPLES 9/19/02 LS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-09-03 Cont ID  
Sent By hpiskura Date 2002-07-30 Time 15:00 Rev Time 0.00
Received By hpiskura Date 2002-09-03 Time 11:26 Sent To  
Notes
2002-07-30 00:00:00PISKURA DID NOT REVIEW THIS PLAN, STAPLE
 S AND WITMER DID.THIS SOFTWARE ADDED M
 Y NAME AFTER VIEWING THEIR NOTES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-05-14 Cont ID  
Sent By bstaples Date 2002-05-14 Time 14:19 Rev Time 5.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-14 00:00:00PROVISO 5/14/02
 1. PLANS ARE TO BE SUBMITTED TO THE
 HEALTH DEPARTMENT FOR APPROVAL OF THE
 KITCHEN. NO WORK SHALL BE PERFORMED IN
 THE AREA OF THE KITCHEN UNTILL THE
 APPROVED PLANS HAVE BEEN SUBMITTED TO
 THE CITY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-05-14 Cont ID  
Sent By bstaples Date 2002-05-14 Time 14:17 Rev Time 5.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-03 00:00:00REVIEW NOTES STRUCTURAL 5/03/02 WILLIAM
 STAPLES 561-659-8096 EXT. 8315.
  
 1. STRUCTURAL INSPECTION PLAN IS A
 FAX.NOT COMPLETELY FILLED OUT AND NOT
 SIGNED AND SEALED.
  
 2. SPECIAL INSPECTOR FORMS SUBMITTED IS
 A FAX. AND NOT SIGNED AN SEALED AS
 REQUIRED BY FS 553.
 3. SHEET S1.0 REVISE STRUCTURAL NOTE TO
 REQUIRE TERMITE PROTECTION OF SOIL.
 4.SHEET S-3.1 DETAILS A&B PROVIDE STRUC
 TURAL CONNECTION DETAIL FOR TRUSS TO
 BEAMS.
 5. SHEET S-4.0
 SECTION A PROVIDE FLASHING DETAIL FOR
 ROOF TO WALL CONNECTION.
 SECTION B PROVIDE FLASHING DETAIL FOR
 METAL DECK AND TRUSS TO BEAM CONNECTION.
  
 SECTION C PROVIDE DETAIL FOR WOOD ROOF
 SHEATING CONNECTION AND FLASHING TO
 BLOCK WALL. PROVIDE FLASHING DETAIL FOR
 STEEL DECK TO BLOCK WALL AT BOTH ENDS.
 PROVIDE CONNECTION DETAIL FOR STEEL
 TRUSSES TO BEAMS.
 6. SHEET S-5.0
 SECTION D INDICATE CONNECTION DETAIL FOR
 ROOF SHEATING TO THE WALL FOR WOOD AND
 STEEL DECKING, PROVIDE FLASHING DETAILS.
 SECTIONS E, F AND G INDICATE THE
 CONNECTOR TO BE USED FOR TRUSS TO BEAM
 CONNECTION.
 7. PROVIDE THE FOLLOWING:
 A. DESIGN LOADS FOR ALL WOOD AND STEEL
 TRUSSES.
 B. DESIGN PRESSURES FOR ALL OPENINGS,
 DOOORS AND WINDOWS, PROVIDE ELEVATIONS
 INDICATING DESIGN PRESSURES.
 C. PROVIDE STRUCTURAL INFORMATION ON
 LADDERS TO THREE MEZZANINE'S.
 D. SUBMIT STRUCTURAL CALCULATIONS.
 E. PROVIDE STRUCTURAL DESIGN FOR METAL
 AND BUILT UP ROOF SYSTEMS.
 8. SEE REVIEW #1 FOR ADDITIONAL ITEMS
 NEEDING CLARIFICATION, FOR ITEMS NOT
 DUPLICATED TO REDUCE CONFUSION.
 9. REVISE PLUMBING DRAWINGS IN
 COMFORMITY WITH CUT SHEET SECTION C ON
 6.3 DATED 4/26/02.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-04 Cont ID  
Sent By jwitmer Date 2002-04-04 Time 12:53 Rev Time 4.50
Received By hpiskura Date 2002-04-04 Time 12:53 Sent To  
Notes
2002-04-04 00:00:00BUILDING PLAN REVIEW
 PERMIT# 02022248
 345 SUMMA STREET
 CONT: WHITING - TURNER
 TEL: 832-4995
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS TO THE STANDARD BUILD-
 ING CODE
 FL ACC= 1997 FLORIDA ACCESSIBILITY CODE
  
