Plan Review Stops For Permit 02021928 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
9 |
Status |
F |
Date |
2003-04-23 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-30 |
Time |
14:21 |
Rev Time |
1.00 |
Received By |
sthyng |
Date |
2003-04-23 |
Time |
16:06 |
Sent To |
|
|
Notes |
2003-04-23 00:00:00 | **********CORRECTIONS************ | | | | PLANS SUBMITTED FOR RESTAMP DO NOT MATCH | | PERMIT SET. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
P |
Date |
2003-03-25 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-18 |
Time |
13:52 |
Rev Time |
0.80 |
Received By |
jwitmer |
Date |
2003-03-25 |
Time |
11:43 |
Sent To |
|
|
Notes |
2003-03-25 00:00:00 | REVISION: 3/7/03 WAREHOUSE/ OFFICE | | INTERIOR WALL DELETION UNIT # 4. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2003-02-12 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-03-18 |
Time |
10:20 |
Rev Time |
0.25 |
Received By |
jwitmer |
Date |
2003-02-12 |
Time |
13:33 |
Sent To |
|
|
Notes |
2003-02-12 00:00:00 | SHOWER: ENTRY TO ROOM MEETS T-SHAPED | | ENTRY FOR 180 DEGREE TURNS.JW |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2003-02-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2003-02-12 |
Time |
13:15 |
Rev Time |
0.25 |
Received By |
jwitmer |
Date |
2003-02-12 |
Time |
13:15 |
Sent To |
|
|
Notes |
2003-02-12 00:00:00 | BUILDING PLAN REVIEW | | PERMIT:02021928 | | ADD: 5915 GEORGIA AVE | | CONT: LCI | | TEL: (561)307-4943 (JASON) | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | REVISION: DENIED | | | | 1)11-4.2.3 SHALL PROVIDE AN ACCESSIBLE | | BATHROOM/ RESTROOM PER 11-4.23.3 | | J WITMER | | BUILDING PLAN REVIEW |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2003-01-23 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2003-01-23 |
Time |
14:35 |
Rev Time |
0.75 |
Received By |
jwitmer |
Date |
2003-01-23 |
Time |
14:35 |
Sent To |
|
|
Notes |
2003-01-23 00:00:00 | REVISION DATED 12-10-02 | | | | PERMIT:02021928 | | ADDRESS: 5915 GEORGIA AVE | | CONT: LCI | | CELL: (561)307-4934DAVID | | | | REVISION: DENIED | | BUILDING REVIEW | | | | 1)11-4.13.6 MANEUVERING CLEARENCES | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | AT DOORS THAT ARE NOT AUTOMATIC OR | | POWER-ASSISTED SHALL BE AS SHOWN IN | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | IN THE REQUIRED CLEARENCES SHALL BE | | CLEAR & LEVEL. | | | | 2)11-4.22.2 DOORS. ALL DOORS TO | | ACCESSIBLE TOLIET ROOMS SHALL COMPLY | | WITH 11-4.13. DOORS SHALL NOT SWING INTO | | CLEAR FLOOR SPACE REQUIRED FOR ANY | | FIXTURE. | | | | 3) 11-4.21 SHOWER STALLS | | SIZE, CLEARENCES, SEAT, GRAB BAR | | | | 4) 11-4.26.3 STRUCTURAL STRENGH BACKING | | REQUIREMENTS | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | ON THE APPLICATION, PLANS, OR ATTACHED | | SEPARATELY. WHEN RESUBMITTING PLANS | | PLEASE CLEARLY INDICATE THE REVISION AND | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | ARY. A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A | | DESCRIPTION OF THE REVISION MADE, IDEN- | | TIFYING THE SHEET OR SPECIFICATION PAGE | | WHERE THE CHANGES CAN BE FOUND, WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | JIM WITMER | | PLAN REVIEW | | TEL: (561)659-8096 EX.8412 | | FAX: (561)659-8026 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2002-09-18 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-09-18 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-09-18 00:00:00 | ARCHITECT'S REVISION DATED 9/9/02 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2002-08-07 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-08-07 |
Time |
15:52 |
Rev Time |
1.25 |
Received By |
jwitmer |
Date |
2002-08-07 |
Time |
15:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-03-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-03-30 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2002-03-30 |
Time |
15:28 |
Sent To |
|
|
Notes |
2002-03-30 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 02021928 | | 5715 GEORGIA AV | | CONT : LCI CONT | | TEL: 659-5111 | | | | SBC= 1997 STANDARD BUILDING CODE | | | | 1) A CURRENT SURVEY NOT PART OF THE | | PERMIT PACKET | | 2) CONTRACTOR HAS NOT PROVIDED THE | | PRODUCT TESTING REPORTS FOR ALL GLAZED | | OPENINGS, EXT DOORS ROLL UP DOORS, | | ROOFING MATERIALS AS WELL AS HURRICANE | | PROTECTION FOR ALL GLAZED OPENINGS. | | 3) IMPACT FEES: CONTRACTOR TO HAVE | | PLANS SUBMITTED TO COUNTY FOR IMPACT FEE | | ASSESSMENT. | | BUILDING PLAN REVIEW | | JIM WITMER | | (561)659-8096 X 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-03-04 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-03-04 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2002-03-04 |
Time |
15:27 |
Sent To |
|
|
Notes |
2002-03-04 00:00:00 | SHOW THE FIRE DESIGN NUMBER FOR THE FIRE | | RATED TENANT SEPARATION WALLS.SEE | | SBC 701.5 | | | | PLEASE PROVIDE A RECENT PROPERTY SURVEY. | | | | SHOW THE FINISH FLOOR ELEVATIONS AND | | THAT OF THE SURROUNDING SITE SO THAT HC | | ACCESSIBILITY MAY BE DETERMINED. | | | | PROVIDE A SKETCH OF THE BUILDING | | DEPICTING THE PRESSURE ZONES FOR THE | | COMPONENTS AND CLADDING, INCLUDING THE | | ROOF COVERING.SEE SBC 1606. | | | | PROVIDE THE TEST REPORTS AND/OR THE | | NOTICE OF ACCEPTANCE FOR THE THE DOORS, | | WINDOWS AND ROOF COVERING. | | | | SHOW HOW THE GLAZED AREAS OF THE | | BUILDING EXTERIOR WILL COMPLY WITH THE | | CITY'S HURRICANE MISSILE IMPACT | | RESISTANT REQUIRMENTS. INCLUDE THE | | REQUISITE TEST REPORTS. | | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | ISSUED, IMPACT FEES MUST BE PAID TO THE | | COUNTY FOR THE CITY, THE PERMIT PLANS | | STAMPED BY THAT OFFICE, AND A COPY OF | | THE RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
F |
Date |
2003-03-18 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-03-18 |
Time |
10:20 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2003-03-18 |
Time |
10:01 |
Sent To |
B |
|
Notes |
2003-03-18 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE NOTE THAT THERE HAVE BEEN NEW | | LOADS ADDED TO THE UNITS ON PREVIOUS | | REVISIONS WITHOUT UPDATED | | CALCULATIONS.WATER HEATERS,EQUIPMENT | | CIRCUITS AND A 30 AMP "COOLER" CIRCUIT | | WERE ADDED. | | | | PLEASE REVISE CALCULATIONS SHOWING | | ACTUAL LOADS AFTER AND PRIOR TO DEMAND | | FACTORS.REVISE THE SERVICE TO SHOW SAME. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT.8392 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
P |
Date |
2003-01-02 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-03-14 |
Time |
10:09 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2003-01-02 |
Time |
12:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2002-12-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-12-27 |
Time |
11:41 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2002-12-27 |
Time |
11:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2002-09-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-09-20 |
Time |
10:44 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2002-09-20 |
Time |
10:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2002-09-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-09-16 |
Time |
07:14 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2002-09-16 |
Time |
07:14 |
Sent To |
|
|
Notes |
