Plan Review Details - Permit 02020196
Plan Review Stops For Permit 02020196
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-07-11 Cont ID  
Sent By jwitmer Date 2002-07-11 Time 12:57 Rev Time 1.50
Received By jwitmer Date 2002-07-11 Time 12:57 Sent To  
Notes
2002-07-11 00:00:00THIS PERMIT WILL BE ISSUED WITH A BUILD-
 ING PROVISO:
 1) THE ORIGINAL PLAN CHECK 1997 STANDARD
 BUILDING CODE.
 2) THE PERMIT APPLICATION AND HISTORY
 REFLECT THE ORIGINAL PLAN CHECK # NOT
 THE MARCH 8TH /2002 APPLIACTION DATE.
 A NEW PERMIT # SHALL BE ISSUED TO RE-
 FLECT THE APPLICATION BEING REVIEWED
 UNDER THE 2001 FLORIDA BUILDING CODE.
 3) THE SITE SPECIFIC ENGINEERING FOR THE
 DOOR, MULLIONS, SIDELIGHTS & TRANSOM
 ARE WIND ONLY.NEITHER THE DADE COUNTY
 PRODUCT APPROVAL REPORT# 01-0910.09
 NOR THE ENGINNEERING INDICATE THEY
 ARE TESTED FOR MORE THAN WIND.
 4) FL BLD CODE 1606.1.4/ 1707.4 &
 3401.7.2.4 REQUIRE GLAZED UNITS BEING
 REPLACED TO HAVE LARGE MISSLE IMPACT
 RESISTANCE TESTING OR STORM SHUTTER
 PROTECTION HAVING PASSED SUCH PRODUCT
 TESTING. EITHER SBCCI OR DADE COUNTY
 TESTING.
 5) THERE HAS BEEN NO SUCH REPORT SUBMIT-
 TED, A SEPARATE PERMIT SHALL BE
 REQUIRED FOR STORM SHUTTER BEFORE A
 CERTIFICATE OF COMPLETION SHALL BE
 ISSUED.
 6) A NEW PERMIT NUMBER SHALL BE ISSUED
 TO REFLECT THE PERMIT APP., REVIEWS
 AND HISTORY OF THIS PERMIT FOR TRACK-
 ING PURPOSES. PERMIT # 02070653.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-05-15 Cont ID  
Sent By jwitmer Date 2002-05-15 Time 14:09 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2002-05-15 00:00:00BUILDING PLAN REVIEW
 PERMIT# 02020196
 2825 OKEECHOBEE BLVD
 CONT: CARRICK CONSTRUCTION
 TEL: (561) 844-5322
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) ALL OF THE STRUCTURAL COMMENTS HAVE
 BEEN ADDRESSED WITH THE EXCEPTION OF THE
 STOREFRONT SYSTEM. THE PRODUCT APPROVAL
 SUBMITTED IS FOR A PAIR OF DOORS, AND
 THE REPORT INDICATES THAT IT IS LIMITED
 TO THE TEST CONFIGURATION! THE PLANS,
 ELEVATION, INDICATES NOT ONLY A PAIR OF
 DOORS, SIDELIGHTS AS WELL AS A TRANSOM
 ABOVE. EITHER A PRODUCT TESTING REPORT
 WITH TESTING OF THIS CONFIGURATION
 (SBCCI OR DADE COUNTY) OR SITE SPECIFIC
 ENGINEERING. THE ENGINEER THAT DESIGNS
 THE STOREFRONT SYSTEM SIGNS & SEALS THE
 DESIGN, THE ARCHITECT OF RECORD SHALL
 REVIEW AND ATTACH AN AFFADAVIT STATING
 THAT THE ENGINEERED SYSTEM WILL MEET THE
 WIND LOADS REQUIRED BY THIS BUILDING.
 THE SECOND ISSUE IS THAT THE PRODUCT
 APPROVAL SUBMITTED DID NOT MEET THE TEST
 ING REQUIREMENTS FOR LARGE MISSLE IMPACT
 RESISTANCE TESTING.
 THE LAST SUBMITTAL IS FOR SHOP DRAW-
 INGS ONLY!!!!!
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-03-30 Cont ID  
Sent By jwitmer Date 2002-03-30 Time 09:50 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-03-30 00:00:00BUILDING PLAN REVIEW
 PERMIT 02020196
 2825 OKEECHOBEE BLVD
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1) BUILDING INFORMATION, SHEET A0.0
 WRONG CODE USE,1997 STANDARD BUILDING
 CODEFOR BUILDING & 1994 STANDARD PLUMBI-
 ING CODE.
 2) PREVIOUS BUILDING REVIEW A PROVISO
 GIVEN FOR STOREFRONT PRODUCT APPROVAL.
 THE PRODUCT TESTING REPORT PROVIDED DOES
 NOT MEET THIS CONFIGURATION, UNDER LIMIT
 ATIOINS IT IS FOR A SINGLE OR DOUBLE SET
 OF DOORS ONLY. DETAIL 2 OF SHEET 2
 INDICATES 2 DOORS SIDELITES AS WELL AS
 A TRANSOM. THE REPORT ALSO STATES THAT
 HURRICANE PROTECTION SHALL BE REQUIRED.
 3) SHEET 4 INDICATES VARIOUS SOFFITS
 BUT NOWHERE DOES IT STATE HOW THE SOFFIT
 FRAMING IS ATTACHED? OR TO WHAT?
  
