Plan Review Stops For Permit 02011677 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-02-11 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-02-11 |
Time |
07:51 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-02-11 |
Time |
07:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-02-04 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-02-04 |
Time |
12:44 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2002-02-04 |
Time |
12:05 |
Sent To |
|
|
Notes |
2002-02-04 00:00:00 | ****************DENIED!***************** | | 1) ONLY ONE SERVICE DROP PERMITTED AS | | PER 230-2. | | | | 2) NO A.I.C. RATINGS PROVIDED. | | | | 3) GROUNDING ELECTRODE CONDUCTOR AS PER | | 250-66. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | (561) 659-8096 | | EXT.8392 |
|
|
|