Plan Review Details - Permit 02021865
Plan Review Stops For Permit 02021865
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-08 Cont ID  
Sent By btrobaug Date 2002-05-16 Time 15:54 Rev Time 0.00
Received By btrobaug Date 2002-05-08 Time 15:52 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-14 Cont ID  
Sent By btrobaug Date 2002-03-14 Time 12:03 Rev Time 0.00
Received By btrobaug Date 2002-03-13 Time 17:23 Sent To  
Notes
2002-03-14 00:00:00******************UNSAT!****************
  
 PLEASE COMPLY WITH THE FOLLOWING AND
 RESUBMIT FOR REVIEW:
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3} BED ROOM CIRCUITS TO COMPLY WITH
 210-12.
  
 4} INDICATE CONDUCTOR AND WIRE SIZE FOR
 POOL PANEL FEEDER.
  
 5} GIVE LOCATION FOR PANEL "B".
  
 6} PLEASE SHOW LOCATIONS FOR AHU'S AND
 DISCONNECTS.
  
 7} INDICATE LOCATIONS FOR C/U
 DISCONNECTS.
  
 8} THERE ARE HAND DRAWN BOXES AND
 FIXTURES ON THE ELECTRICAL PLAN IN
 VIOLATION OF FS.481-221.
  
 9} THERE ARE NO 2ND FLOOR PLANS ON THE
 ELECTRICAL DRAWING.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-07 Cont ID  
Sent By hmoser Date 2002-03-07 Time 18:14 Rev Time 0.50
Received By hmoser Date 2002-03-07 Time 18:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2002-10-11 Cont ID  
Sent By kstevens Date 2002-10-11 Time 09:43 Rev Time 0.00
Received By kstevens Date 2002-10-11 Time 09:42 Sent To  
Notes
2002-10-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN. PLEASE SEE ADJUST-
 ED REVISION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-10-07 Cont ID  
Sent By jleech Date 2002-10-07 Time 14:56 Rev Time 0.25
Received By jleech Date 2002-10-07 Time 14:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-09-04 Cont ID  
Sent By kstevens Date 2002-09-04 Time 15:01 Rev Time 0.00
Received By kstevens Date 2002-09-04 Time 15:01 Sent To  
Notes
2002-09-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT FLOOR PLAN OR ACTUAL INSTALLATION
 OF SYSTEM.
 2) PLEASE SUBMIT RISER DIAGRAM THAT RE-
 FLECTS FLOOR PLAN AND ACTUAL INSTALLAT-
 ION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-11 Cont ID  
Sent By btrobaug Date 2002-05-16 Time 15:54 Rev Time 0.00
Received By kstevens Date 2002-05-11 Time 16:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-02 Cont ID  
Sent By jleech Date 2002-03-02 Time 10:06 Rev Time 0.33
Received By jleech Date 2002-03-02 Time 10:06 Sent To  
Notes
2002-03-02 00:00:00PROVISO;
 REVISED RISER DIAGRAM REQUIRED TO 94 SPC
 REQUIREMENTS.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2002-08-08 Cont ID  
Sent By jgomez Date 2002-08-08 Time 18:44 Rev Time 0.00
Received By jgomez Date 2002-08-08 Time 18:44 Sent To  
Notes
2002-08-08 00:00:00CHECKLIST:
 PROVIDE SPECIFICATIONS FOR SILICONE TO
 BE USED AT BUTT AREA.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2002-06-20 Cont ID  
Sent By jgomez Date 2002-06-20 Time 12:20 Rev Time 0.25
Received By jgomez Date 2002-06-20 Time 12:19 Sent To  
Notes
2002-06-20 00:00:00BUTT GLAZING PRODUCT APPROVAL CHECKLIST:
  
 1-INFORMATION SUBMITTED IS NOT
 ACCEPTABLE. INCOMPLETE INFORMATION AND
 INQUALIFIED DESIGNER. SEE SECTION 2406
 FBC 2001.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2002-06-03 Cont ID  
Sent By jgomez Date 2002-06-03 Time 18:46 Rev Time 0.25
Received By jgomez Date 2002-06-03 Time 18:46 Sent To  
Notes
2002-06-03 00:00:00BUTT GLAZING CHECKLIST:
  
