2002-03-04 00:00:00 | PLUMBING PLAN REVIEW, FBC 2001,DENIED. |
| (1) GENERAL NOTES #1 THE CURRENT CODE |
| IS FBC 2001,SEC 424.2.6 ENGINEERING |
| DESIGN.NOT SBCCI-94 PBC SWIMMING POOL |
| (2) NOTE #5 DISPOSAL OF WATER. SEE FBC |
| 2001,SEC 424.2.10 WASTE WATER DISPOSAL. |
| (3) NOTE #7 WATER SUPPLY.SEE FBC 2001 |
| SEC 424.2.9 WATER SUPPLY. AND LOCAL ORD |
| #2853-95 BACK FLOW PREVENTER REQUIRED |
| ON WATER SERVICE. |
| (4) POOL,SPA SCHEMAIC NOT APPROVED. |
| SPA MAIN DRAIN NOT SHOWN ON SCHEMATIC. |
| SWIMMING POOL HEATER, SEC 424.2.14 WATER |
| HEATING EQUIPMENT. WATER RETENTION PROVI |
| DE A DETAIL OF A POSITIVE MEANS OF RETAI |
| NING WATER IN THE POOL HEATER WITH A |
| BY-PASS. |
| (5) FL ENERGY CODE SEC 612.1ABC 2.3.2 |
| SPAS, HEATED POOLS SHALL BE EQUIPED WITH |
| A COVER TO MINIMIZE HEAT LOSS. |
| (6) SEC 424.2.15 GAS PIPING, SEPERATE |
| PLANS AND PERMIT REQUIRED. |
| (7) SEC 424.2.13.2 JOINTS, CONNECTIONS. |
| PURPLE PRIMER REQUIRED ON PVC PIPING, |
| FBC 2001 PLUMBING, SEC 605.21 |
| (8)424.2.7.2 PROVIDE DETAILS OF MOUNTING |
| AND ANCHORING POOL EQUIPMENT. |
| (9) SEC 424.2.6.6.2 SUCTIONS FITTINGS. |
| PROVIDE A DETAIL OF VACUM CLEANING INLET |