Plan Review Details - Permit 02021826
Plan Review Stops For Permit 02021826
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-23 Cont ID  
Sent By jgomez Date 2002-05-23 Time 12:13 Rev Time 1.50
Received By jgomez Date 2002-05-23 Time 12:13 Sent To  
Notes
2002-05-23 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE PRODUCT APPROVALS (BEFORE ANY
 INSTALLATION) FOR:
 A)FLAT ROOF SYSTEM. SEE PLANS.
 NOTE: SHINGLES CAN'T BE USED ON FLAT
 ROOFS.
 B)SINGLE HUNG WINDOWS WITH LEGIBLE
 DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-29 Cont ID  
Sent By kstevens Date 2002-04-22 Time 17:45 Rev Time 2.00
Received By jgomez Date 2002-04-29 Time 10:57 Sent To  
Notes
2002-04-29 00:00:00CHECKLIST:
 1-BRING DRAWINGS TO PALM BEACH COUNTY TO
 PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 2-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 SBC 1997.
 3-REVISE ROOF SLOPE. MIN. SLOPE TO BE
 1/4" PER FT. SEC. 1503.1.2.3 SBC 1997.
 4-ENGINEER TO SPECIFY ON PLANS HOW IS
 NEW FOUNDATION AND WALL GOING TO BE
 ATTACHED TO EXISTING FOUNDATION AND
 WALLS. SEC. 104.2.2 CITY AMENDMENTS TO
 SBC 1997.
 5-PROVIDE COMPLETE WALL SECTION/DETAIL
 THRU EXISTING WALL AND NEW ROOF.
 SPECIFY HOW NEW 4X6 ROOF JOISTS ARE
 GOING TO BE ANCHORED USING SIMPSON OR
 USP CONNECTOR SPECIFIED ON ROOF
 FRAMING PLAN. NOTE: THIS CONNECTOR IS
 DESIGNED TO BE EMBEDDED INTO CONCRETE.
 HOW IS THE CONNECTOR GOING TO BE
 EMBEDDED INTO EXISTING CONCRETE BEAM?
 6-CLARIFY WHICH TYPE OF CONCRETE SLAB IS
 GOING TO BE USED. WALL SECTION CALLS
 FOR WIRE MESH WHILE FOUNDATION PLAN
 CALLS FOR FIBER MESH.
 7-PROVIDE PRODUCT APPROVAL FOR:
 A)FLAT ROOF SYSTEM SPECIFIED ON PLANS.
 B)SINGLE HUNG WINDOWS WINDOWSWITH
 APPROVED DRAWINGS.
 C)EXTERIOR DOOR WITH APPROVED DRAWINGS.
 D)STORM SHUTTERS WITH APPROVED DRAWINGS.
 SPECIFY SYSTEM AND ANCHOR TYPE AND
 SPACING TO BE USED.
 8-OWES $83.04 FOR UPDATED VALUATION AND
 RADON FEES.
 9-ENGINEER SPECIFY THE DESIGN PRESSURES
 CALCULATED FOR EXTERIOR OPENINGS PER
 SECTION 1606 SBC 1997.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-11 Cont ID  
Sent By btrobaug Date 2002-04-11 Time 07:36 Rev Time 0.00
Received By btrobaug Date 2002-04-11 Time 07:23 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-04-23 Cont ID  
Sent By kstevens Date 2002-04-22 Time 17:47 Rev Time 0.25
Received By pkrauss Date 2002-04-23 Time 14:42 Sent To  
Notes
2002-04-23 00:00:00NO MECHANICAL PLANS OR INFORMATION
 SUBMITTED FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-22 Cont ID  
Sent By btrobaug Date 2002-04-11 Time 07:36 Rev Time 0.00
Received By kstevens Date 2002-04-22 Time 17:33 Sent To M
Notes
2002-04-22 00:00:00PASSED/PROVISO
  
 VENT REQUIRED FOR TUB. REVISION REQUIRED
 BEFORE FINAL.

Review Stop Z ZONING
Rev No 2 Status P Date 2002-04-08 Cont ID  
Sent By sgraham Date 2002-04-08 Time 13:04 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-02-28 Cont ID  
Sent By sgraham Date 2002-02-28 Time 09:48 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-02-28 00:00:00NEED SITE PLAN