 NOTE: FLORIDA STATE STATUTE 553.80 2(B)
 THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE
 PLANS ARE REJECTED FOR THE SAME CODE
 VIOLATION, A FEE OF FOUR TIMES THE
 AMOUNT OF THE PROPORTION OF THE PERMIT
 FEE ATTRIBUTED TO PLAN REVIEW.
  
 THESE PLANS ARE INCOMPLETE, NO STRUCTUR-
 AL REFRENCES, ARCHETECT HAS NOT GIVEN
 ANY INFORMATION TO FOOTING SIZE, COLUMN
 OR BEAM SIZE.
  
 THE ARCHETECT OF RECORD DOESN'T GIVE THE
 ANY INFORMATION AS TO HOW THE BUILDING
 WAS DESIGNED! IMPORTANCE FACTOR,MEAN
 ROOF HEIGTH, ETC. THESE PLAN ARE ONLY
 A CONCEPTUAL RENDERING.
  
 1)- SBC 1804.2.7.2(3) A COMPLETE SOILS
 REPORT IS REQUIRED, 3 COPIES.
 2)- SBC 104.2.2* A SURVEY LESS THAN A
 YEAR OLD.
 3)- SBC 1606.2.6.2COMPONENTS & CLADDING
 THE CONTRACTOR IS TO SUPPLY THE PRODUCT
 TESTING REPORTS FOR THE FOLLOWING ITEMS:
 ALL GLAZED OPENINGS, WINDOWS, EXT.
 DOORS, SKYLIGHTS & ROOFING ASSEMBLIES
 AND STORM SHUTTERS.
 4) TO INDICATE THE POSITIVE & NEGATIVE
 WIND ZONES ON THE ELEVATIONS FOR ALL
 OPENINGS.
 5) MISSING TRUSS LAYOUT SHEET, INDICATE
 THE TRUSS & GIRDER LOADS, VERTICAL, HOR-
 IZONTAL & GRAVITY LOADS THAT ARE TO
 BE RESISTED.
 6) MISSING ANCHOR SCHEDULE WITH TYPE
 OF ANCHOR, ALLOWABLE LOADS.(TRUSSES)
 7) SHEET A-5 SECTION 2 & 3 ONE INDICATES
 WOOD TRUSSES THE OTHER METAL TRUSSES.
 WITHOUT KNOWING HOW THE ARCHETECT
 DESIGNED THIS BUILDING WHICH IS RIGHT?
 TYPE IV OR TYPE V BUILDING?
 8) SAME SECTIONS, SECTION 2 DOES NOT
 INDICATE THE TYPE OF ROOF SHEATHING ON
 WOOD TRUSSES, WHERE AS SECTION 3 INDICAT
 ES METAL TRUSSES, METAL DECKING, 3"
 INSULATION AND PLYWOOD SHEATHING, WHAT
 TYPE OF ATTACHMENT AND WHAT FREQUENCY?
 9) SHEET A-5 INDICATES A VENEERED EXT.
 WALL? TO COMPLY WITH 1403.2.6. FOR
 ANCHORING.
 10) THE PLANS AARE NOT THOROUGH ENOUGH
 TO COMPLETE A REVIEW OF THE BUILDING,
 ALTHOUGH A FOUNDATION PERMIT IS APPLIED
 FOR THE STRUCTURAL PLANS SHALL ALSO
 ACCOMPANY THE ARCHETECTURAL PLANS FOR
 DISCREPANCIES, AND VARIFICATION AS TO
 THE ARCH. & ENGINEER HAVE THE SAME
 CONCEPT FOR THIS PROJECT.
 11) SHEET A-5 DETAIL 3 INDICATES A
 PLASTER SOFFIT AND CEILING ON AN UNDIS-
 CLOSED FRAMING MEMBER? DETAILS, STEEL
 STUDS, EXPANDED WIRE LATH OR ROCK LATH
 HOW IS THE STRUCTURE SUPPORTED?
 THE SAME DETAIL INDICATES A RAISED STUC-
 CO BAND, IS THIS A SOLID STUCCO BAND?
 INDICATE ATTACHMENT HI RIB / HORIZ FRAM?
 12) FL ACC CODE 4.33.3 BLEACHERS EXCEP-
 TION ALLOWS FOR BLEACHER SEATING <300 TO
 HAVE ACCESSIBLE VIEWING AREAS MAY BE
 CLUSTERED, EQUIVALENT ACCESSIBLE VIEWING
 POSITIONS MAY BE ON LEVELS HAVING
 ACCESSIBLE EGRESS. SHOW COMPLIANCE.
 13 THE SAME COMMENTS AS THE FOUNDATION
 PERMIT.WHAT CODE DESIGNED BY?
 14) THRESHOLD BUILDING, THRESHOLD INSP
 REQUIRED, ENGINEER TO COMPRISE THRESHOLD
 INSPECTION PLAN!
 15) MEET WITH DON NEELY ASSISTANT
 BUILDING OFFICIAL.
 16) 3 SETS OF PLANS
 17) PLANS TO COUNTY IMPACT FEES
 18) RADON FEES DUE UNDER FOUNDATION
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-08-28 Cont ID  
Sent By jleahy Date 2002-08-28 Time 09:26 Rev Time 4.00
Received By jleahy Date 2002-08-28 Time 09:25 Sent To  
Notes
2002-08-28 00:00:00RISER SHOWS #1 IN A PARALLEL RUN MUST BE
 1/0

