Plan Review Details - Permit 02021850
Plan Review Stops For Permit 02021850
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-03-18 Cont ID  
Sent By kstevens Date 2002-03-13 Time 14:41 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-03-18 00:00:00*******PROVISO************
  
 1. SUBMIT DRAWING SHOWING EQUIPMENT SLAB
 AND ANCHORING DETAIL
  
 2. CORRECT ALL DRAWINGS TO REFLECT
 COMPLIANCE WITH FBC 2001 CHAPTER 4 SEC.
 424 "PRIVATE SWIMMING POOLS"
  
 NOTE:I WILL NOT BE PASSING ANY FUTURE
 POOLS IF THE DRAWINGS HAVE NOT BEEN CHAN
 GED TO SHOW THE CORRECT CODE AND THE CON
 CRETE SLAB & ANCHORING DETAIL AS REQUIRE
 D IN THE FBC 2001 CHAPTER 4 SECTION 424
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-06 Cont ID  
Sent By btrobaug Date 2002-03-06 Time 13:02 Rev Time 0.00
Received By btrobaug Date 2002-03-06 Time 12:43 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-13 Cont ID  
Sent By btrobaug Date 2002-03-06 Time 13:02 Rev Time 2.00
Received By kstevens Date 2002-03-13 Time 13:44 Sent To B
Notes
2002-03-13 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) SEC 424.2.6.4 PLEASE SUBMIT MANUFACT-
 URES RECOMMENDATIONS.
 2) SEC 424.2.6.6.2 SUBMIT SPECS. FOR
 LISTED FITTING FOR VACUMN AND FOR ALL
 SUCTION INLETS.
 3) 424.2.6.6.3 ENTRAPMENT AVOIDANCE,
 PLEASE SUBMIT DETAILS FOR MAIN DRAIN,
 SPA MAIN DRAIN AND VACUMN LINE. GIVE
 INFORMATION ON GRATES AND BACKUP SYSTEM.
 4) SEC 424.2.6.6.5 SHOW DETAILS FOR
 CLEANER FITTINGS. SHOW LOCATION.
 5) SEC 424.2.7.2 SUBMIT DETAIL FOR AN-
 CHORING EQUIPMENT TO BASE. INDICATE BASE
 TO BE NOMINAL 4" SLAB.
 6) SEC 424.2.9 WATER SUPPLY, LOCAL ORD.
 #2853-95 BACK FLOW PREVENTER REQUIRED ON
 WATER SERVICE. PLEASE INDICATE ON NOTES.
 7) SEC 424.2.13.2 JOINTS AND CONNECTIONS
 FBC 2001 PLUMBING SEC 605.21 PURPLE
 PRIMER REQUIRED ON PVC PIPING. STATE ON
 GENERAL NOTES.
 8) SEC 424.2.14.2 WATER RETENTION. GIVE
 DETAILS SHOWING A POSITIVE MEANS OF RE-
 TAINING WATER IN THE HEATER. SUBMIT MAN-
 UFACTURE CUT SHEETS SHOWING HOW WATER
 WILL BE RETAINED.
 9) SEC 424.2.14.4 INDICATE THAT ALL
 WATER HEATER EQUIPMENT TO BE INSTALLED
 WITH FLANGES OR UNIONS.
 10) SEC 424.2.15 GAS PIPING, SEPARATE
 PLANS AND PERMIT REQUIRED
 11) COMPLY WITH FBC 2001 SEC 104.2
 BUILDING DRAWINGS AND SPECIFICATIONS
 TOO MANY SWIMMING POOL PIPING SCHEMATICS
 ON THE PLAN, THIS IS VERY CONFUSING.
 SHOW INDIVIDUAL PIPING SHCEMATIC FOR EA.
 SWIMMING POOL, SPA. SHOW PIPING FOR THE
 ENTIRE SYSTEM, PIPE SIZES, VENTS, SUCT-
 ION AND DISCHARGE PIPING ECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-05 Cont ID  
Sent By gjoyce Date 2002-03-05 Time 10:27 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***