Plan Review Details - Permit 02020683
Plan Review Stops For Permit 02020683 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-04-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-04-01 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-04-01 |
Time |
14:02 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-03-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-01 |
Time |
07:20 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-01 |
Time |
07:20 |
Sent To |
B |
|
Notes |
2002-03-01 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | -ED. PLEASE NOTE MAIN/BRKRS AND PANELS | | ARE TO BE RATED FOR THE AVAILABLE FAULT | | CURRENTPER 110-9. | | | | 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | -ED PER 210-8-A-6. | | | | 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | GOING TO BUILDING STEEL AND COLD WATER | | PER 250-50. | | MISSING BLDG/FOOTER STEEL. | | | | 4) NOTE: PLEASE SHOW ALL OUTLET SPACING | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | 5)NOTE: PLEASE NOTE MISSING HALL OUTLET | | PER 210-52H | | | | 6)NOTE: PLEASE NOTE THAT AS OF JAN 1ST, | | 2002 NEC. ART 210-12. PLEASE LIST THE | | ARC FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULES. | | | | 7)NOTE: PLEASE CLARIFY NOTE THAT MENTION | | -S 99 NEC AND STATE CODE? PLEASE NOTE | | THAT WE ARE UNDER 99 NEC AND OUR LOCAL | | AMENDMENTS BUT THERE IS NO STATE | | ELECTRICAL CODE THAT WE ARE AWARE OF? | | PLEASE CLARIFY. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-07-06 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-07-06 |
Time |
08:24 |
Rev Time |
0.50 |
Received By |
hmoser |
Date |
2002-07-06 |
Time |
08:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-02-23 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2002-02-23 |
Time |
14:03 |
Rev Time |
0.50 |
Received By |
hmoser |
Date |
2002-02-23 |
Time |
14:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2002-09-26 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-09-26 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-09-26 |
Time |
14:56 |
Sent To |
|
|
Notes |
2002-09-26 00:00:00 | REVISION OK - SANT. RISER DIAGRAM |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-09-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-09-04 |
Time |
07:33 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-09-04 |
Time |
07:33 |
Sent To |
|
|
Notes |
2002-09-04 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) SANITARY RISER DIAGRAM DOES NOT RE- | | FLECT FLOOR PLAN. PLEASE SUBMIT A RISER | | DIAGRAM THAT REFLECTS THE FLOOR PLAN AND | | ALSO REFLECTS ACTUAL INSTALLATION. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2002-02-23 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-02-23 |
Time |
11:13 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2002-02-23 |
Time |
11:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2002-04-03 |
|
|
Cont ID |
|
Sent By |
lhatten |
Date |
2002-04-03 |
Time |
19:54 |
Rev Time |
0.75 |
Received By |
lhatten |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-03 00:00:00 | CALC. FEES & PRINT CARDS 04/03/2002 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2002-03-11 |
|
|
Cont ID |
|
Sent By |
lhatten |
Date |
2002-03-11 |
Time |
11:08 |
Rev Time |
2.50 |
Received By |
lhatten |
Date |
2002-03-11 |
Time |
11:07 |
Sent To |
|
|
Notes |
2002-03-22 00:00:00 | REVIEW & STAMPED PLANS 03/11/2002 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-02-19 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2002-02-19 |
Time |
11:13 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|