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-08-13 Cont ID  
Sent By btrobaug Date 2002-08-13 Time 09:47 Rev Time 0.00
Received By btrobaug Date 2002-08-13 Time 08:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2002-08-06 Cont ID  
Sent By btrobaug Date 2002-08-06 Time 06:57 Rev Time 0.00
Received By btrobaug Date 2002-08-06 Time 06:34 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-02 Cont ID  
Sent By dpalmer Date 2002-05-02 Time 10:43 Rev Time 0.00
Received By dpalmer Date 2002-05-02 Time 10:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-20 Cont ID  
Sent By dpalmer Date 2002-03-20 Time 12:54 Rev Time 0.00
Received By dpalmer Date 2002-03-20 Time 07:49 Sent To  
Notes
2002-03-20 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT THE ELECTRICAL
 SECTION IN THE SPEC BOOKS REFERENCE ALL
 THE OLD CODES. BLDG/FIRE/ELEC/ACCESS,ECT
 PLEASE CHECK FOR ALL CURRENT CODES THAT
 ARE IN AFFECT AT TIME OF APPLICATION.
 PLEASE NOTE; WE ARE UNDER "99" NEC,
 "96" NFPA-72. AND LOCAL AMENDMENTS.
  
 2)NOTE: PLEASE NOTE THAT PER ART 215
 OF CITY-WIDE ELECTRICAL AMENDMENTS.
 COLOR CODING OF 277V/480V STANDS AT
 BROWN/PURPLE/ YELLOW. PLEASE CORRECT.
  
 3)NOTE: PLEASE NOTE THAT NOTE #1 ON E-3
 SAYS MAIN RATED AT 65AIC. PLEASE NOTE
 THAT E-4 MDP IS SHOWN AT 22,000 AIC?
 PLEASE CORRELATE. 110-9/215-5
 PLEASE ALSO NOTE E-3 SHOWS 10,000 AIC
 FOR BRANCH BRKLRS.
  
