Plan Review Details - Permit 02021234
Plan Review Stops For Permit 02021234
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-03-06 Cont ID  
Sent By btrobaug Date 2002-03-05 Time 07:56 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2002-03-06 00:00:00************BUILDING PROVISO************
  
 1. DETAIL FOR PAD FORPOOL EQUIPMENT .
 SHOW TYPES OF ANCHORS & DETAILS.
  
 2. GENERAL NOTES MUST INCLUDE REFERENCE
 TO THE FBC CHAPTER 4 SECTIONS 424.
 REMOVE ALL REFERENCES TO FL. STATE
 STATUTES 515.THIS STATUTE HAS BEEN
 DELETED AND ALL POOL CODE REQUIREMENTS
 ARE SHOWN IN CHAPTER 424 OF THE FBC 2001
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-05 Cont ID  
Sent By btrobaug Date 2002-03-05 Time 07:56 Rev Time 0.00
Received By btrobaug Date 2002-03-05 Time 07:36 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-04-11 Cont ID  
Sent By kstevens Date 2002-04-11 Time 10:58 Rev Time 0.00
Received By kstevens Date 2002-04-11 Time 10:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-03-06 Cont ID  
Sent By pschmitz Date 2002-03-06 Time 07:01 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-03-06 00:00:00PLUMBING PLAN REVIEW, DENIED. 2ND TIME
 (1)GENERAL NOTES #1 THE CURRENYT CODE IS
 FBC 2001,SEC 424.2.6 ENGINEERING DESIGN.
 NOT SBCCI-94 PBC SWIMMING POOL CODE.
 (2)

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-04 Cont ID  
Sent By pschmitz Date 2002-03-04 Time 11:46 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-03-04 00:00:00PLUMBING PLAN REVIEW, FBC 2001,DENIED.
 (1) GENERAL NOTES #1 THE CURRENT CODE
 IS FBC 2001,SEC 424.2.6 ENGINEERING
 DESIGN.NOT SBCCI-94 PBC SWIMMING POOL
 (2) NOTE #5 DISPOSAL OF WATER. SEE FBC
 2001,SEC 424.2.10 WASTE WATER DISPOSAL.
 (3) NOTE #7 WATER SUPPLY.SEE FBC 2001
 SEC 424.2.9 WATER SUPPLY. AND LOCAL ORD
 #2853-95 BACK FLOW PREVENTER REQUIRED
 ON WATER SERVICE.
 (4) POOL,SPA SCHEMAIC NOT APPROVED.
 SPA MAIN DRAIN NOT SHOWN ON SCHEMATIC.
 SWIMMING POOL HEATER, SEC 424.2.14 WATER
 HEATING EQUIPMENT. WATER RETENTION PROVI
 DE A DETAIL OF A POSITIVE MEANS OF RETAI
 NING WATER IN THE POOL HEATER WITH A
 BY-PASS.
 (5) FL ENERGY CODE SEC 612.1ABC 2.3.2
 SPAS, HEATED POOLS SHALL BE EQUIPED WITH
 A COVER TO MINIMIZE HEAT LOSS.
 (6) SEC 424.2.15 GAS PIPING, SEPERATE
 PLANS AND PERMIT REQUIRED.
 (7) SEC 424.2.13.2 JOINTS, CONNECTIONS.
 PURPLE PRIMER REQUIRED ON PVC PIPING,
 FBC 2001 PLUMBING, SEC 605.21
 (8)424.2.7.2 PROVIDE DETAILS OF MOUNTING
 AND ANCHORING POOL EQUIPMENT.
 (9) SEC 424.2.6.6.2 SUCTIONS FITTINGS.
 PROVIDE A DETAIL OF VACUM CLEANING INLET
 END OF COMMENTSPAUL SCHMITZ
 561-659-8096X8233

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-25 Cont ID  
Sent By sgraham Date 2002-02-25 Time 16:23 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy