Plan Review Details - Permit 02011677
Plan Review Stops For Permit 02011677
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-11 Cont ID  
Sent By btrobaug Date 2002-02-11 Time 07:51 Rev Time 0.00
Received By btrobaug Date 2002-02-11 Time 07:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-04 Cont ID  
Sent By btrobaug Date 2002-02-04 Time 12:44 Rev Time 0.33
Received By btrobaug Date 2002-02-04 Time 12:05 Sent To  
Notes
2002-02-04 00:00:00****************DENIED!*****************
 1) ONLY ONE SERVICE DROP PERMITTED AS
 PER 230-2.
  
 2) NO A.I.C. RATINGS PROVIDED.
  
 3) GROUNDING ELECTRODE CONDUCTOR AS PER
 250-66.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 (561) 659-8096
 EXT.8392