2002-03-13 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 02021697 |
| 1219 FLORIDA AV |
| CONT: KEITH TURNEY |
| TEL: 684-0905 |
| |
| SBC= 1997 STANDARD BUILDING CODE |
| FLBC= 2001 FLORIDA BUILDING CODE |
| |
| 1)- PLANS SUBMITTED BETWEEN JAN.1, 2002 |
| AND FEB. 28, 2002 SHALL INDICATE AS TO |
| WHICH CODE THEY ARE DESIGNED TOO? THIS |
| REVIEW SHALL BE COMPLETED UNDER THE |
| 1997 SBC. |
| |
| 2) PLANS INDICATE A WINDOW DRAWN IN ON |
| THE EAST SIDE, NOT AS PART OF THE ARCH. |
| ORIGINAL DEPICTION, ARCH. TO REVIEW AND |
| OK BY LETTER FORM SIGN & SEAL. TO BE APP |
| ROVED BY HISTORICS BEFORE PLANS ARE ISSU |
| ED. |
| |
| 3)- THE PLANS DO NOT INDICATE DESIGN |
| PARAMETERS & ASSUMPTIONS AS REQUIRED |
| BY CHAPTER 16, FL. ST. S 481 & 553. |
| |
| 4)- THE PLANS & PERMIT APPLICATION IN- |
| DICATE THAT THE NORTH & WEST WALLS ARE |
| TO REPLACED AS WELL AS THE CONCRETE SLAB |
| SBC 1804.1.3 THE BOTTOM OF THE FOOTER |
| SHALL BE 12" BELOW GRADE. THE SUB-SHEATH |
| ING REQUIRES A CLEARENCE OF 6" BETWEEN |
| THE EARTH AND SHEATHING UNLESS SHEATHING |
| AND FRAMING ARE OF APPROVED PRESERVATIVE |
| TREATED WOOD OR APPROVED NATURALLY |
| DURABLE WOOD. |
| |
| 5)- SBC 1606.2.5.2 THE PRESSURE ZONES |
| ARE TO BE INDENTIFIED ON THE PLANS, POSI |
| TIVE & NEGITIVE PRESSURES FOR ALL OPEN- |
| INGS. |
| |
| 6)- THE PRODUCT APPROVAL SUBMITTAL FORM |
| FOR THE GARAGE DOOR IS TO BE REJECTED |
| WITHOUT CALCULATIONS INDICATING THAT |
| THE DOOR AND HARDWARE MEET THE WIND |
| REQUIREMENTS OF CHAPTTER 16. |
| |
| 7)- SBC TABLE 600 FOR TYPE VI STRUCTURES |
| LESS THAN 3'-0" FROM THE PROPERTY LINE |
| A 1 HR RATING IS REQUIRED FOR THE EXTER- |
| IOR WALL, INDICATE CODE COMPLIANCE |
| SBC 709.6.2.2. |
| |
| 8)- SBC 1007.3.1 TREADS & RISERS 2R+1T= |
| 24TO 25". |
| |
| 9)- SBC 1203.4.2 EVERY TOLIET ROOM SHALL |
| HAVE A WINDOW OR MECHANICAL VENTILATION. |
| |
| 10)- PLANS DO NOT INDICATE ANY HURRI- |
| CANE STRAPPING FROM RAFTER TO RAFTER |
| AT THE RIDGE. |
| |
| 11)- PRODUCT TESTING REPORTS, THE STEEL |
| SIDE DOOR REPORT EXPIRED, MISSING REPORT |
| FOR ROOFING MATERIALS. |
| |
| 12)- CONTRACTOR TO SSUBMIT PLANS TO THE |
| COUNTY FOR IMPACT FEE ASSESSMENT. |
| |
| 13)- THE PERMIT VALUE OF $19,000.00 IS |
| LOW. THE AVERAGE FOR TYPE VI CONST IS |
| 49.92 X 900= 45,000 WITHOUT VALUE TO |
| THE 900 SQ FT TO THE FIRST FLOOR. |
| |
| 14)- HOLD ON PROPERTY, 4X FEE BLDG W/O |
| FENCE PERMIT, 01/24/01 BOB COMPTON. |
| |
| 15)- TO PAY ADDTIONAL RADON FEES. |