Plan Review Details - Permit 02021919
Plan Review Stops For Permit 02021919
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2002-12-04 Cont ID  
Sent By jwitmer Date 2002-12-04 Time 06:59 Rev Time 0.50
Received By jwitmer Date 2002-12-04 Time 06:59 Sent To  
Notes
2002-12-04 00:00:00SITE SPECIFIC PRODUCT APPROVALS REVIEWED
 & STAMPEDJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-12-03 Cont ID  
Sent By jwitmer Date 2002-12-03 Time 12:58 Rev Time 0.50
Received By jwitmer Date 2002-12-03 Time 12:58 Sent To  
Notes
2002-12-03 00:00:00REVISION 10-09-02 SHEET A-3,A-4JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2002-12-03 Cont ID  
Sent By jwitmer Date 2002-12-03 Time 08:30 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2002-12-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02021919
 ADD: 232 BELMONTE
 CONT: GREG DAVIES
 TEL: (561)793-8225
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 12/03/02 REVIEW PRODUCT SUBMITTAL
  
 SITE SPECIFIC ENGINEERING REPORTS
 SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD. SEE ATTACHED PAPER WORK AND
 WPB MISSLE IMPACT PROTECTION STANDARD.
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-05-31 Cont ID  
Sent By pkrauss Date 2002-11-26 Time 09:45 Rev Time 1.00
Received By jwitmer Date 2002-05-31 Time 14:47 Sent To  
Notes
2002-05-31 00:00:00BUILDING PROVISO: REVISION #2 5/7/02
 1203.2.1. BATHROOMS, MINIMUM HEIGTH OF
 7'-0".

