Plan Review Details - Permit 02021852
Plan Review Stops For Permit 02021852
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-04 Cont ID  
Sent By lsmith Date 2002-04-04 Time 11:43 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-18 Cont ID  
Sent By kstevens Date 2002-03-13 Time 15:11 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-03-18 00:00:00*************BUILDING UNSAT*************
  
 FAILED FOR THE FOLLOWING ITEMS:
  
 1. SUBMIT DETAILED DRAWINGS ON CONCRETE
 SLAB AND ANCHORING OF EQUIPMENT,
  
 2. ALL NOTES MUST STATE COMPLIANCE WITH
 FBC2001 CHAPTER 4 SEC. 424.2 PRIVATE
 SWIMMING POOLS.
  
 3. PLOT PLAN MUST SHOW DISTANCE
 OF EDGE OF WATER TO RESIDENCE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-22 Cont ID  
Sent By btrobaug Date 2002-03-22 Time 09:18 Rev Time 0.00
Received By btrobaug Date 2002-03-22 Time 09:02 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-06 Cont ID  
Sent By btrobaug Date 2002-03-06 Time 13:13 Rev Time 0.00
Received By btrobaug Date 2002-03-06 Time 13:03 Sent To P
Notes
2002-03-06 00:00:00**************UNSAT!********************
 WHEN INSTALLING ELECTRICAL HEATERS A
 LOAD CALCULATION IS REQUIRED FOR THE
 PANEL FEEDING THE EQUIPMENT. PLEASE
 PROVIDE THE SAME AND RESUBMIT FOR
 REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-04-04 Cont ID  
Sent By kstevens Date 2002-04-04 Time 11:28 Rev Time 0.00
Received By kstevens Date 2002-04-04 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-13 Cont ID  
Sent By btrobaug Date 2002-03-22 Time 09:18 Rev Time 1.25
Received By kstevens Date 2002-03-13 Time 15:11 Sent To B
Notes
2002-03-13 00:00:00DENIED
 REFERENCE: FBC 2001
  
 1) FBC SEC 104.2 PLEASE PROVIDE A CLEAR
 COPY OF POOL LAY OUT SHEET WITH PIPING,
 DRAIN LAV OUT, RETURNS, ECT.
 2) SEC 424.2.6.4 PLEASE SUBMIT MANUFACT-
 URE RECOMMENDATIONS.
 3) SEC 424.2.6.6.2 SUBMIT SPECS. FOR
 LISTED FITTING FOR VACUUM AND FOR ALL
 SUCTION INLETS.
 4) SEC 424.2.6.6.3 ENTRAPMENT AVOIDANCE,
 PLEASE SUBMIT DETAILS FOR MAIN DRAIN,
 AND VACUUM LINE. GIVE INFORMATION ON
 GRATES AND BACKUP SYSTEMS.
 5) SEC 424.2.6.6.5 SHOW DETAILS FOR
 CLEANER FITTINGS. SHOW LOCATION.
 6) SEC 424.2.7.2 SUBMIT DETAILS FOR AN-
 CHORING EQUIPMENT TO BASE. INDICATE BASE
 TO BE NOMINAL 4" SLAB.
 7) SEC 424.2.9 WATER SUPPLY, LOCAL ORD.
 #2853-95 BACK FLOW PREVENTER REQUIRED ON
 WATER SERVICE. PLEASE INDICATE ON NOTES.
 8) SEC 424.2.13.2 JOINTS AND CONNECTIONS
 FBC 2001 PLUMBING SEC 605.21 PURPLE
 PRIMER REQUIRED ON PVC PIPE AND FITTINGS
 STATE ON GENERAL NOTES.
 9) SEC 424.2.14.2 WATER RETENTION. GIVE
 DETAILS SHOWING A POSITIVE MEANS OF RE-
 TAINING WATER IN THE HEATER. SUBMIT MAN-
 UFACTURE CUT SHEETS SHOWING HOW WATER
 WILL BE RETAINED.
 10) SEC 424.2.14.4 INDICATE THAT ALL
 WATER HEATER EQUIPMENT TO BE INSTALLED
 WITH FLANGES OR UNIONS.
 11) COMPLY WITH FBC 2001 SEC 104.2
 BUILDING DRAWINGS AND SPECIFICATIONS.
 TOO MANY SWIMMING POOL PIPING SCHEMATICS
 ON THE PLANS, THIS IS VERY CONFUSING.
 SHOW INDIVIDUAL PIPING SCHEMATIC FOR EA.
 SWIMMING POOL. SHOW PIPING FOR THE ENT-
 IRE SYSTEM, PIPE SIZES, VENTS, SUCTION
 AND DISCHARGE PIPING ECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-05 Cont ID  
Sent By gjoyce Date 2002-03-05 Time 10:29 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***