Plan Review Details - Permit 02021836
Plan Review Stops For Permit 02021836 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-03-28 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-03-28 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-03-04 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-03-04 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-03-04 00:00:00 | PROVIDE A DETAIL FOR CUTTING THE SECOND | | FLOOR, AND THE ROOF.ALSO, SHOW THE | | FIRE RATED SHAFT REQUIRED BY SBC 705.6. | | INCLUDE PENETRATIONS FOR THE ELECTRICAL. | | | | WILL THE DEMISING WALL BE CONSTRUCTED | | COMPLETELY?PLANS SHOW DRY WALL TO BE | | INSTALLED AT A LATER DATE. | | | | SHOW THE MEANS OF EGRESS FROM THE NEWLY | | DEMISED SPACES SHOWN AS R1 AND R1A. | | | | IF THE NEW DOOR ON THE NORTH END OF | | SPACE R1A DISCHARGES TO AN EXIT COURT | | OR SIMILAR, THAN THE LOUVER ABOVE MUST | | BE FIRE PROTECTED AS WELL.SEE SBC | | 1010.2 & SBC 1010.3. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
N |
Date |
2002-03-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-05 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-03-05 |
Time |
09:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-03-01 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-03-01 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-03-01 |
Time |
10:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2002-03-28 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-03-04 |
Time |
09:25 |
Rev Time |
0.30 |
Received By |
hpiskura |
Date |
2002-03-04 |
Time |
09:25 |
Sent To |
|
|
Notes |
2002-03-04 00:00:00 | | | PROVISO:MECHANICAL PERMIT 02021838 | | | | PERMIT IS FOR EXHAUST DUCTWORK & FIRE | | DAMPER. (NO HVAC) | | | | PROVIDE MANUFACTURER SUBMITTAL DATA FOR | | FIRE DAMPER PRIOR TO INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2002-03-28 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-03-28 |
Time |
08:02 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|