Plan Review Details - Permit 02021392
Plan Review Stops For Permit 02021392
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-06-18 Cont ID  
Sent By hpiskura Date 2002-06-18 Time 10:35 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-06-18 00:00:00REVISIONS DATED 6/4/02 BY ARCHITECT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-30 Cont ID  
Sent By jwitmer Date 2002-03-30 Time 11:50 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-03-30 00:00:00A8.1 FASTENING DETAILS ENCLUDED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-03-01 Cont ID  
Sent By hpiskura Date 2002-03-01 Time 14:35 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-01 00:00:00PROVISO:DETAIL THE CONNECTION TO THE
 DECK SHOWN IN SECTIONS 1/A8.1 AND
 2/A8.1.INCLUDE FASTENERS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-07-02 Cont ID  
Sent By btrobaug Date 2002-07-02 Time 13:39 Rev Time 0.00
Received By btrobaug Date 2002-07-02 Time 13:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-06-12 Cont ID  
Sent By dpalmer Date 2002-06-12 Time 06:11 Rev Time 0.00
Received By dpalmer Date 2002-06-12 Time 06:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-02 Cont ID  
Sent By dpalmer Date 2002-04-02 Time 13:31 Rev Time 0.00
Received By dpalmer Date 2002-04-02 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-01 Cont ID  
Sent By dpalmer Date 2002-03-01 Time 06:14 Rev Time 0.00
Received By dpalmer Date 2002-03-01 Time 06:13 Sent To  
Notes
2002-03-01 00:00:00****************** UNSAT ************
  
 1)NOTE: PLEASE CLARIFY LOADS SHOWN FOR
 SOME RECEPT CIRCUITS ARE AT 180VA PER
 OUTLET. PLEASE NOTE SOME DO NOT SHOW
 THE SAME AMOUNT/ PLEASE DOUBLE CHECK
 LOADS FOR OUTLETS SHOWN. PLEASE SEE
 220-3/220-10/220-11/220-13
 LOAD WATTS PER SQ FT ETC.
 PLEASE NOTE THAT IT HAS BEEN COMMON TO
 SHOW CONNECTED LOADS. WE STILL NEED TO
 SEE THE CALCS.
  
 2)NOTE: PLEASE SHOW LOADS FOR TRACK
 LIGHTING PER 220-12B.
  
  
 PLEASE SUBMIT THE ABOVE INFORAMTION FOR
 REVEIW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-04-09 Cont ID  
Sent By mcarsill Date 2002-04-09 Time 13:33 Rev Time 0.00
Received By mcarsill Date 2002-04-09 Time 13:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-22 Cont ID  
Sent By mcarsill Date 2002-02-22 Time 11:25 Rev Time 0.00
Received By mcarsill Date 2002-02-22 Time 11:25 Sent To  
Notes
2002-02-22 00:00:00A) WHAT TYPE OF COOKING WILL BE
 PERFORMED AT THIS LOCATION. IT WAS
 NOTED THAT HOOD,DUCT,AND EXTINGUISHING
 SYSTEMS ARE PLANNED. WILL THE FOOD BE
 SOLD OR SAMPLED ON SITE. SEPARATE
 PLANS AND PERMITS WILL BE REQUIRED FOR
 ANY HOOD,DUCTS,OR EXTINGUISHING SYSTEMS.
 B) NO FIRE SPRINKLER DRAWINGS
 PROVIDED WITH PLANS.
 C) MANUAL PULL STATIONS ARE NOT
 REQUIRED IN MERCANTILE OCCUPANCIES.
 D) THE FIRE ALARM NOTES SECTION
 INDICATES CLASS B, STYLE C. ONLY CLASS
 A, STYLE D CIRCUITS WILL BE PERMITTED.
 E) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM EQUIPMENT.
 F) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE
 WALLS AND CEILINGS OF THE SPACE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-06-11 Cont ID  
Sent By pkrauss Date 2002-06-11 Time 11:56 Rev Time 0.35
Received By pkrauss Date 2002-06-11 Time 10:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-04 Cont ID  
Sent By pkrauss Date 2002-04-04 Time 11:16 Rev Time 0.35
Received By pkrauss Date 2002-04-04 Time 11:13 Sent To  
Notes
2002-04-04 00:00:00 
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLERS OR
 FREEZERS.PLEASE PROVIDE PLANS AND
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-02-25 Cont ID  
Sent By ndenmark Date 2002-02-25 Time 15:40 Rev Time 0.50
Received By ndenmark Date 2002-02-25 Time 15:40 Sent To  
Notes
2002-02-25 00:00:00PROVISO:
 APPROVAL IS FOR HVAC ONLY
 BATHROOM EXHAUST FAN TIMER IS TO BE SET
 TO RUN DURING BUSINESS HOURS
  
