Plan Review Stops For Permit 02011628 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2002-07-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-07-15 |
Time |
17:50 |
Rev Time |
0.50 |
Received By |
jwitmer |
Date |
2002-07-15 |
Time |
17:50 |
Sent To |
|
|
Notes |
2002-07-15 00:00:00 | BUILDING PROVISO: | | REV. # 5 6/21/02 THE REDUCTION OF STAIR | | WELL WALL TO ONE HR., SECOND STORY ONLY, | | 2 HR OCCUPANCY REQUIRED BETWEEN STORAGE | | AND MERCANTILE FIRST FLOOR. | | BUILDING PLAN REVIEW | | JIM WITMER | | (561)659-8096X 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2002-06-04 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-06-04 |
Time |
15:00 |
Rev Time |
2.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-06-04 00:00:00 | *****STORAGE: POSTING OF SAME FLOOR LOAD | | BEFORE C/O, C/C 106.4.2/106.4.3 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2002-04-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-04-30 |
Time |
16:12 |
Rev Time |
1.25 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-04-30 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 02011628 | | 1609 S DIXIE HWY | | CONT: MIKE MOORE | | TEL: 775-3447 | | | | SBC= 1997 STANDARD BUILDING CODE | | | | 1)- PROVIDE (2) CURRENT AND COMPLETE | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | APPROVALS FOR: HURRICANE STOREFRONT | | SYSTEM, ARCHITECT NOTE, STOREFRONT SUB- | | CONTRACTOR SHALL PROVIDE WIND LOAD CALCU | | LATIONS FROM A REGISTERED ENGINEER, TO | | ESTABLISH SIZES AND ANCHORING? | | IS THIS TO BE A SEPERATE PERMIT, OR | | IS THIS INFORMATION TO BE INCLUDED | | UNDER THIS PERMIT? | | | | 2)- ROVIDE 2 CURRENT COPIES OF SIGNED & | | SEALED SURVEYS WITH PROPOSED IMPROVEMENT | | TO BE COMPLETED.THEFRONT AND REAR | | DOORS INDICATE THEY ARE SWINGING OVER | | THE PROPERTY LINE. | | | | 3)- 3203.1 DOORS SHALL NOT OPEN OR | | PROJECT UPON PUBLIC PROPERTY. | | | | 4)- TABLE 704.1 OCCUPANCY SEPERATION | | REQUIREMENTS;MERCANTILE/ STORAGE | | LOW HAZARD 2HRS. INDICATE THE CEILING / | | 2ND FL. ASSEMBLY NUMBER? | | | | 5)- 106.4.3 POSTING OF FLOOR LOADS, IT | | SHALL BE THE OWNER, AGENT TO EMPLOY A | | COMPUTANT DESIGN PROFESSIONAL TO COMPUTE | | THE SAFE ALLOWABLE FLOOR LOADS. ALL | | SUCH COMPUTATIONSSHALL BE ACCOMPANIED | | BY AN AFFIDAVITFROM THE DESIGN PROFES- | | SIONAL STATING THE SAFE FLOOR LOAD. THE | | COMPUTATION & AFFIDAVIT SHALL BE ON FILE | | AS A PERMANENT RECORD OF THE BUILDING | | DEPARTMENT. | | | | ANY QUESTIONS PLEASE CALL, | | JIM WITMER | | BUILDING PLAN REVIEW | | DEPARTMENT OF CONSTRUCTION SERVICES | | CITY OF WEST PALM BEACH | | (561) 659-8096 EXT. 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-03-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-03-26 |
Time |
18:47 |
Rev Time |
0.50 |
Received By |
jwitmer |
Date |
2002-03-26 |
Time |
18:37 |
Sent To |
|
|
Notes |