2002-09-16 00:00:00 | ****************** UNSAT *************** | | | | 1)NOTE: PLEASE NOTE, ORIGINAL NOTES | | REQUESTED ALL DEVICES TO HAVE CIRCUITING | | SHOWN ON PLANS AND CORRELATE W/ PANEL | | SCHEDULE SUBMITTED . (CAN BE TYPICAL). | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW. | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-04-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-04-01 |
Time |
09:44 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-04-01 |
Time |
09:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-03-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-05 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-05 |
Time |
15:52 |
Sent To |
|
|
Notes |
2002-03-05 00:00:00 | ***************** UNSAT ************* | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2)NOTE: PLEASE PROVIDE CIRCUITING ON | | PLANS AND CORRELATE WITH SUBMITTED | | PANEL SCHEDULES. | | | | 3)NOTE: PLEASE CLARIFY CIRCUIT PER | | 600-5. | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2003-01-17 |
Time |
11:59 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-01-17 00:00:00 | PER NAM 1/16/03 LS |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2002-07-24 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-07-24 |
Time |
11:15 |
Rev Time |
3.00 |
Received By |
mamini |
Date |
2002-07-24 |
Time |
11:15 |
Sent To |
|
|
Notes |
2002-07-24 00:00:00 | PASSED : | | 1. RESPONSES TO THE REVIEW COMMENTS | | DATED 3-6-02 SATISFACTORY. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2002-03-06 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-03-06 |
Time |
11:07 |
Rev Time |
2.00 |
Received By |
mamini |
Date |
2002-03-06 |
Time |
11:07 |
Sent To |
|
|
Notes |
2002-03-06 00:00:00 | FAILED : | | 1. PLEASE SHOW LOCATIONS FOR METER AND | | BACKFLOW PREVENTERS. | | 2. PLEASE SHOW THE INVERT ELEVATION FOR | | EXISTING SERVICE LATERAL AND/OR CLEAN- | | OUT FROM MAIN. | | 3. IT SHALL BE THE RESPONSIBILITY OF THE | | DEVELOPER/ENGINEER/CONTRACTOR TO DESIGN | | AND INSTALL THE NEW INVERT ELEVATION FOR | | THE BUILDING LATERAL TO MATCH OR BE | | HIGHER THAN THE EXISTING WHILE MAINTAIN- | | ING THE PLUMBING CODE REQUIREMENT FOR | | EFFLUENT PIPE FALL WITH MINIMUM OF THREE | | FEET COVER. IF THESE REQUIREMENTS CAN | | NOT BE MET, THE CITY MUST BE NOTIFIED | | PRIOR TO INSTALLATION.659-8040, 659-8079 | | 4. CIVIL PLANS MUST BE REVIEWED AND | | APPROVED BY PUBLIC UTILITIES ENGINEERING | | SERVICES 659-8040 EXT. 2306 M. GONZALEZ. | | 4. CITY'S STANDARD MAY BE OBTAINED FROM | | PUBLIC UTILITIES ENGINEERING SERVICES, | | 659-8040, EXT.2306 M. GONZALEZ | | 5. DUMPSTER ENCLOSURE MUST BE PER CITY'S | | REQUIREMENT IF GARBAGE TO BE PICKED UP | | BY THE CITY, SEE ATTACHED. | | 6. WATER QUALITY INLET IN DUMPSTER | | ENCLOSURE AREA IS NOT RECOMMENDED. | | 7. DRIVEWAY APPROACHES MUST AT MIN. BE | | PER CITY'S STANDARD, SEE ATTACHED. | | 8. CRUSHED CONCRETE FOR THE BASE | | CONSTRUCTION WOULD NOT BE ACCEPTABLE. | | 9. POLLUTION PREVENTION PLANS MUST BE | | INSTALLED IN FIELD PRIOR TO ANY EARTH | | WORKS. NOTE TO THE G.C MUST BE ADDED. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
P |
Date |
2003-01-17 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2003-01-17 |
Time |
12:00 |
Rev Time |
0.25 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-01-17 00:00:00 | PER NOM 1/16/03 LS |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
P |
Date |
2003-01-16 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2003-01-16 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2003-01-16 |
Time |
13:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2002-09-13 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-09-13 |
Time |
16:48 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-09-13 |
Time |
16:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2002-04-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-04-02 |
