Plan Review Details - Permit 02020683
Plan Review Stops For Permit 02020683
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-01 Cont ID  
Sent By dpalmer Date 2002-04-01 Time 14:02 Rev Time 0.00
Received By dpalmer Date 2002-04-01 Time 14:02 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-01 Cont ID  
Sent By dpalmer Date 2002-03-01 Time 07:20 Rev Time 0.00
Received By dpalmer Date 2002-03-01 Time 07:20 Sent To B
Notes
2002-03-01 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 -ED. PLEASE NOTE MAIN/BRKRS AND PANELS
 ARE TO BE RATED FOR THE AVAILABLE FAULT
 CURRENTPER 110-9.
  
 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 MISSING BLDG/FOOTER STEEL.
  
 4) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 5)NOTE: PLEASE NOTE MISSING HALL OUTLET
 PER 210-52H
  
 6)NOTE: PLEASE NOTE THAT AS OF JAN 1ST,
 2002 NEC. ART 210-12. PLEASE LIST THE
 ARC FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULES.
  
 7)NOTE: PLEASE CLARIFY NOTE THAT MENTION
 -S 99 NEC AND STATE CODE? PLEASE NOTE
 THAT WE ARE UNDER 99 NEC AND OUR LOCAL
 AMENDMENTS BUT THERE IS NO STATE
 ELECTRICAL CODE THAT WE ARE AWARE OF?
 PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-06 Cont ID  
Sent By hmoser Date 2002-07-06 Time 08:24 Rev Time 0.50
Received By hmoser Date 2002-07-06 Time 08:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-02-23 Cont ID  
Sent By hmoser Date 2002-02-23 Time 14:03 Rev Time 0.50
Received By hmoser Date 2002-02-23 Time 14:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-09-26 Cont ID  
Sent By kstevens Date 2002-09-26 Time 14:56 Rev Time 0.00
Received By kstevens Date 2002-09-26 Time 14:56 Sent To  
Notes
2002-09-26 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-09-04 Cont ID  
Sent By kstevens Date 2002-09-04 Time 07:33 Rev Time 0.00
Received By kstevens Date 2002-09-04 Time 07:33 Sent To  
Notes
2002-09-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT FLOOR PLAN. PLEASE SUBMIT A RISER
 DIAGRAM THAT REFLECTS THE FLOOR PLAN AND
 ALSO REFLECTS ACTUAL INSTALLATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-02-23 Cont ID  
Sent By jleech Date 2002-02-23 Time 11:13 Rev Time 0.33
Received By jleech Date 2002-02-23 Time 11:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-04-03 Cont ID  
Sent By lhatten Date 2002-04-03 Time 19:54 Rev Time 0.75
Received By lhatten Date   Time   Sent To  
Notes
2002-04-03 00:00:00CALC. FEES & PRINT CARDS 04/03/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-03-11 Cont ID  
Sent By lhatten Date 2002-03-11 Time 11:08 Rev Time 2.50
Received By lhatten Date 2002-03-11 Time 11:07 Sent To  
Notes
2002-03-22 00:00:00REVIEW & STAMPED PLANS 03/11/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-19 Cont ID  
Sent By sgraham Date 2002-02-19 Time 11:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***