 4) PLANS SUBMITTED FOR PLAN REVIEW WERE
 UNDER THE 1997 STANDARD BUILDING CODE!
 **** PLANS SUBMITTED FOR PERMIT APPLICA-
 TION AFTER MARCH 1, 2002 TO BE DESIGNED
 TO THE 2001 FLORIDA BUILDING CODE!!!!!!
 ********2001 FLORIDA BUILDING CODE******
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-02-19 Cont ID  
Sent By hpiskura Date 2002-02-19 Time 09:19 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-02-19 00:00:00PROVISO:PROVIDE A NOTICE OF
 ACCEPTANCE REPORT AND/OR TESTING FOR
 THE FRONT DOOR FOR WINDLOAD RESISTANCE
 AND
 METHOD OF HURRICANE MISSILE IMPACT
 RESISTANCE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-25 Cont ID  
Sent By dpalmer Date 2002-03-25 Time 05:48 Rev Time 0.00
Received By dpalmer Date 2002-03-21 Time 11:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-13 Cont ID  
Sent By dpalmer Date 2002-02-13 Time 06:50 Rev Time 0.00
Received By dpalmer Date 2002-02-13 Time 06:40 Sent To  
Notes
2002-02-13 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ELECTRICAL
 CODE REFERENCED ON A 0.0 IS INCORRECT,
 PLEASE NOTE WE ARE UNDER THE "99" NEC.
  
 2)NOTE: PLEASE NOTE MISSING SIGNAGE REQ`
 D PER 600-5.
  
 3)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 OUTLETS PER 210-62.
  
 4)NOTE: PLEASE SHOW TRACL LIGHTING CALCS
 PER 220-12B
  
 5)NOTE: PLEASE CLARIFY LOAD SHOWN FOR
 OUTLETS? PLEASE SHOW # OF OUTLETS AT
 180VA 220-3.
  
 6)NOTE: PLEASE SEE ANY FIRE PLAN REVIEW
 COMMENTS.
  
 PLEASE CLARIFY THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ANY QUESTIONS PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-02-21 Cont ID  
Sent By pkrauss Date 2002-02-21 Time 16:07 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-04-02 Cont ID  
Sent By mcarsill Date 2002-04-02 Time 13:53 Rev Time 0.00
Received By mcarsill Date 2002-04-02 Time 13:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-07 Cont ID  
Sent By mcarsill Date 2002-02-07 Time 16:57 Rev Time 0.00
Received By mcarsill Date 2002-02-07 Time 16:57 Sent To  
Notes
2002-02-07 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 IN BUILDING INFORMATION. SHOULD READ
 FLORIDA FIRE PREVENTION CODE, 2000
 EDITION OF THE LIFE SAFETY CODE.
 2) ARE THE 2X4 PARABOLIC WITH BATTERY
 BACKUP NIGHTLITES THE SAME AS EMERGENCY
 LIGHTS.
 3) GENERAL STORAGE AREAS AND CLOSETS
 ARE TO BE PROTECTED BY AT LEAST ONE
 HOUR FIRE RATED ASSEMBLIES WITH C
 LABELED OPENING PROTECTIVES.
 4) AREA SHOWN AS HATCHED ON THE PLANS
 IS USED FOR WHAT PURPOSE. IF USED FOR
 STORAGE IT MUST BE RATED BY AT LEAST
 ONE HOUR.
 5) IS THE DOOR IN THE HATCHED AREA
 LABELED AS AN EXIT.
 6) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-05-08 Cont ID  
Sent By pkrauss Date 2002-05-08 Time 10:13 Rev Time 0.35
Received By pkrauss Date 2002-05-08 Time 10:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-04-01 Cont ID  
Sent By pkrauss Date 2002-04-01 Time 10:42 Rev Time 0.40
Received By pkrauss Date 2002-04-01 Time 10:42 Sent To  
Notes
2002-04-01 00:00:00 
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 ON PLANS AS LETTER MAY GET SEPARATED
 FROM PLANS IN THE FIELD.
  
 PLANS NEED TO REFLECT 2001 FLORIDA
 BUILDING CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-21 Cont ID  
Sent By pkrauss Date 2002-02-21 Time 15:29 Rev Time 0.50
Received By pkrauss Date 2002-02-21 Time 15:28 Sent To  
Notes
2002-02-21 00:00:00 
 PLAN SHEET A0.0 BUILDING INFORMATION -
 SOUTH FLORIDA MECHANICAL CODE, BROWARD
 COUNTY EDITION.PLANS SHALL BE
 DESIGNEDTO EITHER THE 2001 FLORIDA
 BUILDING CODE, MECHANICAL OR THE 1997
 STANDARD MECHANICAL CODE UNTIL MARCH 1,
 2002 - AT WHICH TIMES PLANS SHALL BE
 DESIGNED TO THE 2001 FLORIDA BUIDLING
 CODE, MECHANICAL.
  
 PLANS REVIEWED UNDER THE 1997 STANARD
 MECHANICAL CODE.
  
 PROVIDE SIZE AND MATERIAL OF NEW
 DUCTWORK BEING INSTALLED.
  
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 PRIOR TO CONNECTING TO ANY EXISTING DUCT
 WORK, CALL FOR AN INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-02-21 Cont ID  
Sent By pkrauss Date 2002-02-21 Time 16:07 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
2002-02-21 00:00:00NO PLUMBING PLANS SUBMITTED FOR REVIEW.

Review Stop Z ZONING
Rev No 1 Status N Date 2002-02-21 Cont ID  
Sent By pkrauss Date 2002-02-21 Time 16:08 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***