Time |
17:23 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-04-02 |
Time |
17:23 |
Sent To |
|
|
Notes |
2002-04-02 00:00:00 | RECEIVED LETTER FROM ROBERT BELL, | | ARCHITECT, DELETING THE SEPARATION | | WALLS BETWEEN THE OFFICE AND STORAGE | | AREAS OF EACH TENANT SPACE. LETTER | | INDICATES THAT THESE ITEMS WILL | | BE ADDRESSED LATER IN THE TENANT | | BUILD-OUTS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT. 8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2002-03-21 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-03-21 |
Time |
14:54 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-03-21 |
Time |
14:54 |
Sent To |
|
|
Notes |
2002-03-21 00:00:00 | A) THE INTERIOR WALLS THAT SEPARATE | | THE OFFICE AREAS FROM THE WAREHOUSE | | AREAS ARE TO BE AT LEAST ONE FIRE | | PROTECTED WITH AT LEAST 45 MINUTE | | FIRE DOORS. THE PLANS DO NOT REFLECT | | THIS. | | B) BUILDING ADDRESS REQUIRED ON | | BUILDING. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-03-01 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-03-01 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-03-01 |
Time |
11:03 |
Sent To |
|
|
Notes |
2002-03-01 00:00:00 | A) PLEASE BE ADVISED THAT THE PROPOSED | | BUILDING IS LOCATED WITHIN THE CITY | | FIRE LIMITS. CERTAIN RESTRICTIONS WILL | | APPLY TO THE CONSTRUCTION OF THIS | | BUILDING. PLEASE SEE APPENDIX F OF THE | | STANDARD BUILDING CODE. | | B) BUILDING ADDRESS REQUIRED ON | | BUILDING. | | C) TENANT SEPARATION WALLS SHOULD BE | | IDENTIFIED AS 5/8 TYPE X DRYWALL. | | D) THE WAREHOUSE AREAS ARE TO BE | | SEPARATED FROM THE OFFICE AREAS BY AT | | LEAST ONE HOUR FIRE RATINGS WITH | | OPENING PROTECTIVES RATED FOR THAT | | APPLICATION. IT APPEARS NO FIRE | | SPRINKLERS ARE PLANNED. | | E) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2003-05-01 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-30 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-04-30 |
Time |
14:21 |
Sent To |
P |
|
Notes |
2003-05-01 00:00:00 | PAUL SHANTZ DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2003-04-18 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-18 |
Time |
13:52 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-04-18 |
Time |
13:52 |
Sent To |
B |
|
Notes |
2003-04-18 00:00:00 | JW DESK TO RESTAMP. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2003-03-14 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-03-14 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
sthyng |
Date |
2003-03-14 |
Time |
10:07 |
Sent To |
E |
|
Notes |
2003-03-14 00:00:00 | TO BT DESK - HE WILL SEND TO JW |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2003-02-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-02-06 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2003-02-06 |
Time |
12:03 |
Sent To |
P |
|
Notes |
2003-02-06 00:00:00 | "P" IN BOX./WRT. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-01-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-02 |
Time |
12:46 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-01-02 |
Time |
12:46 |
Sent To |
|
|
Notes |
2003-01-02 00:00:00 | TO COMM BOARD #52 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2002-12-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-12-27 |
Time |
11:42 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-12-27 |
Time |
11:42 |
Sent To |
|
|
Notes |
2002-12-27 00:00:00 | TO COMM BOARD #6 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
N |
Date |
2003-04-30 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-04-30 |
Time |
12:41 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2003-04-30 |
Time |
12:39 |
Sent To |
|
|
Notes |
