Plan Review Details - Permit 02020618
Plan Review Stops For Permit 02020618
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-18 Cont ID  
Sent By rbrown Date 2002-04-18 Time 15:16 Rev Time 0.00
Received By rbrown Date 2002-04-18 Time 15:16 Sent To  
Notes
2002-03-13 00:00:00BUILDING PLAN REVIEW
 *******PROVISO******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-21 Cont ID  
Sent By rbrown Date 2002-02-21 Time 10:33 Rev Time 0.00
Received By rbrown Date 2002-02-21 Time 10:33 Sent To  
Notes
2002-02-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 1) UNTIL MARCH 1, 2002 EITHER STANDARD
 BUILDING CODE 1997 OR FLORIDA BUILDING
 CODE 2001 MAY BE USED.NEITHER CODE IS
 REFERENCED ON THE PLANS.STATE WHICH
 CODE THE WORK IS TO BE CONSTRUCTED TO.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE COPY ROOM DOOR TO THE CORRIDOR IS
 NOT SHOWN AS EXISTING ON THE DEMOLITION
 PLAN.EITHER AMEND THE PLANS TO SHOW
 THAT THIS DOOR IS EXISTING OR SPECIFY A
 NEW ONE-HOUR FIRE-RATED DOOR.
  
 4) THE FIRE REVIEW COMMENT (NO.2) SHALL
 BE ADDRESSED IN RESPECT OF THE PROPOSED
 ONE-HOUR FIRE-RATED ENTRY DOORS WITH
 'FIRE LITE' GLAZING.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-07-02 Cont ID  
Sent By btrobaug Date 2002-07-02 Time 15:42 Rev Time 0.00
Received By btrobaug Date 2002-07-02 Time 15:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-19 Cont ID  
Sent By dpalmer Date 2002-03-19 Time 19:30 Rev Time 0.00
Received By dpalmer Date 2002-03-19 Time 19:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-13 Cont ID  
Sent By dpalmer Date 2002-02-13 Time 07:31 Rev Time 0.00
Received By dpalmer Date 2002-02-13 Time 07:26 Sent To  
Notes
2002-02-13 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMNETS
 THAT MAY CHANGE ELECTRICAL PLAN.
  
 2)NOTE: PLEASE CLARIFY EXSITING SIGNAGE
 PER 600-5
  
 3)NOTE: PLEASE CLARIFY WHAT SIZE OCP IS
 FEEDING 100A MLO.
  
 4)NOTE: PLEASE CLARIFY NO LIGHTING SHOWN
 ON PANEL SCHEDULE/ OR LOAD CALCULATIONS?
 PLEASE CLARIFY LOAD CALCS SHOWN,,,
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-04-17 Cont ID  
Sent By lsmith Date 2002-04-17 Time 10:05 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-19 Cont ID  
Sent By mcarsill Date 2002-03-19 Time 10:37 Rev Time 0.00
Received By mcarsill Date 2002-03-19 Time 10:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-12 Cont ID  
Sent By mcarsill Date 2002-02-12 Time 17:42 Rev Time 0.00
Received By mcarsill Date 2002-02-12 Time 17:41 Sent To  
Notes
2002-02-12 00:00:001) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 2) PLEASE PROVIDE PRODUCT APPROVALS
 FOR ONE HOUR DOORS EQUIPPED WITH
 "FIRELITE" GLAZING.
 3) PLEASE PROVIDE AN ADDITIONAL EXIT
 SIGN LEADING TO THE COPY ROOM.
 4) PLEASE PROVIDE FLAME SPREAD DATA ON
 WHISPER WALL SOUND PANELS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-07-02 Cont ID  
Sent By ndenmark Date 2002-07-02 Time 14:03 Rev Time 0.50
Received By ndenmark Date 2002-07-02 Time 14:03 Sent To  
Notes
2002-07-02 00:00:00REVISION FOR DUCT LOCATIONS
 PROVISO VERIFY FIRE DAMPER INSTALLATION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-01 Cont ID  
Sent By pkrauss Date 2002-04-01 Time 10:07 Rev Time 0.35
Received By pkrauss Date 2002-04-01 Time 10:07 Sent To  
Notes
2002-04-01 00:00:00PROVISO ON PLAN - PRIOR TO CONNECTING TO
 ANY EXISTING DUCTWORK, CALL FOR AN
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-20 Cont ID  
Sent By pkrauss Date 2002-02-20 Time 08:29 Rev Time 0.40
Received By pkrauss Date 2002-02-20 Time 08:28 Sent To  
Notes
2002-02-20 00:00:00********************DENIED**************
  
  
 1.INDICATE DUCT SIZE OF NEW R6 DUCT-
 BOARD.
  
 2.INDICATE ANY EXISTING FIRE DAMPERS.
  
 3.PROVIDE INFORMATION ON ANY DUCT
 SMOKE DETECTORS IN AREAS USED FOR
 EGRESS.
  
 4.NO COMBUSTIBLES ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-04-23 Cont ID  
Sent By kstevens Date 2002-04-23 Time 19:10 Rev Time 0.00
Received By kstevens Date 2002-04-23 Time 19:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-04-18 Cont ID  
Sent By kstevens Date 2002-04-18 Time 10:06 Rev Time 0.00
Received By kstevens Date 2002-04-18 Time 10:06 Sent To  
Notes
2002-04-18 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) FROM PREVIOUS REVIEW. PLEASE SUBMIT
 DETAIL FOR KITCHEN SINK. SHOW COMPLIANCE
 WITH 4.24, 4.24.2, 4.24.3, 4.24.4, AND
 4.24.6. IF FRONTAL APPROACH. IF PARALLEL
 APPROACH, SHOW CLEAR FLOOR SPACE WITH
 SINK CENTERED IN CLEAR FLOOR SPACE.
 2) SHOW CUP DISPENSER FOR DRINKING
 FOUNTAIN FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING PER FACBC SECTION
 4.1.3(10) OR HI LOW DRINKING FOUNTAIN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-25 Cont ID  
Sent By kstevens Date 2002-02-25 Time 11:43 Rev Time 1.00
Received By kstevens Date 2002-02-25 Time 11:43 Sent To  
Notes
2002-02-25 00:00:00DENIED
 REFERENCE: FACBC-97 - SPC-94
  
 1) SPC TABLE 407 REQUIRED 1 DRINKING
 FOUNTAIN.
 2) SHT M-1 PLEASE PROVIDE A SANITARY
 RISER DIAGRAM WITH PIPE SIZING, AND SHOW
 TIE IN AND VENT.
 3) SHT M-1 PLEASE PROVIDE A WATER RISER
 DIAGRAM WITH PIPE SIZING AND IF A WATER
 HAMMER ARRESTOR IS USED SHOW LOCATION
 NEAR FIXTURE NOT AT TOP OF DRAP.
 4) PLEASE SHOW DETAIL OF KITCHEN SINK.
 PLEASE SHOW COMPLIANCE WITH FACBC SEC.
 4.24.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377.

Review Stop Z ZONING
Rev No 1 Status N Date 2002-04-17 Cont ID  
Sent By lsmith Date 2002-04-17 Time 10:05 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***