2002-03-26 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 02011628 | | 1609 S DIXIE | | CONT: MIKE MOORE CONST | | TEL: 775-3447 | | | | SBC= 1997STANDARD BUILDING CODE | | FL ACC CODE= FLORIDA ACCESSIBILITY CODE | | | | 1)- SBC1606.4 PRODUCT APPROVALS SHEET | | A-2 INDICATES THE REMOVAL OF THE EXIST- | | ING STOREFRONT. 2 COPIES EITHER DADE | | COUNTY OR SBCCI REPORT. | | 2)- SBC2405 GLAZING IN HAZARDOUS LOCA- | | TIONS. NEW STOREFRONT DOORS 100A,300A, | | AND 400A. | | 3)- SBC 704.1 HAZARD H-2 LOW HAZARD, | | WHAT TYPE OF MATERIALS TO BE SSTORED? | | A 2 HR FLOOR CEILING RATING SHALL BE | | REQUIRED BETWEEN MERCANTILE / STORAGE. | | SHOW FLOOR/ CEILING UL RATING. | | 4) STORAGE SECOND FLOOR REQUIRES 2 | | MEANS OF EGRESS 1027.1.1. | | 5)- SBC AMEND. 106.4 POSTING OF FLOOR | | LOADS 106.4.2 IT SHALL BE THE OWNER, | | AGENT OF GROUP S AND F OCCUPANCIES TO EM | | PLOY A COMPUTANT ARCHETECT OR ENGINEER | | TO COMPUTE THE SAFE FLOOR ALLOWABLE | | FLOOR LOADING CAPACITY. ALL SUCH COMPUTA | | TIONS SHALL BE ACCOMPANIED BY AN AFFIDAV | | IT FROM THE DESIGN PROFESSIONAL STATING | | THE SAFE FLOOR LOAD. THE COMPUTATIONS & | | AFFIDAVIT SHALL BE ON FILE AS A PERMAN- | | ENT RECORD OF THE BUILDING DEPARTMENT. | | SBC 106.4.3 SIGNS REQUIRED OWNERS RESPON | | CIBILITY TO ENSURE THAT THE SAFE FLOOR | | LOADS SHALL BE. | | 6)- SBC TABLE 1604.1 WHAT IS THE SECOND | | FLOOR DESIGNED TO FOR LIVE LOADS? | | 7) - THE FIRST FLOOR COORIDORS, 500 & | | 600, WHERE DOES THE FLOOR CEILING RATING | | OCCUR AROUND THE FLOORESCENT CEILING | | FIXTURES? | | BUILDING PLAN REVIEW | | JIM WITMER | | (561)659-8096 X 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-02-13 |
Time |
10:59 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2002-02-13 |
Time |
10:59 |
Sent To |
M |
|
Notes |
2002-02-13 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | SBC = STANDARD BUILDING CODE 1997 | | SBC*= STANDARD BUILD'G CODE (CITY AMEND) | | FL ACC CODE = FLORIDA ACCESSIBILITY CODE | | | | 1) UNTIL MARCH 1, 2001 EITHER STANDARD | | BUILDING CODE 1997 OR FLORIDA BUILDING | | CODE 2001 MAY BE USED.NEITHER CODE IS | | REFERENCED ON THE PLANS.STATE WHICH | | CODE THE WORK IS TO BE CONSTRUCTED TO. | | | | 2) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 3) SBC* 1606.4 (FBC 1606.1.4)PRODUCT | | APPROVALS.SUBMIT PRODUCT APPROVALS FOR | | THE NEW STOREFRONTS AND EXTERIOR GLAZED | | DOORS 100A, 200A, 300A AND 400A ON | | S. DIXIE HWY, AND FOR THE NEW STOREFRONT | | LITES ON THE PALM STREET ELEVATION. | | | | 4) SBC 2405 (FBC 2405)GLAZING IN | | HAZARDOUS LOCATIONS.ANNOTATE THE DOOR | | SCHEDULE TO SHOW THE REQUIREMENT FOR | | TEMPERED, OR ALTERNATIVE SAFETY, GLAZING | | IN DOORS 100A, 200A, 300A AND 400A. | | | | 5) FL ACC CODE 4.22 (FBC 11-4.22) | | SHEET A-1, FLOOR PLAN.THE 'TYPICAL | | TOILET ROOM' ELEVATIONS DO NOT SHOW | | SUFFICIENT DIMENSIONS TO ENSURE | | COMPLIANCE WITH FIGURE 29, FOR EXAMPLE, | | DISTANCE BETWEEN THE W.C. AND ADJACENT | | WALL.ALSO, DOOR 401 IS NOT INCLUDED ON | | THE DOOR SCHEDULE. | | | | 6) FL ACC CODE 4.15 (FBC 11-4.15)AN | | ACCESSIBLE DRINKING FOUNTAIN, IN | | COMPLIANCE WITH FIGURE 27, SHALL BE | | PROVIDED IN EACH TENANT SPACE. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
