Plan Review Details - Permit 02021837
Plan Review Stops For Permit 02021837
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-03-17 Cont ID  
Sent By lsmith Date 2003-03-17 Time 16:45 Rev Time 0.20
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-28 Cont ID  
Sent By sthyng Date 2003-03-14 Time 10:21 Rev Time 0.00
Received By lsmith Date 2003-03-17 Time 16:44 Sent To  
Notes
2002-05-28 00:00:00REVISION #1 VARIOUS DATES IN MAY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-04-01 Cont ID  
Sent By hpiskura Date 2002-04-01 Time 10:39 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-10-25 Cont ID  
Sent By btrobaug Date 2002-11-07 Time 08:06 Rev Time 0.50
Received By btrobaug Date 2002-10-25 Time 10:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-10-24 Cont ID  
Sent By btrobaug Date 2002-10-24 Time 16:59 Rev Time 0.50
Received By btrobaug Date 2002-10-24 Time 16:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-29 Cont ID  
Sent By dpalmer Date 2002-05-29 Time 19:43 Rev Time 0.00
Received By dpalmer Date 2002-05-29 Time 19:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-14 Cont ID  
Sent By dpalmer Date 2002-03-14 Time 12:20 Rev Time 0.00
Received By dpalmer Date 2002-03-14 Time 08:34 Sent To  
Notes
2002-03-14 00:00:00******************* UNSAT **************
  
  
 1)NOTE: PLEASE NOTE, THAT PER LOCAL
 AMENDMENTS.230-70A. NO MORETHAN 8' OF
 UNPROTECTED CONDUCTORS INSIDE THE BLDG.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SEE NEC 220-3,220-10,220-11,
 220-13 AND ALL CONTINUOUS LOADS PER
 230-42,215-2,3.
  
 3)NOTE: PLEASE SEE 230-76, 230-79 FOR
 MANUAL MEANS OF DISC AND RATING OF
 SERVICE MAIN TO CLARIFY SHUNT TRIP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE SEE FIRE REVIEW FOR ANY COMMENTS
 THAT MAY AFFECT ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-03-14 Cont ID  
Sent By mamini Date 2002-03-14 Time 15:04 Rev Time 1.00
Received By mamini Date 2002-03-14 Time 15:03 Sent To  
Notes
2002-03-14 00:00:00PASSED WITH PROVISOS:
 1. DRIVEWAYS APPR. MUST BE PER CITY OF
 WPB' STANDARD IF IN CITY'S R.O.W AND PER
 FDOT'S STANDARD IF IN STATE ROAD R.O.W.
 2. ALL OFF-STREET PARKING MUST BE
 PAINTED WITH DOUBLE 4" WHITE FOR REGULAR
 AND BLUE FOR H.C.
 3. COVER FOR PNEUMATIC CULVERT MANHOLE
 MUST BE TRAFFIC RATED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-05-31 Cont ID  
Sent By mcarsill Date 2002-05-31 Time 12:32 Rev Time 0.00
Received By mcarsill Date 2002-05-31 Time 12:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-03-26 Cont ID  
Sent By mcarsill Date 2002-03-26 Time 12:45 Rev Time 0.00
Received By mcarsill Date 2002-03-26 Time 12:45 Sent To  
Notes
2002-03-26 00:00:00A) BUILDING ADDRESS REQUIRED.
 B) WRONG LIFE SAFETY CODE REFERENCED
 ON PLANS. SHOULD READ THE FLORIDA
 FIRE PREVENTION CODE, 2000 EDITION OF
 THE LIFE SAFETY CODE.
 C) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 D) STORAGE ROOM 117,AND
 STORAGE/MECHANICAL ROOM 104 ARE TO BE
 AT LEAST ONE HOUR FIRE RATED AND BE
 EQUIPPED WITH AT LEAST C LABELED FIRE
 DOORS, SINCE NO FIRE SPRINKLERS ARE
 PLANNED.
 E) DOOR 122 FOR THE JANITOR'S ROOM
 IS NOT FIRE RATED LIKE THE ROOM IS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-26 Cont ID  
Sent By sthyng Date 2003-03-26 Time 14:19 Rev Time 0.00
Received By sthyng Date 2003-03-26 Time 14:19 Sent To M
Notes
2003-03-26 00:00:00REVISION TO MECH BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 10:21 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 10:21 Sent To B
Notes
2003-03-14 00:00:00TO HP DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-31 Cont ID  
Sent By pkrauss Date 2003-03-31 Time 14:17 Rev Time 0.45
Received By pkrauss Date 2003-03-31 Time 14:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-02 Cont ID  
Sent By sthyng Date 2003-03-26 Time 14:25 Rev Time 0.35
Received By pkrauss Date 2002-03-20 Time 12:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-06 Cont ID  
Sent By kstevens Date 2002-06-06 Time 10:56 Rev Time 0.00
Received By kstevens Date 2002-06-06 Time 10:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-02 Cont ID  
Sent By jleech Date 2002-04-02 Time 15:01 Rev Time 1.50
Received By jleech Date 2002-04-02 Time 15:01 Sent To  
Notes
2002-04-02 00:00:00DENIED;
 1.WATER HEATER SHALL BE READLY ACCESS-
 ABLE PER 94 SPC SEC. 501.7. INSTALL
 WATER HEATER ON FLOOR OR OTHER READLY
 ACCESSABLE LOCATION.
 2.DRINFING FOUNTAIN SHALL ACCOMMODATE
 PEOPLE WHO HAVE DIFFICULTY BENDING AND
 PEOPLE IN WHEEL CHAIRS. SEE 97 FACBC
 SEC 4.1.3 (10).
 3.APPROVED ENGINEERED MECHANICAL HAMMER
 ARRESTERS SHALL BE SIZED BY THE
 ENGINEER AND INSTALLED PER MANUFACTORS
 RECOMENDATIONS. SEC 607.8.2. PAGE P-1
 WATER RISER DIAGRAM, DELLETE AIR
 CHAMBER FROM DRAWING AND SHOW LOCATION
 OF REQUITED MHA'S.
 4.PAGE P-1 DRY WELL DETAIL. INSTALL A
 TEE IN CONDENSATE PIPE BEFORE THE
 DRY WELL EXTEND TEE ABOVE GROUND AND
 PUT A "U' BEND ONPIPE. THIS SERVICE
 AS A VENT AND AN OVERFLOW OUTLET.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369

Review Stop Z ZONING
Rev No 2 Status P Date 2002-12-18 Cont ID  
Sent By sgraham Date 2002-12-18 Time 09:49 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-13 Cont ID  
Sent By sgraham Date 2002-03-13 Time 10:32 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***