 1-PRODUCT APPROVAL SUBMITTED DOESN'T
 HAVE ANY APPLICATION FOR BUTT GLAZING.
 SEE ARCHITECTURAL PLANS FOR ASSEMBLY
 SHOWN.
 2-SEE SECTION 2406.2 SBC 1997 (OR EVEN
 FBC 2001) FOR QUALIFIED PEOPLE TO
 DESIGN THIS TYPE OF ASSEMBLIES AND
 INFORMATION REQUESTED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-05-18 Cont ID  
Sent By jgomez Date 2002-05-18 Time 15:46 Rev Time 3.00
Received By jgomez Date 2002-05-18 Time 15:46 Sent To  
Notes
2002-05-18 00:00:00APPROVED WITH PROVISO:
 1-SEE PLANS FOR AREAS TO HAVE SAFETY
 GLASS AS REQUIRED BY SECTION 2405.2
 SBC 1997.
 2-PROVIDE PRODUCT APPROVAL FOR:
 A)BUTT GLAZING ASSEMBLY OR SITE COMPLETE
 ENGINEERING PACKAGE.
 NOTE: SEE SECTION 2406.2 SBC 1997 FOR
 QUALIFIED PEOPLE AND MATERIAL REQUIRED
 TO BE SUBMITTED FOR APPROVAL.
 B)SLIDING GLASS DOORS WITH THAT INCLUDES
 SIZES AND DESIGN PRESSURES AS SHOWN ON
 ARCHITECTURAL PLANS.
  
  
 NOTE:
 PROVIDE REQUESTED INFORMATION PRIOR TO
 INSTALLATION TO AVOID DELAYS OR CONFLICT

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-04-11 Cont ID  
Sent By jgomez Date 2002-04-11 Time 18:42 Rev Time 4.50
Received By jgomez Date 2002-04-11 Time 17:10 Sent To  
Notes
2002-04-11 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-CLEARLY SPECIFY ON PLANS AREAS TO HAVE
 SAFETY GLASS. SEC. 2405.2 SBC 1997.
 3-PROVIDE ATTIC ACCESS AT MAIN ROOF,
 GARAGE AND 2ND. FL. SEC. 2309.6 SBC/97
 4-SPECIFY SMOKE DETECTORS @ 1ST & 2ND
 FLOOR. SEC. 905.2.2 SBC 1997.
 5-ROOF FRAMING PLAN DOESN'T MATCH EXT.
 ELEVATIONS. REVISE AS REQUIRED.
 6-SEE COMMENTS THROUGHOUT PLANS AND
 REVISE/UPDATE/CLARIFY AS REQUIRED.
 7-PROVIDE COMPLETE DETAILS/SPECS FOR
 POSTS TO RECEIVE ENGINEERED GIRDERS AT
 THE ENDS. SEE COMMENTS ON PLANS.
 8-PROVIDE COMPLETE DETAIL/SPECS FOR 2X
 STRUCTURAL BUCKS AT SWING DOORS AS
 REQUIRED BY PRODUCT APPROVALS.
 9-PROVIDE COMPLETE 2 STORY SECTION/DET.
 AT BONUS ROOM FRONT ELEVATION. SPECIFY
 ALL CONNECTORS. FOUNDATION PLAN, BLDG
 SECTIONS AND EXTERIOR ELEVATIONS ARE
 VERY CONFUSSING AND DON'T MATCH.
 REVISE AS REQUIRED.
 10-PROVIDE STRUCTURAL BUCK DETAIL FOR
 GARAGE DOOR. SEC. 104.2.2 CITY AMENDM.
 AND SEC. 1606 SBC 1997.
 11-PROVIDE COMPLETE SPECS FOR CEILING
 INSTALLATION AT ENTRY AND REAR PORCHES.
 SPECIFY ALL FASTENERS. SEE ASTM C-1063
 12-DESIGN CERTIFICATION FOR BUILDING
 CODE COMPLIANCE FORM IS INCORRECT.
 MEAN ROOF HEIGHT IS 21'-0" +/-, NOT
 17'-0". REVISE VELOCITY PRESSURE
 ACCORDINGLY. SEC. 1606 SBC 1997.
 NOTE: INFORMATION ON THIS FORM TO BE
 INCLUDED ON DWGS. SEPARATE FORM NOT
 REQUIRED.
 13-PROVIDE PRODUCT APPROVAL FOR:
 A)BUTT GLAZING SYSTEM USED. OR COMPLETE
 SITE SPECIFIC ENGINEERING.
 B)ENTRY DOORS WITH LEGIBLE DRAWINGS.
 C)REAR SWING DOOR WITH LEGIBLE DRAWINGS.
 D)GARAGE DOOR THAT WILL RESIST UPLIFT
 LOADS CALCULATED BY ARCHITECT.
 E)FIXED WINDOWS.
 F)WINDOW MULLIONS.
 G)ARCHED WINDOWS.
 H)ROUND WINDOWS.
 I)SLIDING GLASS DOORS
  
 14-STORM PANELS: CLEARLY INDICATE ON
 PLANS MOUNTING SYSTEM AND ANCHOR TYPE
 AND SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, PANEL SPAN AND STRUCTURE
 TO BE ATTACHED TO (CONCRETE, CONCRETE
 BLOCK OR WOOD).***NOTE: SEE SHUTTER'S
 SUPPLIER. DWGS CAN'T BE USED. SEE NOTE
 REGARDING DWGS GOOD FOR ONE PERMIT ONLY
 NOTE:PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-28 Cont ID  
Sent By sgraham Date 2002-02-28 Time 12:02 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***