Plan Review Details - Permit 02020685
Plan Review Stops For Permit 02020685
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-01 Cont ID  
Sent By dpalmer Date 2002-04-01 Time 16:06 Rev Time 0.00
Received By dpalmer Date 2002-04-01 Time 16:06 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-27 Cont ID  
Sent By btrobaug Date 2002-02-27 Time 14:28 Rev Time 0.00
Received By btrobaug Date 2002-02-26 Time 17:56 Sent To R
Notes
2002-02-27 00:00:00*******************UNSAT!***************
 PLEASE PROVIDE THE FOLLOWING
 INFORMATIONAND MAKE THE NECESSARY
 CHANGES ON THE PLAN.
  
 1) PROVIDE AN A.I.C. RATING TO THE FIRST
 MEANS OF DISCONNECT AS PER 110-9 &
 110-10.
  
 2) PLEASE NOTE THAT A.F.C.I.MUST BE
 PROVIDED AS PER 210-12.INDICATE SAME ON
 PANEL SCHEDULE.
  
 3) BATH ROOM CIRCUITS MUST COMPLY WITH
 210-11(C)(3). INDICATE SAME ON PANEL
 SCHEDULE.
  
 4) COMPLY WITH N.F.P.A.-72,2-5.2.1.6(B)
 WHEN INSTALLING THE SMOKE DETECTOR IN
 THE HALL BETWEEN BED ROOMS 2&3.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY 0F WEST PALM BEACH
 561/ 659-8096

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-02-23 Cont ID  
Sent By hmoser Date 2002-02-23 Time 12:39 Rev Time 0.33
Received By hmoser Date 2002-02-23 Time 12:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-09-04 Cont ID  
Sent By kstevens Date 2002-09-04 Time 14:14 Rev Time 0.00
Received By kstevens Date 2002-09-04 Time 14:14 Sent To  
Notes
2002-09-04 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-02-23 Cont ID  
Sent By jleech Date 2002-02-23 Time 08:37 Rev Time 0.33
Received By jleech Date 2002-02-23 Time 08:37 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-04-03 Cont ID  
Sent By lhatten Date 2002-04-03 Time 20:07 Rev Time 0.75
Received By lhatten Date   Time   Sent To  
Notes
2002-04-03 00:00:00CALC. FEES & PRINT CARDS 04/03/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-03-11 Cont ID  
Sent By btrobaug Date 2002-03-11 Time 15:22 Rev Time 2.50
Received By lhatten Date 2002-03-11 Time 11:09 Sent To  
Notes
2002-03-22 00:00:00REVIEW & STAMPED PLANS 03/11/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-21 Cont ID  
Sent By sgraham Date 2002-02-21 Time 09:33 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***