Plan Review Details - Permit 02021748
Plan Review Stops For Permit 02021748
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-09 Cont ID  
Sent By lsmith Date 2002-05-09 Time 16:34 Rev Time 0.25
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-04-15 Cont ID  
Sent By kstevens Date 2002-04-12 Time 22:34 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-06 Cont ID  
Sent By btrobaug Date 2002-03-06 Time 08:39 Rev Time 0.00
Received By btrobaug Date 2002-03-06 Time 07:36 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-04 Cont ID  
Sent By kstevens Date 2002-05-04 Time 08:42 Rev Time 0.00
Received By kstevens Date 2002-05-04 Time 08:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-12 Cont ID  
Sent By btrobaug Date 2002-03-06 Time 08:39 Rev Time 0.00
Received By kstevens Date 2002-04-12 Time 22:28 Sent To B
Notes
2002-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS.
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92.
 3)
 FBC-2001 SEC 424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 4) VALVES REQUIRED FOR HEATER BYPASS
 5)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 6)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 7)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 8)
 FBC-2001 SEC 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
 9) SIGNED AND SEALED PLANS SHALL NOT
 HAVE CHANGES PENNED ON PLANS. NEW SIGNED
 AND SEALED PLANS SHALL BE RESUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-05 Cont ID  
Sent By gjoyce Date 2002-03-05 Time 10:25 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***