Plan Review Stops For Permit 02020594 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-03-05 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2003-08-06 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-03-05 00:00:00 | PROVISO:IMPACT FEES MUST BE PAID AND R | | ESIDENT INSPECTOR REQUIRED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-02-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-12 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2002-02-12 |
Time |
10:29 |
Sent To |
|
|
Notes |
2002-02-12 00:00:00 | | | BUILDING:H. PISKURA | | | | FBC 705.1.3, REQUIRES THE FIRE RATED | | WINDOWS, (AND DOORS), TO BE LABELED AND | | LISTED IN ACCORDANCE WITH NFPA 80-95. | | | | THE STORAGE ROOM DOORS SHOWN AS (9) ON | | THE PLAN ARE REQUIRED TO BE RATED [45 | | MIN] SINCE THEY ARE WITHIN THE TEN FEET | | WIDE SHADOW OF PROTECTION REQUIRED BY | | FBC 1006.2.4. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-03-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-07 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-07 |
Time |
12:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-02-13 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-02-13 |
Time |
09:26 |
Sent To |
|
|
Notes |
2002-02-13 00:00:00 | ************ UNSAT ****************** | | | | 1)NOTE: PLEASE SHOW BEDROOM ARC FAULT | | REQ`MENTS PER 210-12 | | | | 2)NOTE: PLEASE NOTE THAT ONE SET HAS | | PAGES 4-5-6 CROSSED OUT? AND OTHERS | | CROSSED OUT AND NEW SHEETS??? | | | | PLEASE SUBMIT NEW SETS WITHNOTE ONE | | ADDRESSED. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2002-02-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-12 |
Time |
12:12 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-02-12 00:00:00 | SEE PERMIT # 01081120 & 01091066 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-03-07 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-03-07 |
Time |
16:50 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-03-07 |
Time |
16:50 |
Sent To |
|
|
Notes |
2002-03-07 00:00:00 | A) THE REQUIRED FIRE ALARM SYSTEM ARE TO | | BE PERMITTED SEPARATELY. PLANS, CUT | | SHEETS, WIRING DIAGRAMS, AND BATTERY | | CALCULATIONS ARE TO BE PROVIDED. MANUAL | | PULL STATIONS AND HORN STROBES ARE TO | | BE PROVIDED THROUGHOUT THE BUILDING. ON | | 3.1.02 WRITER CONTACTED FELIX SIERRA | | WH ADVISED THAT THE FIRE ALARM CONTROL | | PANEL WILL BE LOCATED IN AN EXTERIOR | | STORAGE ROOM. THE FIRE ALARM SYSTEM | | IS TO BE CLASS A OR FULLY ADDRESSABLE. | | B) THE EXIT STAIRS ARE TO BE AT LEAST | | 36" WIDE SINCE OCCUPANT LOADS ARE | | EXPECTED TO BE LESS THAN 50 PERSONS. | | THE MINIMUM HEIGHT OF RISER SHALL BE | | 4", MAXIMUM HEIGHT OF RISER 7", WITH | | THE MINIMUM TREAD DEPTH OF AT LEAST | | 11"S. | | C) ILLUMINATION IS TO BE PROVIDED FOR | | THE MEANS OF EGRESS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-02-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-12 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-02-12 00:00:00 | | | THE BUILDING WAS REVIEWED UNDER THE | | FLORIDA FIRE PREVENTION CODE. | | 1) FIRE HYDRANTS WILL BE RELOCATED TO | | ISLANDS TO PREVENT PROBLEMS WITH ACCESS | | TO THEM. THIS ARRANGEMENT WAS AGREED TO | | BY MR. FELIX SIERRA. | | 2) GENERAL NOTES SECTION SHOULD READ | | FLORIDA FIRE PREVENTION CODE. | | 3) ALL STORAGE ROOMS OUTSIDE OF DWELLING | | UNITS TO BE PROTECTED BY AT LEASAT ONE | | HOUR FIRE SEPARATION OF FIRE SPRINKLERS. | | 4) THE REQUIREMENT FOR A FIRE ALARM | | SYSTEM STILL SEEMS TO BE PRESENT. THE | | TWO EXCEPTIONS TO THIS CODE REQUIREMENT | | DOES NOT APPEAR TO APPLY. PLEASE REVIEW | | CODE REQUIREMENT AND EXCEPTIONS. | | 5) THE INFORMATION PROVIDED FOR THE | | WINDOWS IS CONFUSING. ARE THE EGRESS | | WINDOWS, SELF-CLOSING. PLEASE PROVIDE | | ADDITIONAL DETAILS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096, EXT. 8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-08-06 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2003-08-06 |