 4)NOTE: PLEASE NOTE THAT NOTE 12 ON E-3
 SAYS "EQUIPMENT GROUND" PLEASE CLARIFY
 AS "GROUNDING ELECTRODE".
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 'REVIEW. PLEASE MAKE CORRECTIONS AS
 NOTED. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-03-07 Cont ID  
Sent By mamini Date 2002-03-07 Time 09:56 Rev Time 1.00
Received By mamini Date 2002-03-07 Time 09:55 Sent To  
Notes
2002-03-07 00:00:00N/A
 1. SEE PERMIT # 02020236 FOR UNDERGROUND
 UTILITIES/SITE WORKS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-09-05 Cont ID  
Sent By mcarsill Date 2002-09-05 Time 09:43 Rev Time 0.00
Received By mcarsill Date 2002-09-05 Time 09:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-05-14 Cont ID  
Sent By mcarsill Date 2002-05-14 Time 14:59 Rev Time 0.00
Received By mcarsill Date 2002-05-14 Time 14:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-05-02 Cont ID  
Sent By mcarsill Date 2002-05-02 Time 16:35 Rev Time 0.00
Received By mcarsill Date 2002-05-02 Time 16:35 Sent To  
Notes
2002-05-02 00:00:00NEED OLD SETS OF PLANS TO COMPARE WITH
 NEW ONES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-03-26 Cont ID  
Sent By mcarsill Date 2002-03-26 Time 08:20 Rev Time 0.00
Received By mcarsill Date 2002-03-26 Time 08:20 Sent To  
Notes
2002-03-26 00:00:00A) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM. THE FIRE ALARM
 SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE. CUT SHEETS, WIRING DIAGRAM
 AND BATTERY CALCULATIONS REQUIRED.
 B) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY HOOD,DUCT, AND FIRE SUPPRESSION
 SYSTEMS PLANNED FOR USE.
 C) PLEASE PROVIDE MORE DETAILS ON
 PROPOSED KILN.
 D) OCCUPANT LOAD TO BE DETERMINED BY
 FIRE RESCUE.
 E) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS SUBJECT TO AN OCCUPANCY LOAD OF
 100 OR MORE PERSONS.
 F) PLEASE INDENTIFY MAIN INGRESS AND
 EGRESS FOR THE BUILDING THAT IS CAPABLE
 OF PROVIDING EXITING FOR AT LEAST 50 %
 OF THE OCCUPANT LOAD FOR THE BUILDING.
 G) ANY COVERED WALKWAYS, IF COMBUSTIBLE
 OVER FOUR FEET WIDE ARE TO BE FIRE
 SPRINKLER PROTECTEDC.
 H) NO FIRE DEPARTMENT CONNECTION SHOWN
 ON FIRE SPRINKLER DRAWINGS. THIS
 CONNECTION MUST BE NO MORE THAN 150 FEET
 FROM A FIRE HYDRANT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-30 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 11:33 Rev Time 0.00
Received By btrobaug Date 2002-10-29 Time 11:33 Sent To B
Notes
2002-10-30 00:00:00TO HAROLD P./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-04-14 Cont ID  
Sent By hmoser Date 2003-04-14 Time 07:53 Rev Time 0.50
Received By hmoser Date 2003-04-14 Time 07:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-09-18 Cont ID  
Sent By hmoser Date 2002-09-18 Time 16:53 Rev Time 0.33
Received By hmoser Date 2002-09-18 Time 16:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-08-22 Cont ID  
Sent By pkrauss Date 2002-08-22 Time 14:01 Rev Time 0.45
Received By pkrauss Date 2002-08-22 Time 12:56 Sent To  
Notes
2002-08-22 00:00:00REVSIONS ARE APPROVED - ONLY 1 SET OF
 PLANS SUBMITTED FOR MECHANICAL &
 PLUMBING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-02 Cont ID  
Sent By btrobaug Date 2002-08-06 Time 06:57 Rev Time 0.35
Received By pkrauss Date 2002-05-02 Time 12:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-28 Cont ID  
Sent By pkrauss Date 2002-03-28 Time 10:17 Rev Time 1.00
Received By pkrauss Date 2002-03-28 Time 09:52 Sent To  
Notes
2002-03-28 00:00:00*******************DENIED***************
  