2003-04-30 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR REVIEW | | | | PLAN SHEET 1 (PLAN/RISER/SCHED), | | INDICATES A AHU WITH CU ON THE ROOF. | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW WITH MECHANICAL PERMIT | | APPLICATION. | | | | 1.OUTSIDE AIR CALCS AS PER 2001 FBC(M) | | TABLE 403.3. | | | | 2.EXHAUST FANS FOR RESTROOMS, (MAKE, | | MODEL, CFMS).INDICATE LOCATION OF | | EXHAUST FANS. | | | | 3.PROVIDE DUCT LAYOUT. | | | | 4.SHOW COMPLIANCE WITH 2001 FBC | | 1511.7 ON THE HEIGHT FOR THE CONDENSER | | UNIT STANDS ON THE ROOF.PLEASE | | PROVIDE DETAIL. | | | | 5.EQUIPMENT LOCATED ON THE ROOF AT A | | HEIGHT EXCEEDING 16 FT SHALL HAVE A | | PERMANENT MEANS OF ACCESS. 2001 FBC(M) | | 306.5. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
N |
Date |
2003-01-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-04-26 |
Time |
07:43 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2003-01-21 |
Time |
13:54 |
Sent To |
|
|
Notes |
2003-01-21 00:00:00 | MECHANICAL PERMIT REQUIRED - NO PLANS | | SUBMITTED.REVISION SUBMITTED 12-23-02 | | INDICATES AC & COOLER ON ELECTRICAL | | PANEL SCHEDULE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2002-04-04 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-04-04 |
Time |
10:48 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-04-04 |
Time |
10:47 |
Sent To |
|
|
Notes |
2002-04-04 00:00:00 | AS PER LETTER DATED MARCH 8, 2002 - | | LETTER FROM ROBERT L. BELL ARCHITECT PA. | | RESPONSE TO COMMENTS OF NO MECH PLANS | | SUBMITTED....MECH PLANS & | | SPECIFICATIONS TO BE SUBMITTED BY EACH | | TENANT SPACE. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2002-03-04 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-03-04 |
Time |
12:37 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-03-04 |
Time |
12:33 |
Sent To |
|
|
Notes |
2002-03-04 00:00:00 | | | PLANS DO NOT INDICATE WHAT CODE BUILDING | | WAS DESIGNED UNDER.PLEASE SPECIFY | | EITHER THE 1997 STANDARD BUILDING CODE | | OR 2001 FLORIDA BUILDING CODE. | | | | NO MECHANICAL PLANS SUBMITTED FOR | | REVIEW.PLEASE PROVIDE PLANS WITH | | MECHANICAL PERMIT APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
9 |
Status |
F |
Date |
2003-04-26 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-01 |
Time |
09:56 |
Rev Time |
0.25 |
Received By |
kstevens |
Date |
2003-04-26 |
Time |
07:37 |
Sent To |
M |
|
Notes |
2003-04-26 00:00:00 | RESTAMP DENIED | | | | 1) SET FOR RESTAMP DOES NOT REFLECT THE | | FILE COPY SET. | | 2) THERE ARE REVISIONS TO THE ORIGINAL | | SET ON THE SET SUBMITTED. | | 3) IF A RESTAMP SET IS NEEDED, PLEASE | | SUBMIT A SET THAT REFLECTS WHAT WAS | | ISSUED. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 | | (561) 805-6721 | | FAX (561) 653-2692 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
8 |
Status |
P |
Date |
2003-02-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-02-12 |
Time |
09:53 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2003-02-12 |
Time |
09:53 |
Sent To |
|
|
Notes |
2003-02-12 00:00:00 | APPROVED PER PAUL SCHMITZ |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
7 |
Status |
F |
Date |
2003-02-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-02-07 |
Time |
11:03 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2003-02-07 |
Time |
11:03 |
Sent To |
|
|
Notes |
2003-02-07 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) IF SHOWER WILL BE ADDED IN THE FUTURE | | THE ROOM SHALL COMPLY AND BE LARGE | | ENOUGH FOR A 5' TURNING SPACE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
F |
Date |
2003-02-04 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-02-06 |
Time |
12:04 |
Rev Time |
0.60 |
Received By |
kstevens |
Date |
2003-02-04 |
Time |