 KITCHEN EXHAUST DUCT WITHIN 18" OF ROOF
 JOISTS TO BE PROTECTED PER 1997 SMC 505.
 9 SUBSECTION 4
 SEPARATE PERMIT REQUIRED FOR HOOD,
 EXHAUST DUCT, AND SUPPRESSION SYSTEM.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-06-28 Cont ID  
Sent By kstevens Date 2002-06-28 Time 09:37 Rev Time 0.00
Received By kstevens Date 2002-06-28 Time 09:37 Sent To  
Notes
2002-06-28 00:00:00REVISION OK - ADD KIT SINK - ADD WASH
 MACHINES - CHANGE GAS DEV LENGTH (SHORT-
 ER)

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-05-17 Cont ID  
Sent By kstevens Date 2002-05-17 Time 11:31 Rev Time 0.00
Received By kstevens Date 2002-05-17 Time 11:31 Sent To  
Notes
2002-05-17 00:00:00PASSED/PROVISO
  
 MANUAL SHUT OFF VALVE AND UNIOR REQUIRED
 BEFORE (UPSTREAM) OF SOLINOID VALVE.
 MANUFACTURE INFORMATION REQUIRE FOR GAS
 PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-04-20 Cont ID  
Sent By kstevens Date 2002-04-20 Time 08:25 Rev Time 0.00
Received By kstevens Date 2002-04-20 Time 08:25 Sent To  
Notes
2002-04-20 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) FROM PREVIOUS REVIEW (#2) PLEASE SHOW
 ON PLANS APPROVED AIR CHAMBERS, (SEE
 ATTACHED SHEET). AIR CHAMBERS SHALL BE
 RECHARGEABLE AND ACCESSIBLE PER SPC SEC
 607.8.3SHT P-5.1
 2) FROM PREVIOUS REVIEW. SHT P5.1 WATER
 ISOMETRIC, DOUBLE LAVS AND DRINKING
 FOUNTAIN (3 FIXTURES) ARE BEING SUPPLIED
 WITH 1/2" COLD. MAXIMUM FIXTURES SUPPLI-
 ED WITH 1/2" COLD IS 2 FIXTURES. MODEL
 COUNTYWIDE AMENDMENTS TO THE SPC-94 SEC
 607.7. THIS HAS NOT BEEN CHANGED.
 3) FOLLOWING GAS PERMIT APPLICATION REQ-
 UIREMENTS HAVE NOT BEEN ADDRESSED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 E. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. SHOW THIS
 ON GAS RISER DIAGRAM
 F. SHT P5.1 GAS PIPING ISOMETRIC, TRENCH
 W/OPEN GRATE STILL SHOWN ON PLAN. INDIC-
 ATE ON PLAN THAT PIPE WILL BE PAINTED
 WITH A BITUMASTIC PAINT AND FILL TRENCH
 WITH A LIGHT WEIGHT CONCRETE TO ALLOW
 FOR EASY REMOVAL AND SERVICE OF PIPE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-26 Cont ID  
Sent By kstevens Date 2002-02-26 Time 13:47 Rev Time 1.50
Received By kstevens Date 2002-02-26 Time 13:47 Sent To  
Notes
2002-02-26 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A6 DETAIL 1/A6 URNAL IN MENS ROOM
 STATES HC WATER CLOSET. PLEASE SHOW
 CLEAR FLOOR SPACE FOR ALL HDCP FIXTURES.
 2) SHTS P0.1/P5.1 DOMESTIC WATER ISO.
 SHOWS AIR CHAMBERS AT TOP OF DROPS, AND
 PLUMBING NOTES #13 STATES WATER HAMMER
 ARRESTORS TO BE USED. PLEASE CLARIFY. IF
 WATER HAMMER ARRESTORS ARE TO BE USED,
 THEY SHALL BE LOCATED NEAR FIXTURE NOT
 AT TOP OF DROP.
 3) SHT P5.1 WATER ISO. DOUBLE LAVS AND
 DRINKING FOUNTAIN (3 FIXTURES) ARE BEING
 SUPPLIED WITH 1/2" COLD. MAXIMUM FIXTUR-
 ES SUPPLIED BY 1/2" COLD IS 2 FIXTURES.
 MODEL COUNTYWIDE AMENDMENTS TO THE SPC-
 94 SEC 607.7
 4) SHT P5.1 SEPARATE GAS PERMIT REQUIRED
 SEE FOLLOWING LIST OF PERMIT APPLICA-
 TION REQUIREMENTS. PROVIDE INFORMAT-
 ION REQUESTED.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 5) SHT P5.1 GAS PIPING ISOMETRIC, TRENCH
 W/OPEN GRATE NOT APPROVED. SEE SGC-97
 SEC 308.4.2(2) CHANNEL TO BE SUITABLY
 COVERED SO AS TO PREVENT THE ENTRANCE OF
 CORROSIVE MATERIALS. PAINTING PIPE WITH
 A BITUMASTIC PAINT AND FILL TRENCH WITH
 LIGHT WEIGHT CONCRETE TO ALLOW FOR EASY
 REMOVAL AND SERVICE OF PIPE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377