Time |
16:12 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2003-08-06 |
Time |
16:12 |
Sent To |
B |
|
Notes |
2003-08-06 00:00:00 | TO HP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-07-30 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2003-07-30 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
alange |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2002-04-04 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-04-04 |
Time |
07:41 |
Rev Time |
1.15 |
Received By |
pkrauss |
Date |
2002-04-04 |
Time |
07:06 |
Sent To |
|
|
Notes |
2002-04-04 00:00:00 | | | PROVISO ON PLAN - | | | | CONDENSATE SHALL TERMINATE A MINIMUM OF | | 12" FROM THE BUILDING STRUCTURE AS PER | | 2001 FBC 1503.4.4. | | | | "FIRE CHASE" FOR THE BATHROOM EXHAUST | | APPROVED BY HAROLD PISKURA. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2002-03-22 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-03-20 |
Time |
15:55 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2002-03-20 |
Time |
15:44 |
Sent To |
|
|
Notes |
2002-03-20 00:00:00 | | | | | AS PER PRIOR REVIEW O.A. SHALL COMPLY | | WITH THE 2001 FBC, MECHANICAL 403.3. | | | | THIS RESUBMITTAL INDICATES THE DESIGN | | FOR OUTSIDE AIR WILL BE TO THE | | EXCEPTION OF 403.2 & TO THE ASHRAE 62 | | ALTERNATIVE 403.5. | | | | ALTERNATE MEANS & METHODS SHALL HAVE A | | PEER REVIEW BY ENGINEERS INDEPENDANT TO | | CMB ENGINEERING FIRM.UPON APPROVAL OF | | PEER REVIEW PLEASE SUBMIT TO NEIL MELICK | | DIRECTOR/BUILDING OFFICAL FOR REVIEW. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2002-02-26 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-26 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2002-02-26 |
Time |
16:16 |
Sent To |
|
|
Notes |
2002-02-26 00:00:00 | | | | | 1.PLAN SHEET M-1 OUTSIDE AIR CALCS., | | A. CALCULATION DOES NOT INCLUDE | | KITCHEN AREA AS REQUIRED PER | | TABLE 403.3. | | NOTE-PLAN SHEETS A5.01 - A5.06 STILL | | REFER TO THE 1997 SBC FOR THE DOORS | | & WINDOWS. | | | | 2.BALANCED AIR RETURN - DEMONSTRATE A | | 3/4" UNDERCUT OF A DOOR COMPLIES | | WITH 601.4 OF THE 2001 FMC IN WHICH | | PRESSURE DIFFERENTIAL ACROSS DOORS | | SHALL BE LIMITED TO 0.001" WC OR | | LESS. | | | | 3.PLAN SHEET M-6 INDICATES AUXILIARY | | DRAIN PAN WITH OVERFLOW PROTECTION | | ON THE UPPER FLOORS ONLY.AS PER | | 2001 FLORIDA BUILDING CODE, MECH | | 307.2.3,ALL COILS ON WHICH | | CONDENSATION WILL OCCUR SHALL HAVE | | AN AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-02-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-12 |
Time |
08:13 |
Rev Time |
5.00 |
Received By |
pkrauss |
Date |
2002-02-12 |
Time |
08:13 |
Sent To |
|
|
Notes |