 PLAN REVIEW UNDER 1997 SMC
  
 1.FIRE DAMPERS REQUIRED AT WHERE DUCTS
 PENETRATE A WALL WITH A RATING 1 HR
 OR GREATER.INDICATE LOCATIONS OF
 ALL FIRE DAMPERS ON PLAN AS PER 1997
 SMC 610.6.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER AHSRAE 62-1989.
  
 3.INDICATE WHERE EMERGENCY DRAIN LINE
 WILL TERMINATE - AS PER 1997 SMC
 304.8.6.1, DRAIN LINE NOTE LESS THAN
 3/4" PIPE SIZE SHALL EXTEND FROM PAN
 AND TERMINATE AT A CONSPICUOUS POINT
 TO SERVE AS AN ALARM THAT PRIMARY
 DRAIN IS RESTRICTED.
  
 4.PROVIDE DETAIL FOR THE ATTACHMENT
 OF THE CONDENSER UNIT STAND TO THE
 ROOF.PLEASE NOTE AS PER COUNTWIDE
 AMENDMENTS, 18" MINIMUM BETWEEN THE
 ROOF SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL.
  
 5.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE KILN.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLERS OR
 FREEZERS.PROVIDE MANUFACTURER
 SUBMITTAL DATA & PLANS WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 10 Status P Date 2002-11-09 Cont ID  
Sent By kstevens Date 2002-11-09 Time 06:44 Rev Time 0.25
Received By kstevens Date 2002-11-09 Time 06:44 Sent To  
Notes
2002-11-09 00:00:00SUMBITTALS FOR IRRIGATION SYSTEM

Review Stop P PLUMBING
Rev No 9 Status P Date 2002-08-31 Cont ID  
Sent By kstevens Date 2002-08-31 Time 07:47 Rev Time 0.00
Received By kstevens Date 2002-08-31 Time 07:47 Sent To  
Notes
2002-08-31 00:00:00SPECIFICATIONS OK - WATER - SANT -
 GUTTERS/DOWNSPOUTS - TOILET ACCESSORIES

Review Stop P PLUMBING
Rev No 8 Status F Date 2002-08-31 Cont ID  
Sent By kstevens Date 2002-08-31 Time 07:03 Rev Time 0.00
Received By kstevens Date 2002-08-31 Time 07:03 Sent To  
Notes
2002-08-31 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 1) SHT A2.0 TOILET ROOM NEAR OFFICE AND
 DANCE ROOM DOES NOT MEET CODE PER SEC
 4.22
 2) SHT P-1 RELIEF VENTS REQUIRED ON ALL
 CONDENSATE LINES AS THEY EXIT BLDG.
 3) SHT P-1 BACKFLOW PREVENTOR REQUIRED
 ON WATER SERVICE LINE TO WET PLAY AREA.
 4) SHT P-3 DISHWASHER SHALL DRAIN INTO
 THE SANITARY DRAIN NOT GREASE SYSTEM PER
 UTILITY ORD.
 5) GAS PERMIT REQUIRED. FOLLOWING INFOR-
 MATION REQUIRED AT TIME OF GAS PERMIT
 APPLICATION.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER THE STANDARD GAS
 CODE SECS. 402.4 THRU 402.4.4.7.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER THE STANDARD GAS CODE SECS
 602 THRU 612.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 6) SHT P-3 GAS RISER - UNION REQUIRED
 BETWEEN THE MANUAL SHUT OFF VALVE AND
 THE AUTOMATIC SHUT OFF VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 7 Status F Date 2002-08-28 Cont ID  
Sent By kstevens Date 2002-08-28 Time 17:51 Rev Time 0.00
Received By kstevens Date 2002-08-28 Time 17:51 Sent To  
Notes
2002-08-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) AFTER HAVING READ YOUR LETTER DATED
 09 AUGUST 2002, SUBMITTED 23 AUGUST 2002
 I MUST DISAGREE WITH YOUR INTENTION THAT
 THE TOILET ROOM BE CONSIDERED A "PRIVATE
 TOILET". IT WAS THE INTENTION OF THE
 CONSTRUCTION SERVICES DEPT. THAT THE
 TOILET ROOM IN QUESTION SHALL BE A UNI-
 SEX ACCESSIBLE TOILET ROOM PROVIDING
 MINIMUM FACILITIES AS REQUIRED BY CODE.
 FURTHERMORE TO BE A PRIVATE TOILET ROOM
 IT WOULD HAVE TO BE A TOILET ROOM FOR
 ONE INDIVIDUAL OFFICE. OFFICE STAFF
 TOILETS SHALL BE ACCESSIBLE.
  
