Plan Review Details - Permit 02020594
Plan Review Stops For Permit 02020594
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-05 Cont ID  
Sent By alange Date 2003-08-06 Time 16:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-05 00:00:00PROVISO:IMPACT FEES MUST BE PAID AND R
 ESIDENT INSPECTOR REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-12 Cont ID  
Sent By pkrauss Date 2002-02-12 Time 10:29 Rev Time 0.00
Received By pkrauss Date 2002-02-12 Time 10:29 Sent To  
Notes
2002-02-12 00:00:00 
 BUILDING:H. PISKURA
  
 FBC 705.1.3, REQUIRES THE FIRE RATED
 WINDOWS, (AND DOORS), TO BE LABELED AND
 LISTED IN ACCORDANCE WITH NFPA 80-95.
  
 THE STORAGE ROOM DOORS SHOWN AS (9) ON
 THE PLAN ARE REQUIRED TO BE RATED [45
 MIN] SINCE THEY ARE WITHIN THE TEN FEET
 WIDE SHADOW OF PROTECTION REQUIRED BY
 FBC 1006.2.4.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-07 Cont ID  
Sent By dpalmer Date 2002-03-07 Time 11:07 Rev Time 0.00
Received By dpalmer Date 2002-03-07 Time 12:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-13 Cont ID  
Sent By dpalmer Date 2002-02-13 Time 09:26 Rev Time 0.00
Received By dpalmer Date 2002-02-13 Time 09:26 Sent To  
Notes
2002-02-13 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE SHOW BEDROOM ARC FAULT
 REQ`MENTS PER 210-12
  
 2)NOTE: PLEASE NOTE THAT ONE SET HAS
 PAGES 4-5-6 CROSSED OUT? AND OTHERS
 CROSSED OUT AND NEW SHEETS???
  
 PLEASE SUBMIT NEW SETS WITHNOTE ONE
 ADDRESSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-02-12 Cont ID  
Sent By pkrauss Date 2002-02-12 Time 12:12 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
2002-02-12 00:00:00SEE PERMIT # 01081120 & 01091066

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-07 Cont ID  
Sent By mcarsill Date 2002-03-07 Time 16:50 Rev Time 0.00
Received By mcarsill Date 2002-03-07 Time 16:50 Sent To  
Notes
2002-03-07 00:00:00A) THE REQUIRED FIRE ALARM SYSTEM ARE TO
 BE PERMITTED SEPARATELY. PLANS, CUT
 SHEETS, WIRING DIAGRAMS, AND BATTERY
 CALCULATIONS ARE TO BE PROVIDED. MANUAL
 PULL STATIONS AND HORN STROBES ARE TO
 BE PROVIDED THROUGHOUT THE BUILDING. ON
 3.1.02 WRITER CONTACTED FELIX SIERRA
 WH ADVISED THAT THE FIRE ALARM CONTROL
 PANEL WILL BE LOCATED IN AN EXTERIOR
 STORAGE ROOM. THE FIRE ALARM SYSTEM
 IS TO BE CLASS A OR FULLY ADDRESSABLE.
 B) THE EXIT STAIRS ARE TO BE AT LEAST
 36" WIDE SINCE OCCUPANT LOADS ARE
 EXPECTED TO BE LESS THAN 50 PERSONS.
 THE MINIMUM HEIGHT OF RISER SHALL BE
 4", MAXIMUM HEIGHT OF RISER 7", WITH
 THE MINIMUM TREAD DEPTH OF AT LEAST
 11"S.
 C) ILLUMINATION IS TO BE PROVIDED FOR
 THE MEANS OF EGRESS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-12 Cont ID  
Sent By pkrauss Date 2002-02-12 Time 10:36 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
2002-02-12 00:00:00 
 THE BUILDING WAS REVIEWED UNDER THE
 FLORIDA FIRE PREVENTION CODE.
 1) FIRE HYDRANTS WILL BE RELOCATED TO
 ISLANDS TO PREVENT PROBLEMS WITH ACCESS
 TO THEM. THIS ARRANGEMENT WAS AGREED TO
 BY MR. FELIX SIERRA.
 2) GENERAL NOTES SECTION SHOULD READ
 FLORIDA FIRE PREVENTION CODE.
 3) ALL STORAGE ROOMS OUTSIDE OF DWELLING
 UNITS TO BE PROTECTED BY AT LEASAT ONE
 HOUR FIRE SEPARATION OF FIRE SPRINKLERS.
 4) THE REQUIREMENT FOR A FIRE ALARM
 SYSTEM STILL SEEMS TO BE PRESENT. THE
 TWO EXCEPTIONS TO THIS CODE REQUIREMENT
 DOES NOT APPEAR TO APPLY. PLEASE REVIEW
 CODE REQUIREMENT AND EXCEPTIONS.
 5) THE INFORMATION PROVIDED FOR THE
 WINDOWS IS CONFUSING. ARE THE EGRESS
 WINDOWS, SELF-CLOSING. PLEASE PROVIDE
 ADDITIONAL DETAILS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096, EXT. 8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-06 Cont ID  
Sent By alange Date 2003-08-06 Time 16:12 Rev Time 0.00
Received By alange Date 2003-08-06 Time 16:12 Sent To B
Notes
2003-08-06 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 14:59 Rev Time 0.00
Received By alange Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-04-04 Cont ID  
Sent By pkrauss Date 2002-04-04 Time 07:41 Rev Time 1.15
Received By pkrauss Date 2002-04-04 Time 07:06 Sent To  
Notes
2002-04-04 00:00:00 
 PROVISO ON PLAN -
  