P |
Date |
2002-10-23 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-10-23 |
Time |
13:10 |
Rev Time |
0.25 |
Received By |
btrobaug |
Date |
2002-10-23 |
Time |
12:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2002-09-18 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-09-18 |
Time |
15:03 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2002-08-27 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-08-27 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-08-26 |
Time |
12:33 |
Sent To |
|
|
Notes |
2002-08-27 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | 1} CIRCUITS S2-2,4 & 6 ON SHEET E-1 2ND | | FLOOR ELECTRIC PLAN AREN'T LISTED ON | | SAMECIRCUITS ON THE PANEL SCHEDULE. | | | | 2} PANEL S2 SHOWN AS REVISION #4WAS NOT | | ON REV #4. | | | | 3} LOCATION OF S2 NOT SHOWN ON THE PLANS | | | | 4}PLEASE CORRELATE THE REVISION NUMBERS | | WITH REVISIONS THAT WERE MADE. | | | | 5} THE RISER DIAGRAM ON THE LAST | | REVISION DOES NOT MATCH THE RISER ON | | THIS REVISION (GUTTER LOCATION,# OF | | PANELS,ETC.)YET IS NOT INDICATED AS | | BEING REVISED (CLOUDED) ON THIS DRAWING. | | | | PLEASE CORRECT DRAWINGS TO INDICATE THE | | REVISIONS MADE AND RESUBMIT FOR REVIEW. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2002-06-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-06-10 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-06-10 |
Time |
14:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2002-05-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-05-31 |
Time |
06:32 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-05-31 |
Time |
06:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2002-05-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-05-14 |
Time |
06:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-05-14 |
Time |
06:11 |
Sent To |
|
|
Notes |
2002-05-14 00:00:00 | *************** UNSAT *************** | | | | PLEASE NOTE THAT PLANS ARE COMING BACK | | WITH THE SOME OF THE SAME COMMENTS FROM | | THE FIRST TWO REVIEWS NOT ADDRESSED. | | | | 1)NOTE: PLEASE NOTE FA/FAC 553-802B WITH | | RESPECT TO DESIGN PROFESSIONALS DOCUMENT | | (S). PLANS THAT ARE REJECTED 3 OR MORE | | TIMES WITH THE SAME COMMENTS ARE SUBJECT | | TO A FEE OF FOUR TIMES THE AMOUNT OF THE | | PROPORTION OF THE PERMIT | | FEE ATTRIBUTED TO PLANS REVIEW. | | PLEASE NOTE THAT % OF PERMIT FEE IS | | ABOUT 30%. PLEASE NOTE THAT THIS FEE | | WILL BE ASSESSED IF CORRECTIONS ARE NOT | | MADE THIS TIME AROUND. | | | | 2)NOTE: PLEASE NOTE CONDUCTORS FOR | | RISER DIAGRAM STILL DO NOT MEET 240-3-C | | SEE 75 DEGREE COLUMN/ 110-14. | | | | 3)NOTE: PLEASE NOTE THERE IS STILL NO | | CLARIFICATION FOR EQUIPMENT GROUNDING | | BETWEEN MAIN DISCONNECT AND PANELS AS | | ASKED. | | | | 4)NOTE: PLEASE NOTE LOAD CALCULATIONS | | STILL NOTE SHOWN? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. AS PREVIUOUSLY STATED ON FIRST | | TWO REVIEWS. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. AS OF TODAYS DATE, NO ONE | | HAS CALLED. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2002-03-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-03-25 |