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-20 Cont ID  
Sent By jwitmer Date 2002-04-20 Time 14:38 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-08 Cont ID  
Sent By dpalmer Date 2002-04-17 Time 08:38 Rev Time 3.00
Received By jwitmer Date 2002-04-08 Time 11:09 Sent To  
Notes
2002-04-08 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02021919
 232 BELMONT RD
 CONT: GREGORY DAVIES
 TELL: 793-8225
 CELL:(561)310-2971
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1) SBC 104.2.2 ADDITIONAL INFOR REQUIRED
 PERMIT APPLICATION INDICATES A NEW
 SINGLE FAMILY RESIDENCE, SHEET A-1 INDI-
 CATES EXISTING FLOOR AREA IS THIS AN
 ADDITON AND REMODEL?
 2) SHEET A-5 INDICATES WIND LOADS FROM
 SBC FROM 1205 COACTAL EXPOSURE? 1205 IS
 RODENT PROOFING, AND EXPOSURE "B" IS
 CORRECT.
 3) THIS STRUCTURE IS TO BE CONSIDERED A
 3 STORY STRUCTURE,SINCE THE TOWER IS
 CONSIDERED HABITABLE SPACE,
 SBC 15.17.1.2.1. THE TOWER SHALL BE CON-
 STRUCTED OF AND SUPPORTED BY NONCOMBUST-
 IBLE MATERIALS. SUCH STRUCTURES SHALL BE
 SEPERATED FROMTHE BUILDING BELOW BY
 CONSTRUCTION HAVING A FIRE RESISTANCE
 RATING OF NOT LESS THAN 1 1/2 HRS AND
 IF ACCESS DOORS ARE PROVIDED, SUCH DOORS
 SHALL BE OFAN APPROVED FIRE RESISTANCE
 TYPE.
 THE OTHER VIEW IS TO CONSIDER THE TOWER
 A STORY IN TABLE 500, TYPE VI UNPRO.
 CONSTRUCTION ONLY ALLOWS FOR 2 STORIES,
 TO GAIN THE THIRD STORY TABLE 500 ALLOWS
 TYPE VI 1-HR PROTECTED CONSTRUCTION.THIS
 WOULD BE FOR ALL FRAMING ASSEMBLIES,
 CEILING/ FLOOR FOR THE FIRST AND SECOND
 FLOORS.
 3)- SHEET A-4 INDICATES THE FRONT DOOR
 TO BE A SOLID CORE WOOD DOOR/ W PECKY
 CYPRESS SITE SPECIFIC REPORT SHALL BE
 REQUIRED, THE PLANS ALSO INDICATE A
 TRANSOM ABOVE?
 4)- BEDROOM #2 EMERGENCY ESCAPE & RES-
 CUE OPENINGS, EVERY SLEEPING ROOM LOCAT-
 ED ON THE SECOND FLOOR SHALL HAVE AT
 LEAST ONE EXTERIOR EMERGENCY ESCAPE
 OPENING. THE MINIMUM CLEAR WIDTH IS 20".
 THE CLEAR WIDTH OR VENT WIDTH SHALL BE
 20".
 5)- SHEET A-9 SECTION OF MASONARY FIRE-
 PLACE, THE MASONAARY FIREPLACE DOES NOT
 GIVE SUFFICIENT INFORMATION, NOT ONLY IS
 THE HEIGTH BUT THE WIDTH OF THE FIRE
 PLACE OPENING.
 SBC 2114.3.2. THE FIREBOX OF A MASANARY
 FIREPLACE SHALL HAVE A MINIMUM DEPTH OF
 20 INCHES. THE THROAT SHALL BE AT LEAST
 8" ABOVE THE FIREPLACE OPENING.
 2114.3.3 THE FRONT AND SIDE WALLS OF THE
 THROAT AND SMOKE CHAMBER SHALL BE CONST
 RUCTED OF SOLID MASONARY HAVING A MINI-
 MUM TOTAL THICKNESS OF 8". THE BACK WALL
 OF THE THROAT AND SMOKE CHAMBER SHALL BE
 CONSTRUCTED OF SOLID MASONARY HAVING A
 MINIMUM THICKNESS OF 6". A MINIMUM 5/8"
 THICK CLAY FLUE LINING COMPL;YING WITH
 ASTM 315 SHALL BE PERMITTED TO FORM THE
 INSIDE SURFACE OF THE SMOKE CHAMBER.
 THE SIZE OF THE FLUE SHALL BE REQUIRED
 TO DETERMINE IF IT MEETS TABLE 2114.3.4.
 SBC 2114.3.9 AALL COMBUSTIBLE WOOD
 BEAMS, JOIST, AND STUDS SHALL BE MAIN-
 TAINED A MINIMUM OF 2" FROM THE OUTSIDE
 FACE OF THE CHIMNEY OR FIREPLACE
 MASONARY.ALSO SEE 2113.5, EXCEPTION.
 SBC 2114.3.11 ALL COMBUSTIBLE MAN-
 TLES AND SIMILAR TRIM SHALL BE KEPT AT
 LEAST 6" FROM THE FIREPLACE OPENING.
 2113.6 CLEANOUTS, CLEANOUT OPENINGS
 SHALL BE PROVIDED WITHIN 6" OF THE BASE
 OF EACH FLUE WITHIN EVERY MASONARY FIRE-
 PLACE. SEE EXCEPTION.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-12-05 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 09:58 Rev Time 0.00
Received By btrobaug Date 2002-12-04 Time 18:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-05-29 Cont ID  
Sent By btrobaug Date 2002-11-22 Time 18:31 Rev Time 0.00
Received By dpalmer Date 2002-05-29 Time 17:07 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-04-19 Cont ID  
Sent By dpalmer Date 2002-04-19 Time 13:01 Rev Time 0.00
Received By dpalmer Date 2002-04-19 Time 13:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-04-17 Cont ID  
Sent By dpalmer Date 2002-04-17 Time 08:37 Rev Time 0.00
Received By dpalmer Date 2002-04-17 Time 08:37 Sent To B
Notes
2002-04-17 00:00:00************* UNSAT ******************
  
 1) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 2 )NOTE: PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
 MISSING COUNTER AND PENINSULARS.
  
 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SIZE PER 250-66
  
 4)NOTE: PLEASE NOTE THAT SD ON LOWER
 LEVEL SHALL BE MOUNTED IN CLOSE
 PROXIMITY TO THE STAIRWAY LEADING TO THE
 FLOOR ABOVE. NFPA-72 2-5.2.1.3. SHOW
  
 5)NOTE: PLEASE NOTE MISSING BATH GFI
 IN LOWER BATHROOM PER 210-52D.
  