 PLEASE SUBMIT A REVISION SHOWING ALL
 DETAILS FOR THIS TOILET ROOM PER SECT.
 11-4.22 AND ALL SUBSECTIONS.
  
 IF YOU HAVE ANY QUESTIONS
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 6 Status P Date 2002-08-16 Cont ID  
Sent By kstevens Date 2002-08-16 Time 08:13 Rev Time 0.00
Received By kstevens Date 2002-08-16 Time 08:13 Sent To  
Notes
2002-08-16 00:00:00SUBMITTAL OK - W.C.

Review Stop P PLUMBING
Rev No 5 Status F Date 2002-08-05 Cont ID  
Sent By kstevens Date 2002-08-05 Time 13:56 Rev Time 0.00
Received By kstevens Date 2002-08-05 Time 13:56 Sent To  
Notes
2002-08-05 00:00:00DENIED
  
 SHEET SD-1 NOT APPROVED. TOILET ROOM NOT
 ACCESSIBLE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-05-14 Cont ID  
Sent By kstevens Date 2002-05-14 Time 14:26 Rev Time 0.00
Received By kstevens Date 2002-05-14 Time 14:26 Sent To  
Notes
2002-05-14 00:00:00OK PER NEIL MELICK

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-05-03 Cont ID  
Sent By kstevens Date 2002-05-03 Time 10:46 Rev Time 0.00
Received By kstevens Date 2002-05-03 Time 10:46 Sent To  
Notes
2002-05-03 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) PLANS TO BE ROUTED TO HEALTH DEPT.
 2) SHT A2.0 SHOWER BATH BY DANCE CLASS
 SHALL BE ACCESSIBLE.
 3) SHT FS-1.1 EQUIP SCHED. #29 NO SANT.
 0R WATER SHOWN FOR THIS EQUIP.
 4) COMPLETE PLANS REQUIRED FOR FURTHER
 REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-02 Cont ID  
Sent By kstevens Date 2002-05-02 Time 13:20 Rev Time 0.00
Received By kstevens Date 2002-05-02 Time 13:20 Sent To  
Notes
2002-05-02 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) PLANS SHALL BE ROUTED TO THE PALM
 BEACH COUNTY HEALTH UNIT, DIVISION OF
 ENVIRONMENTAL HEALTH, 901 EVERNIA STREET
 WPB FLA 33401. 3RD NOTICE
 2) SHT P-2, SANT RISER DIAG., JANITOR
 MOP SINK SHALL BE ON GREASE LINE, BUT
 THE MEZZININE FLOOR DRAIN SHALL BE ON
 THE SANITARY SYSTEM.
 3) SHT A2.0 SHOWER BATH BY DANCE CLASS
 SHALL BE ACCESSIBLE PER FACBC SEC 4.1.3
 (11). PLEASE SHOW 5' TURNING RADIUS,
 CLEAR FLOOR SPACE, W/C 1'6" OFF WALL,
 HEIGHT FOR LAV., DOOR SHALL NOT OPEN IN-
 TO CLEAR FLOOR SPACE OF LAV.
 4) SHT A2.3 SECONDARY DRAIN (SCUPPER)
