Plan Review Details - Permit 02020712
Plan Review Stops For Permit 02020712
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-18 Cont ID  
Sent By rbrown Date 2002-03-14 Time 10:36 Rev Time 0.00
Received By rbrown Date 2002-03-14 Time 10:36 Sent To  
Notes
2002-03-14 00:00:00BUILDING PLAN REVIEW
 *******PROVISO******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
  
 --PASSED WITH THE FOLLOWING PROVISO--
 SUBMIT REVISED PLANS IF ANY OF THE FIVE
 UNLABELLED ROOMS ARE TO BE USED AS
 SLEEPING ROOMS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-22 Cont ID  
Sent By rbrown Date 2002-02-22 Time 11:37 Rev Time 0.00
Received By rbrown Date 2002-02-22 Time 11:37 Sent To  
Notes
2002-02-22 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) UNTIL MARCH 1, 2002 EITHER STANDARD
 BUILDING CODE 1997 OR FLORIDA BUILDING
 CODE 2001 MAY BE USED.NEITHER CODE IS
 REFERENCED ON THE PLANS.STATE WHICH
 CODE THE WORK IS TO BE CONSTRUCTED TO.
  
 2) AMEND THE PLANS TO SHOW THE
 USE/OCCUPANCY OF EACH ROOM.
  
 3) THE PROJECT DESCRIPTION ON THE PERMIT
 APPLICATION FORM STATES "TENANT
 SEPARATION WALLS", BUT THE NEW WALLS ON
 THE PLANS ARE ANNOTATED AS "NEW INTERIOR
 PARTITION",AND THERE ARE INTERCONNECTING
 DOORS BETWEEN ROOMS EAST OF THE ELEVATOR
 ANNOTATE THE PLANS TO CLARIFY THE SCOPE
 OF THE PERMIT APPLICATION.
  
 4) FBC 1005.4EVERY SLEEPING ROOM SHALL
 HAVE AT LEAST ONE EXTERIOR EMERGENCY
 ESCAPE AND RESCUE OPENING.IDENTIFY THE
 BEDROOMS ON THE PLANS AND DEMONSTRATE
 COMPLIANCE.THE INTERNAL DOOR HARDWARE
 SHALL NOT BE LOCKABLE, PREVENTING ACCESS
 TO THE EXISTING EXIT DOOR.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-14 Cont ID  
Sent By dpalmer Date 2002-03-14 Time 13:30 Rev Time 0.00
Received By dpalmer Date 2002-03-14 Time 13:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-14 Cont ID  
Sent By dpalmer Date 2002-02-14 Time 07:30 Rev Time 0.00
Received By dpalmer Date 2002-02-14 Time 07:30 Sent To  
Notes
2002-02-14 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT PERMIT
 APPLICATION SAYS TENANT WALLS? AND
 ELEC/PLUMB/MECH BOXES ARE CHECKED??
  
 2)NOTE: PLEASE NOTE PLANS CALL FOR ALL
 RESIDENTIAL ?? PLEASE SUBMIT LOAD
 CALCULATIONS AND PANEL SCHEDULES.
 PLEASE CLARIFY 2ND FLOOR IS SHOWN AS
 ALL ONE UNIT? PLEASE CLARIFY HOW THERE
 IS TENANT SEPARATION WALLS IN ONE UNIT
 OR ARRE THEY JUST INTERIOR WALLS FOR
 BEDROOMS?
  
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING #`S
 ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-19 Cont ID  
Sent By mcarsill Date 2002-03-19 Time 09:39 Rev Time 0.00
Received By mcarsill Date 2002-03-19 Time 09:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-14 Cont ID  
Sent By mcarsill Date 2002-02-14 Time 10:43 Rev Time 0.00
Received By mcarsill Date 2002-02-14 Time 10:43 Sent To  
Notes
2002-02-14 00:00:001) IS THE ENTIRE FLOOR SPACE USED
 FOR RESIDENTIAL PURPOSES. IS THE FLOOR
 A MIXED USE.
 2) ADDITIONAL SMOKE DETECTORS MAY BE
 NEEDED.
 3) PLEASE IDENTIFY ROOMS OR ROOM USES.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-03-15 Cont ID  
Sent By pkrauss Date 2002-03-15 Time 15:47 Rev Time 0.35
Received By pkrauss Date 2002-03-15 Time 15:47 Sent To  
Notes
2002-03-15 00:00:00 
 PROVISO ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-20 Cont ID  
Sent By pkrauss Date 2002-02-20 Time 09:55 Rev Time 0.45
Received By pkrauss Date 2002-02-20 Time 09:55 Sent To  
Notes
2002-02-20 00:00:00*******************DENIED***************
  
  
 APPLICATION INDICATES TENANT SEPARATION,
 SHOW COMPLIANCE WITH FLA ENERGY CODE
 (1997), THE SUPPLY OF HEATING & COOLING
 TO EACH ZONE SHALL BE CONTROLLED BY
 INDIVIDUAL THERMOSTATIC CONTROLS FOR
 CONTROLLING THE TEMPERATURE WITHIN THE
 ZONE.
  
 INDICATE THE USE OF THE ROOM TO THE
 SOUTHEAST.NO VENTILATION PROVIDED FOR
 THIS SPACE.ELECTIRICAL PLAN INDICATES
 AN OUTLET FOR TELEPHONE & COMPUTER.
  
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-03-15 Cont ID  
Sent By kstevens Date 2002-03-15 Time 16:16 Rev Time 0.33
Received By kstevens Date 2002-03-15 Time 16:16 Sent To  
Notes
2002-03-15 00:00:00PASSED/PROVISO
  
 BECAUSE OF CHANGE OF OCCUPANCY FROM
 COMMERCIAL TO RESIDENTIAL A WASHING
 MACHINE CONNECTION WAS REQUIRED. SPC-94
 TABLE 407.
 SUBSEQUENTLY A REVISION SHALL BE
 REQUIRED SHOWING THE WASHING MACHINE
 CONNECTION BOTH ON THE FLOOR PLAN AND
 ON A RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-02-19 Cont ID  
Sent By kstevens Date 2002-02-19 Time 09:22 Rev Time 0.33
Received By kstevens Date 2002-02-19 Time 09:22 Sent To  
Notes
2002-02-19 00:00:00NO PLUMBING INFORMATION ON THESE PLANS

Review Stop Z ZONING
Rev No 1 Status N Date 2002-03-20 Cont ID  
Sent By rbrown Date 2002-03-20 Time 15:55 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***