Time |
06:12 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-03-25 |
Time |
06:12 |
Sent To |
|
|
Notes |
2002-03-25 00:00:00 | ****************** UNSAT *************** | | | | PLEASE NOTE THAT NOT ALL NOTES FROM | | FIRST REVIEW WERE ADDRESSED. | | | | 1)NOTE: PLEASE SHOW LOAD CALCAULTIONS, | | NOTHING SHOWN. PLEASE NOTE ALL CONTINUOS | | LOADS NEED TO BE SHOWN AT 125%. 215-3, | | 230-42 ETC. | | | | 2)NOTE: PLEASE NOTE THAT UNIT "A" SHOWS | | PANEL "H" BEING INSIDE UNIT? PLEASE | | CLARIFY IF THIS IS "HOUSE" PANEL AND | | WHY IT IS SHOWN IN UNIT"A". GROUPING | | MAINS.230-72 | | 3)NOTE: PLEASE NOTE THAT PANEL"S" THAT | | IS SHOWN FOR STORAGE AREA DOES NOT | | CORRELATE ON RISER DIAGRAM. PLEASE NOTE | | OTHER METER LOCATION MENTIONS FOR FIRST | | FLOOR STORAGE? ARE THESE FOR POSSIBLE | | FUTURE TENANT SPACE? | | PLEASE NOTE THAT RISER MENTIONS THAT | | THERE WILL BE "MCB" PANELS IN THOSE | | AREAS, PLEASE NOTE GROUPING OF MAINS | | ON PLANS. 230-72 | | | | 4)NOTE: PLEASE CLARIFY "NUMBER OF | | SERVICE DROPS" AS NOTED ON PLANS> PLEASE | | NOTE THAT ONLY ONE SERVICE DROP IS | | PERMITTED UNDER 230-70. PLEASE CLARIFY | | IF THIS NOTE IS MEANT FOR "3" SETS OF | | SERVICE ENTRANCE CONDUCTORS.? | | | | 5)NOTE: PLEASE NOTE THAT MAIN DISCONNECT | | FOR PANEL "S" IS SHOWN AS 200A WITH | | 150A OCP. PLEASE NOTE THAT CONDUCTORS | | TO PANEL ARE ONLY SHOWN AS #6`S?? | | 310-16. | | | | 6)NOTE: PLEASE NOTE THAT SERVICE | | ENTRANCE CONDUCTORS ARE SHOWN AS 3 SETS | | OF 500MCM. PLEASE NOTE PER 310-16/110-14 | | 500MCM IS RATED AT 380A. PLEASE NOTE | | 240-3-C. RATED FOR MAIN. | | | | 7)NOTE: PLEASE CLARIFY MEANS OF EQUIP- | | -MENT GROUNDING BETWEEN MAINS AND PANELS | | . SIZE PER 250-122 | | | | 8)NOTE: PLEASE NOTE MISSING MAIN FOR | | PANEL"A". 230-72. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-02-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-02-06 |
Time |
20:43 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-02-06 |
Time |
20:40 |
Sent To |
|
|
Notes |
2002-02-06 00:00:00 | ***************** UNSAT ************ | | | | 1)NOTE: PLEASE NOTE THAT ALL CIRCUITING | | NEEDS TO BE SHOWN ON PLANS AND CORRELATE | | WITH A PANEL SCHEDULE. | | | | 2)NOTE: PLEASE NOTE THAT PLANS NEED TO | | BE COMPLETE FOR STORAGE AREA AND SECOND | | FLOOR. | | | | 3)NOTE: PLEASE NOTE FIRE REVIEW COMMENTS | | AND NOTE THAT "GARAGE" STORAGE NEEDS TO | | BE CLARIFIED. | | | | 4)NOTE: PLEASE NOTE NO LOAD CALCULATIONS | | WERE SUBMITTED.215-5 | | | | 5)NOTE: PLEASE NOTE THAT RISER DIAGRAM | | SHOWS 3-#10`S TO 150A PANEL? MISPRINT? | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 7)NOTE: PLEASE NOTE THAT NO GROUNDING | | ELECTRODE SYSTEM IS SHOWN.215-5/250 | | | | 8)NOTE: PLEASE CLARIFY MAINS NOT SHOWN | | FOR FIRST FLOOR AND SECOND FLOOR STORAGE | | AREAS.?? PANELS? PLEASE NOTE GROUPING | | OF MAINS PER 230-72. | | | | 9)NOTE: PLEASE NOTE THAT FIRST FLOOR | | STORAGE SHOWS ELECTRICAL BUT NO PANEL | | | | 10)NOTE: PLEASE NOTE MISSING SHOW WINDOW | | OUTLETS PER 210-62 | | | | 11)NOTE: PLEASE NOTE MISSING SIGN PER | | 600-5. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW. | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2002-05-17 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-05-17 |