 MISSING FOR ROOF ABOVE MEN'S REST ROOM.
 5) SHT FS-1.1 EQUIP SCHED. #10 WATER
 FILTER SHALL BE NSF APPROVED. SUBMIT
 MANUFACTURE INFORMATION. (FS SHEETS NOT
 FOUND)
 6) SHT FS-1.1 EQUIP SCHED. #29 NO SANT.
 OR WATER SHOWN FOR THIS EQUIP.
 7) SHT FS-1.2 MECH NOTES #6 IS THERE A
 WASH DOWN FOR HOOD?
 8) SHT P-1 GREASE TRAP, RODNEY COMPO NOT
 CONTACTED TO SIZE GREASE TRAP. CALLED
 HIM MYSELF AND HE SAID HE WOULD CONTACT
 ARCHITECT OR ENGINEER.
 9) SHT P-2 WATER RISER, 1" COLD OUT OF
 WOMEN'S ROOM "TO PLAY AREA" BUT SHT P-1
 SHOWS IT SUPPLING A DRINKING FOUNTAIN.
 PLEASE CLAIRFY. ALSO A SHUT OFF VALVE IS
 REQUIRED FOR THIS LINE.
 10) ALL GAS FOR KITCHEN TO BE ON SEPAR-
 ATE PERMIT. PLANS SHALL BE SUBMITTED
 WITH PERMIT APPLICATION.
 11) SHT L2 WATER PLAY BY VORTEX, PUMP
 VAULT (FOR WATER PLAY) & ENCLOSURE BY
 VORTEX. - SUBMIT MANUFACTURE SHEETS AND
 INFORMATION WITH LISTED APPROVAL. SHOW
 DETAILS OF SYSTEM. SUBMIT INFORMATION TO
 HEALTH DEPT. FOR APPROVAL BEFORE RESUB-
 MITTING TO CITY FOR REVIEW. 2ND NOTICE,
 THESE SHEETS NOT RESUBMITTED.
 12) PLANS ARE NOT COMPLETE, PLEASE IN-
 CLUDE ALL SHEETS FOR REVIEW WHEN RESUB-
 MITTING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-01 Cont ID  
Sent By kstevens Date 2002-04-01 Time 11:02 Rev Time 0.00
Received By kstevens Date 2002-04-01 Time 11:02 Sent To  
Notes
2002-04-01 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 1) PLEASE ROUTE PLANS PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH 901 EVERNIA STREET FOR PLAN RE-
 VIEW PRIOR TO RESUBMITTING.
 2) PROVIDE CALCULATIONS FOR MINIMUM FAC-
 ILITIES PER TABLE 407 AND SEC 407.1.3
 3) SHT A2.3PROVIDE CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SEC 1108 & 1109. ADD AREAS FROM ROOFS
 DRAINING ON TO ROOFS AND 1/2 OF AREA OF
 ALL VERTICAL WALLS.
 4) SUBMIT A STORM RISER DIAGRAM. SHOW
 ALL PIPE SIZES AND SHOW AREA DRAINED FOR
 EACH DRAIN.
 5) SHT A2.3 ROOF ABOVE COMPUTER ROOM/
 GAME ROOM, NO SECONDARY DRAIN SHOWN.
 6) SHT A6.3 DETAIL #1 W/C TO BE 1'6" TO
 CENTERLINE OFF WALL - SHOW ON DETAIL
 7) SHT A6.3 DETAIL #2 W/C TO BE 1'6" TO
 CENTERLINE OFF WALL - SHOW ON DETAIL
 8) SHT A6.3 DETAIL #3 ROLL IN SHOWER
 SHALL COMPLY WITH FIG 57 AND SECTION
