Plan Review Details - Permit 02020845
Plan Review Stops For Permit 02020845
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-07 Cont ID  
Sent By jwitmer Date 2002-03-07 Time 16:35 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-03-07 00:00:00PERMIT 02020845
 ADDRESS: 425 17TH ST
 COMPLETE PROPRTY MANAGEMENT
 TEL: (561) 626-2778
  
  
 1)- PLANS DO NOT IDENTIFY AS TO WHICH
 CODE THE PLANS WERE DESIGNED TOO?
 1997 SBC OR 2001 FLORIDA CODE?
 1997 SBC OR 2001 FLORIDA CODE?
 2)- THE PLANS LOOK LIKE THIS IS A 8 UNIT
 APT. COMPLEX, THE PLAN DOES NOT INDICATE
 BATHROOMS IN EACH UNIT.
 PLANS ARE TO BE DRAWN TO A DRAFTSMAN
 QUALITY WITH A MINIMUM OF 1/8" SCALE.
 3)- PLANS DO NOT INDICATE THE BUCK
 ATACHMENT FOR WINDOWS OR DOOR.
 4)- EXTERIOR ENTRY DOORS TO BE RATED
 AS A 20 MIN. DOOR.
 5)-SBC1005.4.4. EMERGENCY ESCAPE & RES-
 CUE OPENINGS (WINDOWS) GIVE THE CLEAR
 OPEN AREA FIRST & SECOND FLOOR.
 6)- FL ENERGY CODE 101.4.1 PREVIOSLY
 UNCONDITIONED EXISTING BUILDINGS WHICH
 WERE PERMITTED PRIOR TO MARCH 15, 1979
 TO WHICH HEATING OR COOLING SYSTEMS ARE
 ADDED SHALL MEET THE PRESCRIPTIVE
 REQUIREMENTS OF METHOD "C" FORM 600C-97
 IF DESIGNED UNDER 97 SBC OR FORM 600C-01
 IF DESIGNED UNDER THE 2001 FLORIDA CODE.
 A FORM SHALL BE REQUIRED FOR THE WORST
 CASE FIRST FLOOR & SECOND FLOOR.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-22 Cont ID  
Sent By dpalmer Date 2002-02-22 Time 12:53 Rev Time 0.00
Received By dpalmer Date 2002-02-22 Time 12:53 Sent To P
Notes
2002-02-22 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT NO ELECTRICAL
 WAS SUBMITTED FOR REVIEW. PLEASE NOTE
 THAT AN ELECTRICAL CONTRACTOR IS
 SIGNED ON FOR PERMIT? PLEASE SUBMIT
 LAYOUT FOR WORK AND SIZE OF ALL NEW
 A/C UNITS BEING INSTALLED,LOAD CALCS,
 SIZE OF EXISTING SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRIACL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-03-05 Cont ID  
Sent By pkrauss Date 2002-03-05 Time 09:48 Rev Time 0.00
Received By mcarsill Date 2002-03-05 Time 15:21 Sent To  
Notes
2002-03-05 00:00:00A) APARTMENT ENTRY DOORS ARE TO BE AT
 LEAST 20 MINUTE FIRE RATING AND BE
 EQUIPPED WITH SELF-CLOSING DEVICES.
 B) ELECTRIC POWERED SMOKE DETECTORS
 ARE REQUIRED OUTSIDE OF THE
 SLEEPING ROOMS.
 C) PLEASE PROVIDE INTERIOR
 CLASSIFICATION FOR THE WALLS AND
 CEILINGS.
 D) EGRESS WINDOWS TO COMPLY WITH
 BUILDING AND FIRE CODE REQUIREMENTS.
 E) BUILDING ADDRESS REQUIRED.
 F) PORTABLE FIRE EXTINGUISHERS
 REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-03-05 Cont ID  
Sent By pkrauss Date 2002-03-05 Time 09:46 Rev Time 0.30
Received By pkrauss Date 2002-03-05 Time 09:42 Sent To FIRE
Notes
2002-03-05 00:00:00 
 NO MECHANICAL SUBMITTED FOR REVIEW.
 PLEASE PROVIDE PLANS AND OR
 MANUFACTURER SUBMITTAL DATA FOR THE A/C
 EQUIPMENT WITH THE PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-03 Cont ID  
Sent By dpalmer Date 2002-02-22 Time 12:58 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-03-03 00:00:00REPLACE PLUMBING FIXTURES,ONLY. PES