09:00 |
Sent To |
|
|
Notes |
2003-02-04 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) PER SECTION 11-4.1.3(11) ADAPTABLE | | SHOWERS SHALL COMPLY WITH 11-4.23. | | CONTROLS SHALL BE LOCATED PER 11-4.21.5, | | & AN UNOBSTRUCTED TURNING SPACE COMPLY- | | ING WITH 11-4.2.3 SHALL BE PROVIDED WITH | | IN AN ACCESSIBLE BATHROOM/SHOWER ROOM, | | PER 11-4.23.3. PLEASE PROVIDE DETAILS | | FOR ALL SECTIONS TO SHOW ADAPTABILITY. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2003-01-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-01-21 |
Time |
14:25 |
Rev Time |
1.50 |
Received By |
kstevens |
Date |
2003-01-21 |
Time |
14:25 |
Sent To |
|
|
Notes |
2003-01-21 00:00:00 | REVISION OK - ADD WATER HEATER |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2003-01-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-01-21 |
Time |
13:12 |
Rev Time |
1.25 |
Received By |
kstevens |
Date |
2003-01-18 |
Time |
16:10 |
Sent To |
|
|
Notes |
2003-01-21 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) SHT 1 SHOWER STALL, SHOWER SHALL | | COMPLY WITH 11-4.21 AND ALL SUBSECTIONS. | | ALSO THE CLEAR FLOOR SPACE, TURNING | | RADIUS, ACCESSIBLE DOOR ECT. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2002-08-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-08-02 |
Time |
18:18 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-08-02 |
Time |
18:18 |
Sent To |
|
|
Notes |
2002-08-02 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) PER SPC-94 TABLE 407 DRINKING FOUNT- | | AINS ARE REQUIRED FOR EACH SPACE. RES- | | PONSE NOTED. THIS IS NOT CONSIDERED A | | FIXTURE. EACH DRINKING FOUNTAIN SHALL BE | | PIPED INTO THE SANITARY AND SHALL BE | | SUPPLIED WITH POTABLE WATER FROM THE | | WATER RISER TO BE CONSIDERED A FIXTURE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-04-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-19 |
Time |
20:58 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-19 |
Time |
20:58 |
Sent To |
|
|
Notes |
2002-04-20 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) PER SPC TABLE 407 DRINKING FOUNTAINS | | ARE REQUIRED. THERE IS NO EXCEPTION FOR | | SIZE OF SPACE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-03-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-03-04 |
Time |
18:34 |
Rev Time |
0.75 |
Received By |
kstevens |
Date |
2002-03-04 |
Time |
18:34 |
Sent To |
|
|
Notes |
2002-03-04 00:00:00 | DENIED | | REFERENCE: FACBC-97 - BUILDING CODE ?? | | | | 1) PLANS DO NOT SPECIFY WHICH CODE THIS | | BLDG IS DESIGNED UNDER. PLEASE INDICATE | | EITHER SPC OR FLA. BLDG CODE FOR REVIEW. | | 2) SHT #1 PLEASE PROVIDE MINIMUM FACIL- | | ITIES. DRINKING FOUNTAIN - SERVICE SINK | | ECT MIGHT BE REQUIRED PER CODE. | | 3) SHTS #'S 2 & 3PLEASE CALCULATE PRI- | | MARY AND SECONDARY ROOF DRAINS PER CODE. | | CONSIDER 1/2 AREA OF VERTICAL WALLS FOR | | EACH CALCULATIONS AND SHOW LOCATIONS OF | | PRIMARY AND SECONDARY DRAIN ON PLANS. | | SUBMIT STORM RISER DIAGRAMS AND INDICATE | | DOWNSPOUT/LEADER SIZE. | | 4) SHT 1 WATER RISER DIAGRAM REQUIRED. | | SHOW PIPE SIZES, AND IF WATER HAMMER | | ARRESTORS ARE SHOWN LOCATION SHALL BE | | NEAR FIXTURE IN AN "EFFECTIVE RANGE" NOT | | AT TOP OF DROP. | | 5) BACKFLOW REQUIRED ON WATER SERVICE. | | LOCATION TO BE APPROVED BEFORE INSTALL- | | ATION. CALL 659-8005 | | 6) PLUMBING CONTRACTOR TO SUPPLY VALVE, | | BACKFLOW (WATTS N36), AND ADAPTOR FOR | | IRRIGATION CONTRACTOR. | | 7) SEPARATE PERMIT REQUIRED FOR IRRIGAT- | | ION. SUBMIT PLANS WITH PERMIT APPLICAT- | | ION. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-02-28 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-02-28 |
Time |
11:56 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|