 4.21. SHOW DETAILS FOR CONTROL HEIGHT,
 SEAT PLACEMENT (ADJACENT TO CONTROLS),
 GRAB BARS ECT.
 9) SHT FS-1.1 EQUIP SCHED. #10 WATER
 FILTER SHALL BE NSF APPROVED. SUBMIT
 MANUFACTURE INFORMATION.
 10 SHT FS-1.1 EQUIP SCHED. #29 NO SANT.
 OR WATER SHOWN FOR THIS EQUIP.
 11) SHT FS-1.2 MECH NOTES #6 IS THERE A
 WASH DOWN FOR HOOD?
 12) SHT P-1 GREASE TRAP, CONTACT RODNEY
 COMPO ENVIRONMENTAL COMPLIANCE FOR SIZE-
 ING OF GREASE TRAP. WASTE ORD #2938-96
 (561) 837-4074.
 13) SHTS P-1/P-2 RPZ BACKFLOW REQUIRED
 ON WATER SERVICE.
 14) SHT P-2 WATER RISER - VALVE REQUIRED
 FOR 3/4" HOT TO 3 COMP. SINK IN KITCHEN.
 15) SHT P-2 WATER RISER - W/C'S IN WOMEN
 ROOM FED BY HOT WATER/HOT & COLD TO
 DOUBLE COMP SINK REVERSED.
 16) SHT P-2 WATER RISER - 1" COLD OUT OF
 WOMENS ROOM "TO PLAY AREA" BUT SHT P-1
 SHOWS IT SUPPLYING A DRINKING FOUNTAIN.
 PLEASE CLAIRFY. ALSO A SHUT OFF VALVE IS
 REQUIRED FOR THIS LINE.
 17) SHT P-2 WATER RISER - 1" COLD WATER
 TO PLAY AREA REQUIRES A SHUT OFF VALVE,
 AND A BACKFLOW PREVENTER.
 18) SHT P-2 GAS RISER, THE FOLLOWING IN-
 FORMATION IS REQUIRED FOR GAS PERMIT
 APPROVAL. SEPARATE GAS PERMIT REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 F). EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 19) SHT P-3 WATER HEATER DETAIL SHOWS
 RELIEF LINE & PAN DRAIN DRAINING INTO A
 FLOOR DRAIN, BUT SHT P-1 & SHT P-2 FIX-
 TURE SCHED. SHOW LINES PIPED OUTSIDE- 6"
 ABOVE GRADE. PLEASE CLAIRFY.
 20) SHT L2 WATER PLAY BY VORTEX, PUMP
 VAULT (FOR WATER PLAY) & ENCLOSURE BY
 VORTEX. - SUBMIT MANUFACTURE SHEETS AND
 INFORMATION WITH LISTED APPROVAL. SHOW
 DETAILS OF SYSTEM. SUBMIT INFORMATION TO
 HEALTH DEPT. FOR APPROVAL BEFORE RESUB-
 MITTING TO CITY FOR REVIEW.
 21) SHT P-2 SANITARY RISER DIAGRAM,
 FLOOR DRAIN IN MENS ROOM NOT SHOWN OR
 RISER DIAGRAM.
 22) SHT P-2 2 FLOOR DRAINS SHOWN ON SHT
 P-1 FLOOR PLAN AND ONLY 1 SHOWN ON RISER
 DIAGRAM. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-06 Cont ID  
Sent By gjoyce Date 2002-03-06 Time 11:06 Rev Time 0.75
Received By gjoyce Date   Time   Sent To  
Notes
2002-03-06 00:00:00DUMPSTER DOES NOT MEET CODE AND BUILD
 SQUARE FOOTAGE DOES NOT MATCH APPLICATIO
 CALLED MAT 832-4995