Plan Review Details - Permit 02021097
Plan Review Stops For Permit 02021097
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-03-18 Cont ID  
Sent By btrobaug Date 2002-03-05 Time 07:21 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-03-18 00:00:00**********PROVISO*********
  
 THE FOLLOWING ITEMS NEED TO BE ADDED TO
 THE DRAWINGS TO COMPLY WITH THE NEW
 FBC 2001 CHAPTER 4 SEC 424.2 FOR
 PRIVATESWIMMING POOLS:
  
 1. ALL REFERENCES TO THE BUILDING CODES
 MUST BE "FBC 2001"
  
 2. INCLUDED ON THE DETAIL DRAWINGS MUST
 BE A DETAIL OF THE CONCRETE SLAB FOR
 THEPOOL EQUIPMENT INCLUDING ALL
 ANCHORING DETAIL.
  
 3. PLOT PLAN MUST CLEARLY SHOW DISTANCES
 FROM POOL TO RESIDENCE & WATERS EDGE TO
 PROPERTY LINE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-05 Cont ID  
Sent By btrobaug Date 2002-03-05 Time 07:21 Rev Time 0.00
Received By btrobaug Date 2002-03-05 Time 07:02 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-05-15 Cont ID  
Sent By kstevens Date 2002-05-15 Time 13:54 Rev Time 0.00
Received By kstevens Date 2002-05-15 Time 13:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-04 Cont ID  
Sent By kstevens Date 2002-05-04 Time 07:10 Rev Time 0.00
Received By kstevens Date 2002-05-04 Time 07:10 Sent To  
Notes
2002-05-04 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 2)
 FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 3)
 FBC-2001 SEC 424.2.7.1 POOL CIRCULATING
 PUMPS SHALL BE EQUIPPED ON THE INLET
 SIDE WITH AN APPROVED TYPE HAIR AND LINT
 STRAINER WHEN USED WITH A PRESSURE FIL-
 TER. (DETAIL)
 4)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 5)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 6)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-03 Cont ID  
Sent By pschmitz Date 2002-03-03 Time 10:40 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-03-03 00:00:00PLUMBING PLAN REVIEW,FBC 2001, DENIED.
 (1) GENERAL NOTES #8 PALM BCH CNTY 1994
 SWIMMING POOL CODE,CURRENT CODE,FBC 2001
 SEC 424.2.6 ENGINEERING DESIGN.
 (2) SEC 424.2.6.6.2 SUCTION FITTINGS.
 CLEANING LINE.PROVIDE DETAIL
 (3) SEC 424.2.7.2 PROVIDE A DETAIL OF
 MOUNTING & ANCHORING POOL EQUIPMENT.
 (4) SEC 424.WATER SUPPLY.AND LOCAL
 ORDINANCE #2853-95. BACK FLOW PREVENTER
 REQUIRED ON WATER SERVICE.
 (5) SEC 424.2.21.4 PROVIDE A DETAIL OF
 HYDROSTATIC RELIEF VALVE, AS REQUIRED.
 FOR AREAS OF HIGH WATER TABEL.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-21 Cont ID  
Sent By sgraham Date 2002-02-21 Time 15:41 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***