 CONDENSATE SHALL TERMINATE A MINIMUM OF
 12" FROM THE BUILDING STRUCTURE AS PER
 2001 FBC 1503.4.4.
  
 "FIRE CHASE" FOR THE BATHROOM EXHAUST
 APPROVED BY HAROLD PISKURA.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-03-22 Cont ID  
Sent By pkrauss Date 2002-03-20 Time 15:55 Rev Time 0.50
Received By pkrauss Date 2002-03-20 Time 15:44 Sent To  
Notes
2002-03-20 00:00:00 
  
 AS PER PRIOR REVIEW O.A. SHALL COMPLY
 WITH THE 2001 FBC, MECHANICAL 403.3.
  
 THIS RESUBMITTAL INDICATES THE DESIGN
 FOR OUTSIDE AIR WILL BE TO THE
 EXCEPTION OF 403.2 & TO THE ASHRAE 62
 ALTERNATIVE 403.5.
  
 ALTERNATE MEANS & METHODS SHALL HAVE A
 PEER REVIEW BY ENGINEERS INDEPENDANT TO
 CMB ENGINEERING FIRM.UPON APPROVAL OF
 PEER REVIEW PLEASE SUBMIT TO NEIL MELICK
 DIRECTOR/BUILDING OFFICAL FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-02-26 Cont ID  
Sent By pkrauss Date 2002-02-26 Time 16:39 Rev Time 0.00
Received By pkrauss Date 2002-02-26 Time 16:16 Sent To  
Notes
2002-02-26 00:00:00 
  
 1.PLAN SHEET M-1 OUTSIDE AIR CALCS.,
 A. CALCULATION DOES NOT INCLUDE
 KITCHEN AREA AS REQUIRED PER
 TABLE 403.3.
 NOTE-PLAN SHEETS A5.01 - A5.06 STILL
 REFER TO THE 1997 SBC FOR THE DOORS
 & WINDOWS.
  
 2.BALANCED AIR RETURN - DEMONSTRATE A
 3/4" UNDERCUT OF A DOOR COMPLIES
 WITH 601.4 OF THE 2001 FMC IN WHICH
 PRESSURE DIFFERENTIAL ACROSS DOORS
 SHALL BE LIMITED TO 0.001" WC OR
 LESS.
  
 3.PLAN SHEET M-6 INDICATES AUXILIARY
 DRAIN PAN WITH OVERFLOW PROTECTION
 ON THE UPPER FLOORS ONLY.AS PER
 2001 FLORIDA BUILDING CODE, MECH
 307.2.3,ALL COILS ON WHICH
 CONDENSATION WILL OCCUR SHALL HAVE
 AN AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-12 Cont ID  
Sent By pkrauss Date 2002-02-12 Time 08:13 Rev Time 5.00
Received By pkrauss Date 2002-02-12 Time 08:13 Sent To  
Notes
2002-02-12 00:00:00*******************DENIED***************
  
 2001 FBC, MECHANICAL
  
 1.SHOW COMPLIANCE WITH FBC CHAPTER 13
 SECTION 610.1.ABC.1, ALL AIR
 DISTRIBUTION SYSTEMS SHALL BE SIZED
 & DESIGNED IN ACCORDANCE WITH
 RECOGNIZED ENGINEERING STANDARDS
 SUCH AS ACCA MANUAL D OR OTHER
 STANDARDS.
  
 2.REVISE ALL PLAN SHEETS TO REFER TO
 THE "2001 FLORIDA BUILDING CODE"
 INSTEAD OF THE 1997 SBC.
  
 3.PLAN SHEET A7.03 DETAIL #1 -
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION FOR ALL UNITS AS PER 2001
 FBC, MECHANICAL 307.2.3.
  
 4.PLAN SHEET M-2 - INDICATE DUCT SIZE
 OF BATHROOM EXHAUST.
  
 5.PLAN SHEET M-3 - CLARIFY DETAIL OF
 1ST FL (REV), EXHAUST DUCT DOES NOT
 APPEAR TO BE IN A RATED SHAFT.
  
 6.PROVIDE EXHAUST FAN MODEL # & CFM.
  