2002-02-12 00:00:00 | *******************DENIED*************** | | | | 2001 FBC, MECHANICAL | | | | 1.SHOW COMPLIANCE WITH FBC CHAPTER 13 | | SECTION 610.1.ABC.1, ALL AIR | | DISTRIBUTION SYSTEMS SHALL BE SIZED | | & DESIGNED IN ACCORDANCE WITH | | RECOGNIZED ENGINEERING STANDARDS | | SUCH AS ACCA MANUAL D OR OTHER | | STANDARDS. | | | | 2.REVISE ALL PLAN SHEETS TO REFER TO | | THE "2001 FLORIDA BUILDING CODE" | | INSTEAD OF THE 1997 SBC. | | | | 3.PLAN SHEET A7.03 DETAIL #1 - | | AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION FOR ALL UNITS AS PER 2001 | | FBC, MECHANICAL 307.2.3. | | | | 4.PLAN SHEET M-2 - INDICATE DUCT SIZE | | OF BATHROOM EXHAUST. | | | | 5.PLAN SHEET M-3 - CLARIFY DETAIL OF | | 1ST FL (REV), EXHAUST DUCT DOES NOT | | APPEAR TO BE IN A RATED SHAFT. | | | | 6.PROVIDE EXHAUST FAN MODEL # & CFM. | | | | 7.SHOW COMPLIANCE WITH 2001 FBC, MECH | | 403.1 & 601.4, BALANCED AIR RETURN. | | | | 8.PROVIDE OUTSIDE AIR CALCULATIONS AS | | PER 403.3 & TABLE 403.3, REQUIRED | | OUTDOOR VENTILATION AIR FOR PRIVATE | | DWELLING SINGLE AND MULTIPLE LIVING | | AREAS. | | | | 9.HOLD LANDSCAPE BACK 12" FROM | | CONDENSER UNITS. | | | | 10. CONDENSER UNITS NOT TO PLACED UNDER | | THE DRIP EDGE OF THE STRUCTURE. | | | | 11. CONDENSATE SHALL TERMINATE 12" FROM | | THE BUILDING STRUCTURE AS PER 2001 | | FBC 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2002-03-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-03-28 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-03-28 |
Time |
13:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-03-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-03-04 |
Time |
11:25 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2002-03-04 |
Time |
11:25 |
Sent To |
|
|
Notes |
2002-03-04 00:00:00 | DENIED | | REFERENCE: FBC-2001 - FHA-AMEND-98 | | DESIGN MANUAL | | | | 1) FROM PREVIOUS REVIEW - SHT T1.01 | | COVER SHEET CALLS FOR IRRIGATION SHEETS | | IR-1 & IR-2, NONE FOUND. PLEASE SUBMIT | | IRRIGATION SHEETS. | | 2) FROM PREVIOUS REVIEW - #7 WATER RISER | | DIAGRAM TYPICAL OF ALL UNITS. WATER HAM- | | MER ARRESTORS REQUIRED FOR ALL REFRIG. | | ICE MAKERS. PLEASE SHOW ON RISER DIAG. | | 3) FROM PREVIOUS REVIEW - #9 SHT P-6, | | SANT. RISER DIAG. W/MACHINE STACK SHOWS | | 2" ON HORIZONTAL DRAIN LINE BUT 3" ON | | VERTICAL STACK PLEASE SIZE DRAIN FOR 3" | | ALSO. UNIT "B" UNCHANGED | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-02-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-12 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-02-12 00:00:00 | DENIED | | REFERENCE:FBC-2001 - FHA AMEND-98 | | DESIGN MANUAL | | | | 1) SHT T1.01 COVER SHEET CALLS FOR | | IRRAGATION SHEETS IR-1/IR-2, NONE | | FOUND.PLEASE SUBMIT IRRIGATION SHEETS. | | 2) SHT 10.01 GENERAL NOTES #2 CHANGE | | CODE REFERENCE TO READ FLA. BLDG. CODE | | 2001. | | 3) SHT P-2 1ST FLOOR/1ST FLOOR (REV), | | "A" CLEANOUT REQUIRED AT CHANGE OF | | DIRECTION GREATER THAN 45 DEGREES. FBC | | SEC 708.3.3. | | 4) SHT P-2 2ND FLOOR/2ND FLOOR (REV), | | "A" MINIMUM 1-1/2" WASTE ARM TO KITCHEN | | SINK NOT 1" AS SHOWN. FBC 709.1 | | 5) SHT P-3 1ST FLOOR/1ST FLOOR (REV), | | "B" CLEANOUT REQUIRED AT CHANGE OF | | DIRECTION GREATER THAN 45 DEGREES. FBC | | SEC 708.3.3. | | 6)SHT P-3 2ND FLOOR/2ND FLOOR (REV), | | "B" MINIMUM 1-1/2" WASTE ARM TO | | KITCHEN SINK NOT 1" AS SHOWN. FBC 709.1 | | 7) SHT P-6 WATER RISER DIAGRAMS TYPICAL | | FOR ALL UNITS. WATER HAMMER ARRESTORS | | SHALL BE LOCATED IN AN "EFFECTIVE | | RANGE" OF ALL QUICK CLOSING VALVES | | (SOLENOID) PLEASE SHOW THESE ON RISER | | DIAGRAMS. FBC SEC 604.9 | | 8) SHT P-6 WATER RISER DIAGRAM FOR "C" | | UNIT SHOWS AIR CHAMBER. AIR CHAMBERS | | ARE NOT APPROVED, PLEASE REMOVE. | | 9) SHT P-6 SANITARY RISER DIAGRAM. W/M | | STACK SHOWS 2" ON HORIZONTAL DRAIN LINE | | BUT 3" ON VERTICAL STACK. PLEASE SIZE | | DRAIN FOR 3" ALSO. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-02-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-12 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-02-12 00:00:00 | PASSED ON PERMIT 01070171 PER SHIRLEY | | GRAHAM. |
|
|