Plan Review Stops For Permit 02021177 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-06-04 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-06-04 |
Time |
12:16 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-06-04 |
Time |
12:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-03-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-03-01 |
Time |
19:31 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-03-01 |
Time |
19:31 |
Sent To |
|
|
Notes |
2002-03-01 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | 1) UNTIL MARCH 1, 2002 EITHER STANDARD | | BUILDING CODE 1997 OR FLORIDA BUILDING | | CODE 2001 MAY BE USED.NEITHER CODE IS | | REFERENCED ON THE PLANS.STATE WHICH | | CODE THE WORK IS TO BE CONSTRUCTED TO. | | | | 2) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 3) FBC 1012.1.4SECOND FLOOR EXIT DOOR | | 201/2.THE SWING OF THE RELOCATED DOOR | | OBSTRUCTS THE ROUTE TO THE STAIRS. | | MOVE/RECONFIGURE THE DOOR TO AVOID | | OBSTRUCTION OF THE MEANS OF EGRESS. | | | | 4) FBC 2405.2THE GLAZING IN DOOR 201-1 | | IS IN A 'HAZARDOUS LOCATION' AND IS | | REQUIRED TO BE SAFETY GLASS SATISFYING | | THE REQUIREMENTS OF THE CONSUMER | | PRODUCT SAFETY COMMISSION 16, CODE OF | | FEDERAL REGULATIONS, PART 1201 | | (CPSC 16-CFR, PART 1201).SUBMIT | | DETAILS TO DEMONSTRATE COMPLIANCE. | | | | 5) FBC* 104.2.1.2SHEET A1.2, DETAIL 5 | | AND DOOR ELEVATIONS.STATE THE | | THICKNESS OF THE TEMPERED GLASS IN THE | | DOOR AND STOREFRONT.ALSO, AMEND THE | | FLOOR PLAN TO CLARIFY THE LOCATION OF | | DOOR ELEVATION D. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-06-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-06-04 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-06-04 |
Time |
13:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-02-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-02-26 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-02-26 |
Time |
13:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2002-06-17 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-06-17 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2002-06-14 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-06-14 |
Time |
14:08 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-06-14 |
Time |
14:08 |
Sent To |
|
|
Notes |
2002-06-14 00:00:00 | ON 6.14.02 MET WITH RENE TERCILLA | | AND HE RED-LINED THE DRAWINGS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2002-06-05 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-06-05 |
Time |
11:59 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-06-05 |
Time |
11:59 |
Sent To |
|
|
Notes |
2002-06-05 00:00:00 | 1) WINDOWS USED FOR RESCUE PURPOSES | | WILL BE REQUIRED IN ROOMS THAT DO NOT | | HAVE DIRECT EXIT TO THE EXTERIOR. THE | | EXCEPTIONS TO THESE REQUIREMENTS DO NOT | | APPEAR TO BE APPLICABLE. IT WAS NOTED | | THAT NO CHANGES WERE TO BE MADE TO THE | | EXISTING WINDOWS. HOWEVER, MINIMUM | | CODE COMPLIANCE DOES NOT APPEAR TO | | BE MET AND MUST BE CORRECTED. | | | | 2) ENSURE THAT EMERGENCY LIGHTING | | IS INSTALLED. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-02-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-02-20 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-02-20 |
Time |
15:20 |
Sent To |
|
|
Notes |
2002-02-20 00:00:00 | A) PLEASE INDICATE HOURS OF OPERATION | | AND AGES OF CHILDREN EXPECTED WITHIN | | THE EXISTING BUILDING. | | B) IS THE EXISTING BUILDING SPRINKLER | | PROTECTED OR NOT. | | C) PLEASE INDICATE WINDOWS FOR RESCUE | | ON THE PLANS. PLEASE INDICATE SIZES | | OF WINDOWS. | | D) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | E) IF NO FIRE SPRINKLERS ARE PRESENT, | | ELECTRICAL ROOM 902 IS REQUIRED TO BE | | AT LEAST ON HOUR FIRE RATED. | | F) PLEASE INDICATE LOCATIONS OF PORTABLE | | FIRE EXTINGUISHERS. | | G) PANIC HARDWARE WILL BE REQUIRED ON | | EXIT DOORS BASED ON OCCUPANT LOAD | | COUNTS PROVIDED WITH PLANS. | | H) ANY CORRIDORS ARE REQUIRED TO BE | | AT LEAST 1/2 HOUR RATED. | | I) IT APPEARS THAT WINDOWS ARE LOCATED | | NEAR THE EXIT DOORS, NEAR ROOMS 202 | | AND 204. | | J) PLEASE PROVIDE MORE DETAILS ON | | EXISTING STAIRS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2002-06-17 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-06-17 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-06-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-06-13 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-06-13 |
Time |
09:08 |
Sent To |
|
|
Notes |
2002-06-13 00:00:00 | PASSED/PROVISO | | | | CUP DISPENSER SHALL BE INSTALLED AT | | DRINKING FOUNTAIN. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-02-25 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-02-25 |
Time |
17:38 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-02-25 |
Time |
17:37 |
Sent To |
|
|
Notes |
2002-02-25 00:00:00 | DENIED | | REFERENCE: SPC OR FBC? - FACBC-97 | | | | 1) CODE NOT REFERENCED ON PLANS. EITHER | | CODE DESIGN MAY BE USED PRIOR TO MARCH 1 | | 2002.PLAN REVIEW WILL BE DONE ON SPC- | | 94. | | 2) SHT G1.1 PLEASE SHOW WHERE 6" RAIN | | CONDUCTORS WILL BE RELOCATED. | | 3) PLEASE SUBMIT EXISTING FLOOR PLAN SO | | CHANGES CAN BE DETERMINED. | | 4) PLEASE SUBMIT CALCULATIONS FOR MINI- | | MUM FACILITIES. SHOW CLEAR FLOOR SPACE, | | SHOW TURNING RADIUS IN TOILET ROOMS. | | 5) PROVISIONS SHALL BE MADE FOR THOSE | | WHO HAVE DIFFICULITY BENDING OR STOOPING | | IF THE DRINKING FOUNTAINS ARE NOT HI/LOW | | TYPE. FACBC SEC 4.1.3(10). | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2002-06-17 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-06-17 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|