Plan Review Details - Permit 02020691
Plan Review Stops For Permit 02020691
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-01 Cont ID  
Sent By dpalmer Date 2002-04-01 Time 16:41 Rev Time 0.00
Received By dpalmer Date 2002-04-01 Time 16:41 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-01 Cont ID  
Sent By dpalmer Date 2002-03-01 Time 06:35 Rev Time 0.00
Received By dpalmer Date 2002-03-01 Time 06:35 Sent To B
Notes
2002-03-01 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT. PLEASE NOTE THAT
 MAINS/BRKRS AND PANELS NEED TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT. PER
 110-9
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 MISSING BLDG/FOOTER STEEL.
  
 5)NOTE: PLEASE SEE 210-12 PLEASE LIST
 THE REQ`D ARC FAULT PROTECTED CIRCUITS
 ON PANEL SCHEDULE. PLEASE NOTE THAT
 THIS REQ`MENT CAME INTO AFFECT JAN 1ST
 2002
  
 6)NOTE: PLEASE NOTE THAT NOTES MENTION
 99 NEC AND STATE CODE.??
 PLEASE NOTE THAT THERE IS NO STATE
 ELECTRICAL CODE THAT WE ARE AWARE OF.
 PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-02-23 Cont ID  
Sent By hmoser Date 2002-02-23 Time 12:47 Rev Time 0.33
Received By hmoser Date 2002-02-23 Time 12:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-09-16 Cont ID  
Sent By kstevens Date 2002-09-16 Time 17:54 Rev Time 0.00
Received By kstevens Date 2002-09-16 Time 17:54 Sent To  
Notes
2002-09-16 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-09-04 Cont ID  
Sent By kstevens Date 2002-09-04 Time 14:45 Rev Time 0.00
Received By kstevens Date 2002-09-04 Time 14:45 Sent To  
Notes
2002-09-04 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT FLOOR PLAN. MASTER BATH SHOWN NO
 SHOWER AND BOTH LAVS ARE ON SAME WALL.
 2) HALL BATH SHOWS SAME SIDE (RIGHT) OF
 BLDG DRAIN AS WASH MACHINE AND KITCHEN
 AND KITCHEN IS TOWARD THE BACK OF HOUSE
 NOT EVEN WITH WASH MACHINE. NO LAUNDRY
 TRAY IS SHOWN ON FLOOR PLAN.
 3) PLEASE SUBMIT A SANITARY RISER DIA-
 GRAM THAT REFLECTS THE FLOOR PLAN AND
 REFLECTS ACTUAL INSTALLATION OF SYSTEM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-02-23 Cont ID  
Sent By jleech Date 2002-02-23 Time 09:00 Rev Time 0.33
Received By jleech Date 2002-02-23 Time 09:00 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-04-03 Cont ID  
Sent By lhatten Date 2002-04-03 Time 20:22 Rev Time 0.75
Received By lhatten Date   Time   Sent To  
Notes
2002-04-03 00:00:00CALC. FEES & PRINT CARDS 04/03/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-03-10 Cont ID  
Sent By lhatten Date 2002-03-10 Time 11:06 Rev Time 2.50
Received By lhatten Date 2002-03-10 Time 11:05 Sent To  
Notes
2002-03-22 00:00:00REVIEW & STAMPED PLANS 03/10/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-21 Cont ID  
Sent By sgraham Date 2002-02-21 Time 09:31 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***