Plan Review Stops For Permit 02020196 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2002-07-11 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-07-11 |
Time |
12:57 |
Rev Time |
1.50 |
Received By |
jwitmer |
Date |
2002-07-11 |
Time |
12:57 |
Sent To |
|
|
Notes |
2002-07-11 00:00:00 | THIS PERMIT WILL BE ISSUED WITH A BUILD- | | ING PROVISO: | | 1) THE ORIGINAL PLAN CHECK 1997 STANDARD | | BUILDING CODE. | | 2) THE PERMIT APPLICATION AND HISTORY | | REFLECT THE ORIGINAL PLAN CHECK # NOT | | THE MARCH 8TH /2002 APPLIACTION DATE. | | A NEW PERMIT # SHALL BE ISSUED TO RE- | | FLECT THE APPLICATION BEING REVIEWED | | UNDER THE 2001 FLORIDA BUILDING CODE. | | 3) THE SITE SPECIFIC ENGINEERING FOR THE | | DOOR, MULLIONS, SIDELIGHTS & TRANSOM | | ARE WIND ONLY.NEITHER THE DADE COUNTY | | PRODUCT APPROVAL REPORT# 01-0910.09 | | NOR THE ENGINNEERING INDICATE THEY | | ARE TESTED FOR MORE THAN WIND. | | 4) FL BLD CODE 1606.1.4/ 1707.4 & | | 3401.7.2.4 REQUIRE GLAZED UNITS BEING | | REPLACED TO HAVE LARGE MISSLE IMPACT | | RESISTANCE TESTING OR STORM SHUTTER | | PROTECTION HAVING PASSED SUCH PRODUCT | | TESTING. EITHER SBCCI OR DADE COUNTY | | TESTING. | | 5) THERE HAS BEEN NO SUCH REPORT SUBMIT- | | TED, A SEPARATE PERMIT SHALL BE | | REQUIRED FOR STORM SHUTTER BEFORE A | | CERTIFICATE OF COMPLETION SHALL BE | | ISSUED. | | 6) A NEW PERMIT NUMBER SHALL BE ISSUED | | TO REFLECT THE PERMIT APP., REVIEWS | | AND HISTORY OF THIS PERMIT FOR TRACK- | | ING PURPOSES. PERMIT # 02070653. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2002-05-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-05-15 |
Time |
14:09 |
Rev Time |
0.75 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-05-15 00:00:00 | BUILDING PLAN REVIEW | | PERMIT# 02020196 | | 2825 OKEECHOBEE BLVD | | CONT: CARRICK CONSTRUCTION | | TEL: (561) 844-5322 | | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1) ALL OF THE STRUCTURAL COMMENTS HAVE | | BEEN ADDRESSED WITH THE EXCEPTION OF THE | | STOREFRONT SYSTEM. THE PRODUCT APPROVAL | | SUBMITTED IS FOR A PAIR OF DOORS, AND | | THE REPORT INDICATES THAT IT IS LIMITED | | TO THE TEST CONFIGURATION! THE PLANS, | | ELEVATION, INDICATES NOT ONLY A PAIR OF | | DOORS, SIDELIGHTS AS WELL AS A TRANSOM | | ABOVE. EITHER A PRODUCT TESTING REPORT | | WITH TESTING OF THIS CONFIGURATION | | (SBCCI OR DADE COUNTY) OR SITE SPECIFIC | | ENGINEERING. THE ENGINEER THAT DESIGNS | | THE STOREFRONT SYSTEM SIGNS & SEALS THE | | DESIGN, THE ARCHITECT OF RECORD SHALL | | REVIEW AND ATTACH AN AFFADAVIT STATING | | THAT THE ENGINEERED SYSTEM WILL MEET THE | | WIND LOADS REQUIRED BY THIS BUILDING. | | THE SECOND ISSUE IS THAT THE PRODUCT | | APPROVAL SUBMITTED DID NOT MEET THE TEST | | ING REQUIREMENTS FOR LARGE MISSLE IMPACT | | RESISTANCE TESTING. | | THE LAST SUBMITTAL IS FOR SHOP DRAW- | | INGS ONLY!!!!! | | ANY QUESTIONS PLEASE CALL, | | JIM WITMER | | BUILDING PLAN REVIEW | | DEPARTMENT OF CONSTRUCTION SERVICES | | CITY OF WEST PALM BEACH | | (561) 659-8096 EXT. 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-03-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-03-30 |
Time |
09:50 |
Rev Time |
0.50 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-03-30 00:00:00 | BUILDING PLAN REVIEW | | PERMIT 02020196 | | 2825 OKEECHOBEE BLVD | | | | SBC= 1997 STANDARD BUILDING CODE | | | | 1) BUILDING INFORMATION, SHEET A0.0 | | WRONG CODE USE,1997 STANDARD BUILDING | | CODEFOR BUILDING & 1994 STANDARD PLUMBI- | | ING CODE. | | 2) PREVIOUS BUILDING REVIEW A PROVISO | | GIVEN FOR STOREFRONT PRODUCT APPROVAL. | | THE PRODUCT TESTING REPORT PROVIDED DOES | | NOT MEET THIS CONFIGURATION, UNDER LIMIT | | ATIOINS IT IS FOR A SINGLE OR DOUBLE SET | | OF DOORS ONLY. DETAIL 2 OF SHEET 2 | | INDICATES 2 DOORS SIDELITES AS WELL AS | | A TRANSOM. THE REPORT ALSO STATES THAT | | HURRICANE PROTECTION SHALL BE REQUIRED. | | 3) SHEET 4 INDICATES VARIOUS SOFFITS | | BUT NOWHERE DOES IT STATE HOW THE SOFFIT | | FRAMING IS ATTACHED? OR TO WHAT? | | | | 4) PLANS SUBMITTED FOR PLAN REVIEW WERE | | UNDER THE 1997 STANDARD BUILDING CODE! | | **** PLANS SUBMITTED FOR PERMIT APPLICA- | | TION AFTER MARCH 1, 2002 TO BE DESIGNED | | TO THE 2001 FLORIDA BUILDING CODE!!!!!! | | ********2001 FLORIDA BUILDING CODE****** | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 X 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-02-19 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-02-19 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-02-19 00:00:00 | PROVISO:PROVIDE A NOTICE OF | | ACCEPTANCE REPORT AND/OR TESTING FOR | | THE FRONT DOOR FOR WINDLOAD RESISTANCE | | AND | | METHOD OF HURRICANE MISSILE IMPACT | | RESISTANCE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-03-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-25 |