 6)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 7)NOTE: PLEASE NOTE THAT AHU#3 IS NOT
 SHOWN? PLEASE CLARIFY. COND UNIT#3 IS
 SHOWN ,BUT NOT AHU.
 PLEASE SHOW/CLARIFYDISC`S NOT SHOWN
 PER 440-11.
  
 8)NOTE: PLEASE NOTE THAT GARAGR OUTLET
 IS TO BE SHOWN AS GFI/GFI PROTECTED,
 210-8
  
 9)NOTE: PLEASE NOTE/CLARIFY REQ`ED MEANS
 OF EGRESS LIGHTING FOR HALL/STAIRWAY.
 SHOWN AS "J"-BOX ONLY. PLEASE SEE OTHER
 HALLS, HABITABLE ROOMS ANDBACK PORCH.
 210-70
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-14 Cont ID  
Sent By btrobaug Date 2002-03-14 Time 16:12 Rev Time 0.00
Received By btrobaug Date 2002-03-13 Time 07:52 Sent To R
Notes
2002-03-14 00:00:00*****************UNSAT!*****************
 PLEASE COMPLY WITH THE FOLLOWING AND
 RESUBMIT FOR REVIEW:
  
 1} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
  
 2} PLEASE SHOW ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6,AND
 210-52(C)(1)&(C)(3)
  
 3} SHOW DISCONNECT LOCATIONS FOR A/C
 CONDENSORS.
  
 4} GFI'S AT CONDENSORS PER 210-63NEC &
 309.2 MECHANICAL CODE.
  
 5} GARAGE GFI'S PER 210-52(G)
  
 6} SMOKE DETECTOR @ 1ST FLOOR STAIRWELL
 TO COMPLY WITH 2-5.2.1.4 NFPA-72.
  
 7} DEN BATH GFI PER 210-52(D).
  
 8} SMOKE DETECTOR @ 1ST FLOOR DEN BATH
 2-5.2.1.6 NFPA-72.( 3').
  
 9} BED ROOM CIRCUITS TO COMPLY WITH
 210-12 NEC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-25 Cont ID  
Sent By btrobaug Date 2002-11-25 Time 10:05 Rev Time 0.00
Received By btrobaug Date 2002-11-22 Time 09:50 Sent To B
Notes
2002-11-25 00:00:00TO JIM W./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-22 Cont ID  
Sent By btrobaug Date 2002-11-22 Time 18:31 Rev Time 0.00
Received By btrobaug Date 2002-11-22 Time 18:31 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-12-26 Cont ID  
Sent By pkrauss Date 2002-12-26 Time 07:24 Rev Time 0.40
Received By pkrauss Date 2002-12-26 Time 07:03 Sent To  
Notes
2002-12-26 00:00:00MECH REV PERMIT 02051887

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-11-26 Cont ID  
Sent By pkrauss Date 2002-11-26 Time 09:45 Rev Time 0.35
Received By pkrauss Date 2002-11-26 Time 09:10 Sent To B
Notes
2002-11-26 00:00:00MECHANICAL REVISION PERMIT 02051887

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-05-31 Cont ID  
Sent By pkrauss Date 2002-05-31 Time 07:13 Rev Time 0.35
Received By pkrauss Date 2002-05-31 Time 07:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-03 Cont ID  
Sent By dpalmer Date 2002-05-29 Time 17:07 Rev Time 0.50
Received By hmoser Date 2002-04-03 Time 17:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-07 Cont ID  
Sent By hmoser Date 2002-03-07 Time 18:56 Rev Time 0.50
Received By hmoser Date 2002-03-07 Time 18:55 Sent To  
Notes
2002-03-07 00:00:00PLAN DENIED
 ENERGY CALCS AND PLANS DO NOT MATCH.
 NO MANUAL J
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-01 Cont ID  
Sent By jleech Date 2002-06-01 Time 06:26 Rev Time 0.33
Received By jleech Date 2002-06-01 Time 06:26 Sent To  
Notes
2002-06-01 00:00:00REVISION RESET SHOWER 1ST FL.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-02 Cont ID  
Sent By jleech Date 2002-03-02 Time 12:27 Rev Time 0.33
Received By jleech Date 2002-03-02 Time 12:26 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2002-04-08 Cont ID  
Sent By btrobaug Date 2002-03-14 Time 16:13 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-12 Cont ID  
Sent By sgraham Date 2002-03-12 Time 15:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***