Time |
12:56 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-05-17 |
Time |
12:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2002-03-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-03-20 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-03-20 |
Time |
10:03 |
Sent To |
|
|
Notes |
2002-03-20 00:00:00 | A) THE TENANT DATA BOX INDICATES A | | STORAGE OCCUPANCY OF 5,016 SQUARE | | FEET. IT ALSO INDICATES THAT THE | | SECOND FLOOR STORAGE OCCUPANCY (FUTURE) | | IS 11,322 SQUARE FEET. PLEASE INDICATE | | THE TOTAL SQUARE FEET FOR THE | | BUILDING. DOES THE MEAN SQUARE FEET | | OF BOTH FLOORS 22,644 SQUARE FEET. | | WHAT IS THE TENANT SEPARATION BETWEEN | | THE FIRST FLOOR MECANTILE AND THE | | SECOND FLOOR STORAGE. THIS OFFICE IS | | REQUESTING A SECTION VEIW OF THE | | BUILDING FROM FRONT TO BACK. THIS | | OFFICE IS ALSO UNSURE HOW EXITING | | IS ACCOMPLISHED FROM THE SECOND FLOOR | | STORAGE AREA. FUTURE OR NOT THE | | EXITING MUST BE CLARIFIED NOW SO | | EXITING AND ANY FIRE PROTECTION | | PRESCRIPTIVE CODE REQUIREMENTS BE | | CAN BE MET. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-02-06 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-02-06 |
Time |
09:02 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-02-06 |
Time |
09:02 |
Sent To |
|
|
Notes |
2002-02-06 00:00:00 | 1) PLEASE INDICATE OCCUPANCY TYPES FOR | | TENANT SPACES A,B,C AND D. | | 2) PLEASE INDICATE INTERIOR FINISHES | | FOR WALLS AND CEILINGS. | | 3) DOORS 200B AND 300B SWING TO FAR INTO | | THE CORRIDORS 500 AND 600. | | 4) PLEASE INDICATE ON THE PLANS | | LOCATIONS OF EMERGENCY LIGHTING | | EQUIPMENT. | | 5) MORE DETAILS WILL BE NEEDED WITH | | REGARDS TO EXITING, STORAGE ARRANGEMENTS | | SECOND FLOOR AREA OF FUTURE LOW HAZARD | | STORAGE OCCUPANCY. | | 6) PLEASE INDICATE ON PLANS IF THE | | BUILDING IS SPRINKLER PROTECTED OR NOT. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2002-05-08 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-05-08 |
Time |
09:47 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-05-08 |
Time |
09:47 |
Sent To |
|
|
Notes |
2002-05-08 00:00:00 | | | NO MECHANICAL PLANS SUBMITTED FOR | | REVIEW.PLEASE PROVIDE PLANS WITH | | MECHANICAL PERMIT APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2002-02-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-03-26 |
Time |
18:34 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2002-02-14 |
Time |
10:46 |
Sent To |
|
|
Notes |
2002-02-14 00:00:00 | | | | | NO MECHANICAL PLANS SUBMITTED FOR | | REVIEW.PLEASE PROVIDE PLANS WITH | | MECHANICAL PERMIT APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT.8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2002-06-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-06-10 |
