Plan Review Details - Permit 02021177
Plan Review Stops For Permit 02021177
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-04 Cont ID  
Sent By rbrown Date 2002-06-04 Time 12:16 Rev Time 0.00
Received By rbrown Date 2002-06-04 Time 12:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-01 Cont ID  
Sent By rbrown Date 2002-03-01 Time 19:31 Rev Time 0.00
Received By rbrown Date 2002-03-01 Time 19:31 Sent To  
Notes
2002-03-01 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) UNTIL MARCH 1, 2002 EITHER STANDARD
 BUILDING CODE 1997 OR FLORIDA BUILDING
 CODE 2001 MAY BE USED.NEITHER CODE IS
 REFERENCED ON THE PLANS.STATE WHICH
 CODE THE WORK IS TO BE CONSTRUCTED TO.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) FBC 1012.1.4SECOND FLOOR EXIT DOOR
 201/2.THE SWING OF THE RELOCATED DOOR
 OBSTRUCTS THE ROUTE TO THE STAIRS.
 MOVE/RECONFIGURE THE DOOR TO AVOID
 OBSTRUCTION OF THE MEANS OF EGRESS.
  
 4) FBC 2405.2THE GLAZING IN DOOR 201-1
 IS IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER
 PRODUCT SAFETY COMMISSION 16, CODE OF
 FEDERAL REGULATIONS, PART 1201
 (CPSC 16-CFR, PART 1201).SUBMIT
 DETAILS TO DEMONSTRATE COMPLIANCE.
  
 5) FBC* 104.2.1.2SHEET A1.2, DETAIL 5
 AND DOOR ELEVATIONS.STATE THE
 THICKNESS OF THE TEMPERED GLASS IN THE
 DOOR AND STOREFRONT.ALSO, AMEND THE
 FLOOR PLAN TO CLARIFY THE LOCATION OF
 DOOR ELEVATION D.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-04 Cont ID  
Sent By dpalmer Date 2002-06-04 Time 13:20 Rev Time 0.00
Received By dpalmer Date 2002-06-04 Time 13:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-02-26 Cont ID  
Sent By dpalmer Date 2002-02-26 Time 15:09 Rev Time 0.00
Received By dpalmer Date 2002-02-26 Time 13:44 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-06-17 Cont ID  
Sent By rbrown Date 2002-06-17 Time 13:48 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-06-14 Cont ID  
Sent By mcarsill Date 2002-06-14 Time 14:08 Rev Time 0.00
Received By mcarsill Date 2002-06-14 Time 14:08 Sent To  
Notes
2002-06-14 00:00:00ON 6.14.02 MET WITH RENE TERCILLA
 AND HE RED-LINED THE DRAWINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-06-05 Cont ID  
Sent By mcarsill Date 2002-06-05 Time 11:59 Rev Time 0.00
Received By mcarsill Date 2002-06-05 Time 11:59 Sent To  
Notes
2002-06-05 00:00:001) WINDOWS USED FOR RESCUE PURPOSES
 WILL BE REQUIRED IN ROOMS THAT DO NOT
 HAVE DIRECT EXIT TO THE EXTERIOR. THE
 EXCEPTIONS TO THESE REQUIREMENTS DO NOT
 APPEAR TO BE APPLICABLE. IT WAS NOTED
 THAT NO CHANGES WERE TO BE MADE TO THE
 EXISTING WINDOWS. HOWEVER, MINIMUM
 CODE COMPLIANCE DOES NOT APPEAR TO
 BE MET AND MUST BE CORRECTED.
  
 2) ENSURE THAT EMERGENCY LIGHTING
 IS INSTALLED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-20 Cont ID  
Sent By mcarsill Date 2002-02-20 Time 15:20 Rev Time 0.00
Received By mcarsill Date 2002-02-20 Time 15:20 Sent To  
Notes
2002-02-20 00:00:00A) PLEASE INDICATE HOURS OF OPERATION
 AND AGES OF CHILDREN EXPECTED WITHIN
 THE EXISTING BUILDING.
 B) IS THE EXISTING BUILDING SPRINKLER
 PROTECTED OR NOT.
 C) PLEASE INDICATE WINDOWS FOR RESCUE
 ON THE PLANS. PLEASE INDICATE SIZES
 OF WINDOWS.
 D) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 E) IF NO FIRE SPRINKLERS ARE PRESENT,
 ELECTRICAL ROOM 902 IS REQUIRED TO BE
 AT LEAST ON HOUR FIRE RATED.
 F) PLEASE INDICATE LOCATIONS OF PORTABLE
 FIRE EXTINGUISHERS.
 G) PANIC HARDWARE WILL BE REQUIRED ON
 EXIT DOORS BASED ON OCCUPANT LOAD
 COUNTS PROVIDED WITH PLANS.
 H) ANY CORRIDORS ARE REQUIRED TO BE
 AT LEAST 1/2 HOUR RATED.
 I) IT APPEARS THAT WINDOWS ARE LOCATED
 NEAR THE EXIT DOORS, NEAR ROOMS 202
 AND 204.
 J) PLEASE PROVIDE MORE DETAILS ON
 EXISTING STAIRS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-06-17 Cont ID  
Sent By rbrown Date 2002-06-17 Time 13:48 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-13 Cont ID  
Sent By kstevens Date 2002-06-13 Time 09:08 Rev Time 0.00
Received By kstevens Date 2002-06-13 Time 09:08 Sent To  
Notes
2002-06-13 00:00:00PASSED/PROVISO
  
 CUP DISPENSER SHALL BE INSTALLED AT
 DRINKING FOUNTAIN.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-25 Cont ID  
Sent By kstevens Date 2002-02-25 Time 17:38 Rev Time 0.50
Received By kstevens Date 2002-02-25 Time 17:37 Sent To  
Notes
2002-02-25 00:00:00DENIED
 REFERENCE: SPC OR FBC? - FACBC-97
  
 1) CODE NOT REFERENCED ON PLANS. EITHER
 CODE DESIGN MAY BE USED PRIOR TO MARCH 1
 2002.PLAN REVIEW WILL BE DONE ON SPC-
 94.
 2) SHT G1.1 PLEASE SHOW WHERE 6" RAIN
 CONDUCTORS WILL BE RELOCATED.
 3) PLEASE SUBMIT EXISTING FLOOR PLAN SO
 CHANGES CAN BE DETERMINED.
 4) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FACILITIES. SHOW CLEAR FLOOR SPACE,
 SHOW TURNING RADIUS IN TOILET ROOMS.
 5) PROVISIONS SHALL BE MADE FOR THOSE
 WHO HAVE DIFFICULITY BENDING OR STOOPING
 IF THE DRINKING FOUNTAINS ARE NOT HI/LOW
 TYPE. FACBC SEC 4.1.3(10).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-06-17 Cont ID  
Sent By rbrown Date 2002-06-17 Time 13:48 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***