 7.SHOW COMPLIANCE WITH 2001 FBC, MECH
 403.1 & 601.4, BALANCED AIR RETURN.
  
 8.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 403.3 & TABLE 403.3, REQUIRED
 OUTDOOR VENTILATION AIR FOR PRIVATE
 DWELLING SINGLE AND MULTIPLE LIVING
 AREAS.
  
 9.HOLD LANDSCAPE BACK 12" FROM
 CONDENSER UNITS.
  
 10. CONDENSER UNITS NOT TO PLACED UNDER
 THE DRIP EDGE OF THE STRUCTURE.
  
 11. CONDENSATE SHALL TERMINATE 12" FROM
 THE BUILDING STRUCTURE AS PER 2001
 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-03-28 Cont ID  
Sent By kstevens Date 2002-03-28 Time 13:29 Rev Time 0.00
Received By kstevens Date 2002-03-28 Time 13:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-03-04 Cont ID  
Sent By kstevens Date 2002-03-04 Time 11:25 Rev Time 1.00
Received By kstevens Date 2002-03-04 Time 11:25 Sent To  
Notes
2002-03-04 00:00:00DENIED
 REFERENCE: FBC-2001 - FHA-AMEND-98
 DESIGN MANUAL
  
 1) FROM PREVIOUS REVIEW - SHT T1.01
 COVER SHEET CALLS FOR IRRIGATION SHEETS
 IR-1 & IR-2, NONE FOUND. PLEASE SUBMIT
 IRRIGATION SHEETS.
 2) FROM PREVIOUS REVIEW - #7 WATER RISER
 DIAGRAM TYPICAL OF ALL UNITS. WATER HAM-
 MER ARRESTORS REQUIRED FOR ALL REFRIG.
 ICE MAKERS. PLEASE SHOW ON RISER DIAG.
 3) FROM PREVIOUS REVIEW - #9 SHT P-6,
 SANT. RISER DIAG. W/MACHINE STACK SHOWS
 2" ON HORIZONTAL DRAIN LINE BUT 3" ON
 VERTICAL STACK PLEASE SIZE DRAIN FOR 3"
 ALSO. UNIT "B" UNCHANGED
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-12 Cont ID  
Sent By pkrauss Date 2002-02-12 Time 10:44 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
2002-02-12 00:00:00DENIED
 REFERENCE:FBC-2001 - FHA AMEND-98
 DESIGN MANUAL
  
 1) SHT T1.01 COVER SHEET CALLS FOR
 IRRAGATION SHEETS IR-1/IR-2, NONE
 FOUND.PLEASE SUBMIT IRRIGATION SHEETS.
 2) SHT 10.01 GENERAL NOTES #2 CHANGE
 CODE REFERENCE TO READ FLA. BLDG. CODE
 2001.
 3) SHT P-2 1ST FLOOR/1ST FLOOR (REV),
 "A" CLEANOUT REQUIRED AT CHANGE OF
 DIRECTION GREATER THAN 45 DEGREES. FBC
 SEC 708.3.3.
 4) SHT P-2 2ND FLOOR/2ND FLOOR (REV),
 "A" MINIMUM 1-1/2" WASTE ARM TO KITCHEN
 SINK NOT 1" AS SHOWN. FBC 709.1
 5) SHT P-3 1ST FLOOR/1ST FLOOR (REV),
 "B" CLEANOUT REQUIRED AT CHANGE OF
 DIRECTION GREATER THAN 45 DEGREES. FBC
 SEC 708.3.3.
 6)SHT P-3 2ND FLOOR/2ND FLOOR (REV),
 "B" MINIMUM 1-1/2" WASTE ARM TO
 KITCHEN SINK NOT 1" AS SHOWN. FBC 709.1
 7) SHT P-6 WATER RISER DIAGRAMS TYPICAL
 FOR ALL UNITS. WATER HAMMER ARRESTORS
 SHALL BE LOCATED IN AN "EFFECTIVE
 RANGE" OF ALL QUICK CLOSING VALVES
 (SOLENOID) PLEASE SHOW THESE ON RISER
 DIAGRAMS. FBC SEC 604.9
 8) SHT P-6 WATER RISER DIAGRAM FOR "C"
 UNIT SHOWS AIR CHAMBER. AIR CHAMBERS
 ARE NOT APPROVED, PLEASE REMOVE.
 9) SHT P-6 SANITARY RISER DIAGRAM. W/M
 STACK SHOWS 2" ON HORIZONTAL DRAIN LINE
 BUT 3" ON VERTICAL STACK. PLEASE SIZE
 DRAIN FOR 3" ALSO.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-12 Cont ID  
Sent By pkrauss Date 2002-02-12 Time 12:13 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
2002-02-12 00:00:00PASSED ON PERMIT 01070171 PER SHIRLEY
 GRAHAM.