Time |
05:48 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-21 |
Time |
11:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-02-13 |
Time |
06:50 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-02-13 |
Time |
06:40 |
Sent To |
|
|
Notes |
2002-02-13 00:00:00 | *************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT ELECTRICAL | | CODE REFERENCED ON A 0.0 IS INCORRECT, | | PLEASE NOTE WE ARE UNDER THE "99" NEC. | | | | 2)NOTE: PLEASE NOTE MISSING SIGNAGE REQ` | | D PER 600-5. | | | | 3)NOTE: PLEASE NOTE MISSING SHOW WINDOW | | OUTLETS PER 210-62. | | | | 4)NOTE: PLEASE SHOW TRACL LIGHTING CALCS | | PER 220-12B | | | | 5)NOTE: PLEASE CLARIFY LOAD SHOWN FOR | | OUTLETS? PLEASE SHOW # OF OUTLETS AT | | 180VA 220-3. | | | | 6)NOTE: PLEASE SEE ANY FIRE PLAN REVIEW | | COMMENTS. | | | | PLEASE CLARIFY THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ANY QUESTIONS PLEASE | | CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2002-02-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-21 |
Time |
16:07 |
Rev Time |
0.05 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-04-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-04-02 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-04-02 |
Time |
13:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-02-07 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-02-07 |
Time |
16:57 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-02-07 |
Time |
16:57 |
Sent To |
|
|
Notes |
2002-02-07 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED | | IN BUILDING INFORMATION. SHOULD READ | | FLORIDA FIRE PREVENTION CODE, 2000 | | EDITION OF THE LIFE SAFETY CODE. | | 2) ARE THE 2X4 PARABOLIC WITH BATTERY | | BACKUP NIGHTLITES THE SAME AS EMERGENCY | | LIGHTS. | | 3) GENERAL STORAGE AREAS AND CLOSETS | | ARE TO BE PROTECTED BY AT LEAST ONE | | HOUR FIRE RATED ASSEMBLIES WITH C | | LABELED OPENING PROTECTIVES. | | 4) AREA SHOWN AS HATCHED ON THE PLANS | | IS USED FOR WHAT PURPOSE. IF USED FOR | | STORAGE IT MUST BE RATED BY AT LEAST | | ONE HOUR. | | 5) IS THE DOOR IN THE HATCHED AREA | | LABELED AS AN EXIT. | | 6) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2002-05-08 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-05-08 |
Time |
10:13 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-05-08 |
Time |
10:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2002-04-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-04-01 |
Time |
10:42 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2002-04-01 |
Time |
10:42 |
Sent To |
|
|
Notes |
2002-04-01 00:00:00 | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | ON PLANS AS LETTER MAY GET SEPARATED | | FROM PLANS IN THE FIELD. | | | | PLANS NEED TO REFLECT 2001 FLORIDA | | BUILDING CODE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-02-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-21 |
Time |
15:29 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2002-02-21 |
Time |
15:28 |
Sent To |
|
|
Notes |
2002-02-21 00:00:00 | | | PLAN SHEET A0.0 BUILDING INFORMATION - | | SOUTH FLORIDA MECHANICAL CODE, BROWARD | | COUNTY EDITION.PLANS SHALL BE | | DESIGNEDTO EITHER THE 2001 FLORIDA | | BUILDING CODE, MECHANICAL OR THE 1997 | | STANDARD MECHANICAL CODE UNTIL MARCH 1, | | 2002 - AT WHICH TIMES PLANS SHALL BE | | DESIGNED TO THE 2001 FLORIDA BUIDLING | | CODE, MECHANICAL. | | | | PLANS REVIEWED UNDER THE 1997 STANARD | | MECHANICAL CODE. | | | | PROVIDE SIZE AND MATERIAL OF NEW | | DUCTWORK BEING INSTALLED. | | | | PROVIDE OUTSIDE AIR CALCULATIONS AS PER | | ASHRAE 62-89. | | | | PRIOR TO CONNECTING TO ANY EXISTING DUCT | | WORK, CALL FOR AN INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2002-02-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-21 |
Time |
16:07 |
Rev Time |
0.05 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-02-21 00:00:00 | NO PLUMBING PLANS SUBMITTED FOR REVIEW. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2002-02-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-21 |
Time |
16:08 |
Rev Time |
0.05 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|