Plan Review Details - Permit 02021973
Plan Review Stops For Permit 02021973
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-19 Cont ID  
Sent By jwitmer Date 2002-04-19 Time 11:42 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-26 Cont ID  
Sent By jwitmer Date 2002-03-26 Time 07:09 Rev Time 2.00
Received By jwitmer Date 2002-03-26 Time 07:09 Sent To  
Notes
2002-03-26 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02021973
 3101 WADDELL AV
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1)- THIS PROJECT REQUIURES A RESIDENT IN
 SPECTOR, 3 SETS OF PLAN REQUIRED FOR
 EVERY TOWNHOUSE ISSUED.
  
 2)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 MISSING THE NORANDEX REPORTS FOR WINDOWS
 AND DOORS SITE SPECIFIC, ADDRESS TO BE
 ON EACH SIGNED & SEALED COPY.
  
 3)-SCREEN ENCLOSURES ARE TO BE A SEPER-
 ATE PERMIT WITH ASSOCIATED FEES.
  
 4)- SHEET 12/ 15 THE 5050 SH WINDOW IN
 THE BREAKFAST AREA IS TO LARGE TABLE 600
  
 5)- SHEET 5,6 & 10 TRUSSES REVIEWED
 UNDER 02010168, FG-5 A5 INDICATES A 3
 POINT BEARING GIRDER TRUSS, TTRUSS ENG.
 INDICATES A 5 POINT BEARING, MISSING
 BEARING POINTS 13,14.
  
 6)- SG-1 TRUSS ENG POINT # 5 INDICATES
 2060 LBS. UPLIFT WHERE AS SH A5 NOTE A-3
 INDICATES 1370 OR 1890 LBS SHORT RESTRAI
 NT OR UPLIFT VALUE.
  
 7)- TRUSS ENG H-4 TRUSS ENG POINT #1
 INDICATES 3203 LBS UPLIFT, POINT 11 INDI
 CATES 3174, ARCH A-6 DETAIL 4/10 IS A
 WALL SECTION TO A FLOOR GIRDER TRUSS
 CONNECTION MISSING INFO FOR THE ROOF
 TRUSS 2ND STORY WALL CONNECTION?
  
 8)- TRUSS ENG H-5 H-8 & T-1 INDICATE A
 3" BEARING END (BUCKET) ARCH SHEET A6
 INDICATES A (WA-5) NOT IN SCHEDULE?
  
 9)- WHERE MULTIPLE STRAPS ARE TO BE USED
 IN CMU OR CONCRETE A DERATING SHALL BE
 REQUIRED WHEN USED CLOSER THAN 8".
 USP SHALL CALCULATE THE AMOUNT OF DERAT-
 ING REQUIRED.
  
 10)- SHEET A-6 DETAIL 2 INDICATES A
 STRAP TO BE WELDED TO A MANUFACTURED
 BUCKET. SHALL REQUIRE THE MANUFACTURES
 APPROVAL & FIELD WELDING REQUIRES CERTI-
 FICATION OF THE WELDER.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-19 Cont ID  
Sent By btrobaug Date 2002-03-19 Time 17:27 Rev Time 0.00
Received By btrobaug Date 2002-03-19 Time 17:10 Sent To FIRE
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-03-20 Cont ID  
Sent By btrobaug Date 2002-03-19 Time 17:27 Rev Time 0.00
Received By mcarsill Date 2002-03-20 Time 10:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-16 Cont ID  
Sent By hmoser Date 2002-03-16 Time 10:32 Rev Time 0.33
Received By hmoser Date 2002-03-16 Time 10:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-09 Cont ID  
Sent By jleech Date 2002-03-09 Time 06:38 Rev Time 0.25
Received By jleech Date 2002-03-09 Time 06:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-21 Cont ID  
Sent By pkrauss Date 2002-03-21 Time 09:19 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***