Plan Review Details - Permit 02020068
Plan Review Stops For Permit 02020068 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-02-15 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-02-15 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-02-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-02-12 |
Time |
17:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-02-12 |
Time |
17:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2002-02-15 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-02-15 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-02-06 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-02-06 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-02-06 |
Time |
14:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-03-04 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-03-04 |
Time |
16:50 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2002-03-04 |
Time |
16:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-02-14 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-14 |
Time |
16:29 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2002-02-14 |
Time |
16:23 |
Sent To |
|
|
Notes |
2002-02-14 00:00:00 | *******************DENIED*************** | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | PER ASHRAE 62-89. | | | | 2.CONDENSATE TO COMPLY WITH COUNTYWIDE | | AMENDMENTS 1994 SPC 804.3.(SHALL | | NOT TERMINATE INTO SANITARY). | | | | 3.OVERFLOW PROTECTION - AUXILIARY | | DRAIN LINE SHALL TERNIMATE AT A | | CONSPICUOUS POINT TO SERVE AS AN | | ALARM THAT REGULAR DRAIN IS | | RESTRICTED. | | | | SEPARATE PERMIT REQUIRED FOR ANY HOOD, | | FIRE SUPRESSION, AND WALK-IN | | COOLER/FREEZERS.PLEASE PROVIDE PLANS | | AND MANUFACTURER SUBMITTAL DATA WITH | | PERMIT APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2002-03-26 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-03-26 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-03-26 |
Time |
10:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-03-08 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-03-08 |
Time |
18:52 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-03-08 |
Time |
18:52 |
Sent To |
|
|
Notes |
2002-03-08 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) FROM PREVIOUS REVIEW - WATER HEATER | | SHALL REQUIRE A PERMINATE SHIPS LADDER | | FOR ALL WATER HEATERS ON SHELVES OR | | ABOVE CEILINGS. PLEASE SHOW DETAILS. | | | | 2) FROM PREVIOUS REVIEW - SHTS P1/P2 | | FLOOR PLAN WASTE AND VENT AND SANT RISER | | DIAGRAM, SEPARATE SANITARY AND GREASY | | WASTE LINES REQUIRED. SAMPLE POINT SHALL | | BE OUTSIDE BLDG AND THEN TIE GREASE INTO | | SANITARY AFTER SAMPLE POING. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-02-12 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-02-12 |
Time |
18:48 |
Rev Time |
1.25 |
Received By |
kstevens |
Date |
2002-02-12 |
Time |
18:48 |
Sent To |
|
|
Notes |
2002-02-12 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) SHT A-2 EQUIPMENT SCHED. 21A LISTED | | BUT NOT FOUND ON FLOOR PLAN, PLEASE | | CLAIRFY. | | 2) SHT A-2 EQUIP. SCHED. 34 WATER FILTER | | SHALL MEET NSF REQUIREMENTS. PLEASE FUR- | | NISH MANUFACTURE'S INFORMATION. | | 3) SHT A-2 EQUIP. SCHED. 7 W/HEATER REQ- | | UIRES A PERMINATE SHIPS LADDER TO ASSURE | | READILY ACCESSIBLE. SHOW DETAILS. | | 4) SHT A-3 WATER HEATER SUPPORT DETAIL, | | 1/2" PAN DRAIN SHOWN. 1" MINIMUM DRAIN | | REQUIRED. SPC SEC 507.8.2 | | 5) SHT P-1 FLOOR PLAN WASTE & VENT, SEP- | | ARATE SANITARY AND GREASE LINES REQUIRED | | 6) SHT P-1 GREASE TRAP CALCULATIONS. | | MINIMUM SIZE GREASE TRAP IS 750 GALS. | | GREASE TRAP TO BE SIZED BY ROD COMPO, | | ENVIRONMENTAL COMPLIANCE, (561) 837-4074 | | WASTE ORD. #2938-96 | | 7) BACKFLOW REQUIRED ON WATER SERVICE | | SHALL BE MAX. 4' AFF FOR SERVICE. (SHT | | P-1 KEY NOTE #2). | | 8) SHTS P-1/P-2 GREASE TRAP INSIDE BLDG. | | NOT APPROVED. | | 9) SHT P-2 WASTE & VENT RISER DIAGRAM, | | 3-COMPARTMENT SINK SHALL HAVE TRAPS ON | | EACH COMPARTMENT. | | 10 SHT P-2 WATER RISER DIAGRAM, WATER | | FILTER NOT SHOWN. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2002-02-15 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-02-15 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|