Time |
12:14 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-06-10 |
Time |
12:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2002-05-24 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-24 |
Time |
12:27 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-24 |
Time |
12:27 |
Sent To |
|
|
Notes |
2002-05-24 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) SHT MP-2 WATER RISER DIAGRAM - WATER | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | FIXTURES IN AN "EFFECTIVE RANGE" -NOT- | | AT TOP OF DROPS AS SHOWN. PLEASE CHANGE | | PLANS | | 2) SHT A-1 DRINKING FOUNTAINS SHALL | | COMPLY WITH SEC 4.15. PLEASE PROVIDE | | DETAILS WITH 4.25.2 SPOUT HEIGHT, 4.15.5 | | CLEAR FLOOR SPACE, & 4.1.3(10) PROVIDE | | FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | STOOPING. (HI/LOW D.F OR CUP DISPENSER) | | 3) SHT A-1 STORAGE AREAS SHALL HAVE ONE | | EACH MALE AND FEMALE TOILET R00MS FOR | | EACH FLOOR PER OCCUPANT LOAD GIVEN. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2002-04-19 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-04-19 |
Time |
08:02 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-04-19 |
Time |
08:02 |
Sent To |
|
|
Notes |
2002-04-19 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) FROM PREVIOUS REVIEW - SHT A-1 EXIST- | | ING TOILET ROOM AT NORTH WEST CORNER OF | | STORAGE AREA. IS THIS TOILET ROOM HDCP | | ACCESSIBLE, AND CAN IT BE ACCESSED FROM | | THE STORAGE AREA? | | 2) TO CALCULATE MINIMUM FACILITIES FOR | | STORAGE AREAS,(FIRST & SECOND FLOOR), WE | | NEED TO KNOW THE NUMBER OF PEOPLE WORK- | | ING PER SHIFT IN STORAGE AREAS. | | 3) SHT ME-2 WATER HAMMER ARRESTORS ARE | | LOCATED AT TOP OF DROP NOT NEAR FIXTURES | | IN AN "EFFECTIVE RANGE" AS REQUESTED IN | | PREVIOUS REVIEW. | | 4) RPZ BACKFLOW REQUIRED ON WATER SERV- | | ICE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-02-12 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-02-12 |
Time |
09:33 |
Rev Time |
1.33 |
Received By |
kstevens |
Date |
2002-02-12 |
Time |
09:32 |
Sent To |
|
|
Notes |
2002-02-12 00:00:00 | DENIED | | | | 1) PLEASE INDICATE WHICH CODE THIS IS | | DESIGNED FOR. | | 2) SHT A-1 PLEASE PROVIDE SQUARE FOOTAGE | | FOR ALL TENANT SPACES AND FOR STORAGE | | AREA. | | 3) SHT A-1 IS EXISTING TOILET ROOM AT | | NORTH WEST CORNER OF STORAGE AREA HDCP | | ACCESSIBLE, AND CAN IT BE ACCESSED FROM | | STORAGE AREA? | | 4) SHT A-1 PLEASE GIVE OCCUPANCY OF EACH | | TENANT SPACE. | | 5) SHT A-1 TOILET ROOM DETAIL, PLEASE | | INDICATE THAT W/C SHALL BE 1'6" TO | | CENTER AND LAV SHALL BE 1'3" TO CENTER. | | 6) SHT ME-2 SANT RISER ISOMETRIC SHOWS | | 2" AT TIE IN TO EXISTING. MINIMUM 4" IS | | REQUIRED FOR STANDARD CODE AND 3" FOR | | FLA. BUILDING CODE 2001. | | 7) SHT ME-2 PLEASE PROVIDE A WATER RISER | | DIAGRAM. SHOW LOCATION OF WATER HAMMER | | ARRESTORS NEAR FIXTURES NOT AT TOP OF | | DROPS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|