Plan Review Stops For Permit 02020618 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-04-18 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-04-18 |
Time |
15:16 |
Sent To |
|
|
Notes |
2002-03-13 00:00:00 | BUILDING PLAN REVIEW | | *******PROVISO****** | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | --PROVISO-- | | A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-02-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-02-21 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2002-02-21 |
Time |
10:33 |
Sent To |
|
|
Notes |
2002-02-21 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | 1) UNTIL MARCH 1, 2002 EITHER STANDARD | | BUILDING CODE 1997 OR FLORIDA BUILDING | | CODE 2001 MAY BE USED.NEITHER CODE IS | | REFERENCED ON THE PLANS.STATE WHICH | | CODE THE WORK IS TO BE CONSTRUCTED TO. | | | | 2) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 3) THE COPY ROOM DOOR TO THE CORRIDOR IS | | NOT SHOWN AS EXISTING ON THE DEMOLITION | | PLAN.EITHER AMEND THE PLANS TO SHOW | | THAT THIS DOOR IS EXISTING OR SPECIFY A | | NEW ONE-HOUR FIRE-RATED DOOR. | | | | 4) THE FIRE REVIEW COMMENT (NO.2) SHALL | | BE ADDRESSED IN RESPECT OF THE PROPOSED | | ONE-HOUR FIRE-RATED ENTRY DOORS WITH | | 'FIRE LITE' GLAZING. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2002-07-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-07-02 |
Time |
15:42 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-07-02 |
Time |
15:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-03-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-19 |
Time |
19:30 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-19 |
Time |
19:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-02-13 |
Time |
07:31 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-02-13 |
Time |
07:26 |
Sent To |
|
|
Notes |
2002-02-13 00:00:00 | *************** UNSAT ************** | | | | 1)NOTE: PLEASE SEE FIRE REVIEW COMMNETS | | THAT MAY CHANGE ELECTRICAL PLAN. | | | | 2)NOTE: PLEASE CLARIFY EXSITING SIGNAGE | | PER 600-5 | | | | 3)NOTE: PLEASE CLARIFY WHAT SIZE OCP IS | | FEEDING 100A MLO. | | | | 4)NOTE: PLEASE CLARIFY NO LIGHTING SHOWN | | ON PANEL SCHEDULE/ OR LOAD CALCULATIONS? | | PLEASE CLARIFY LOAD CALCS SHOWN,,, | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2002-04-17 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2002-04-17 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-03-19 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-03-19 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-03-19 |
Time |
10:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-02-12 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-02-12 |
Time |
17:42 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-02-12 |
Time |
17:41 |
Sent To |
|
|
Notes |
2002-02-12 00:00:00 | 1) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | 2) PLEASE PROVIDE PRODUCT APPROVALS | | FOR ONE HOUR DOORS EQUIPPED WITH | | "FIRELITE" GLAZING. | | 3) PLEASE PROVIDE AN ADDITIONAL EXIT | | SIGN LEADING TO THE COPY ROOM. | | 4) PLEASE PROVIDE FLAME SPREAD DATA ON | | WHISPER WALL SOUND PANELS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2002-07-02 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-07-02 |
Time |
14:03 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2002-07-02 |
Time |
14:03 |
Sent To |
|
|
Notes |
2002-07-02 00:00:00 | REVISION FOR DUCT LOCATIONS | | PROVISO VERIFY FIRE DAMPER INSTALLATION |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-04-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-04-01 |
Time |
10:07 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-04-01 |
Time |
10:07 |
Sent To |
|
|
Notes |
2002-04-01 00:00:00 | PROVISO ON PLAN - PRIOR TO CONNECTING TO | | ANY EXISTING DUCTWORK, CALL FOR AN | | INSPECTION. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-02-20 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-20 |
Time |
08:29 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2002-02-20 |
Time |
08:28 |
Sent To |
|
|
Notes |
2002-02-20 00:00:00 | ********************DENIED************** | | | | | | 1.INDICATE DUCT SIZE OF NEW R6 DUCT- | | BOARD. | | | | 2.INDICATE ANY EXISTING FIRE DAMPERS. | | | | 3.PROVIDE INFORMATION ON ANY DUCT | | SMOKE DETECTORS IN AREAS USED FOR | | EGRESS. | | | | 4.NO COMBUSTIBLES ABOVE THE CEILING | | IN THE RETURN AIR PLENUM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2002-04-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-23 |
Time |
19:10 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-23 |
Time |
19:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-04-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-18 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-18 |
Time |
10:06 |
Sent To |
|
|
Notes |
2002-04-18 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) FROM PREVIOUS REVIEW. PLEASE SUBMIT | | DETAIL FOR KITCHEN SINK. SHOW COMPLIANCE | | WITH 4.24, 4.24.2, 4.24.3, 4.24.4, AND | | 4.24.6. IF FRONTAL APPROACH. IF PARALLEL | | APPROACH, SHOW CLEAR FLOOR SPACE WITH | | SINK CENTERED IN CLEAR FLOOR SPACE. | | 2) SHOW CUP DISPENSER FOR DRINKING | | FOUNTAIN FOR THOSE WHO HAVE DIFFICULTY | | BENDING OR STOOPING PER FACBC SECTION | | 4.1.3(10) OR HI LOW DRINKING FOUNTAIN. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-02-25 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-02-25 |
Time |
11:43 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2002-02-25 |
Time |
11:43 |
Sent To |
|
|
Notes |
2002-02-25 00:00:00 | DENIED | | REFERENCE: FACBC-97 - SPC-94 | | | | 1) SPC TABLE 407 REQUIRED 1 DRINKING | | FOUNTAIN. | | 2) SHT M-1 PLEASE PROVIDE A SANITARY | | RISER DIAGRAM WITH PIPE SIZING, AND SHOW | | TIE IN AND VENT. | | 3) SHT M-1 PLEASE PROVIDE A WATER RISER | | DIAGRAM WITH PIPE SIZING AND IF A WATER | | HAMMER ARRESTOR IS USED SHOW LOCATION | | NEAR FIXTURE NOT AT TOP OF DRAP. | | 4) PLEASE SHOW DETAIL OF KITCHEN SINK. | | PLEASE SHOW COMPLIANCE WITH FACBC SEC. | | 4.24. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2002-04-17 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2002-04-17 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|