Plan Review Details - Permit 02011628
Plan Review Stops For Permit 02011628
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-07-15 Cont ID  
Sent By jwitmer Date 2002-07-15 Time 17:50 Rev Time 0.50
Received By jwitmer Date 2002-07-15 Time 17:50 Sent To  
Notes
2002-07-15 00:00:00BUILDING PROVISO:
 REV. # 5 6/21/02 THE REDUCTION OF STAIR
 WELL WALL TO ONE HR., SECOND STORY ONLY,
 2 HR OCCUPANCY REQUIRED BETWEEN STORAGE
 AND MERCANTILE FIRST FLOOR.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-06-04 Cont ID  
Sent By jwitmer Date 2002-06-04 Time 15:00 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-06-04 00:00:00*****STORAGE: POSTING OF SAME FLOOR LOAD
 BEFORE C/O, C/C 106.4.2/106.4.3

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-04-30 Cont ID  
Sent By jwitmer Date 2002-04-30 Time 16:12 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-30 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02011628
 1609 S DIXIE HWY
 CONT: MIKE MOORE
 TEL: 775-3447
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1)- PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR: HURRICANE STOREFRONT
 SYSTEM, ARCHITECT NOTE, STOREFRONT SUB-
 CONTRACTOR SHALL PROVIDE WIND LOAD CALCU
 LATIONS FROM A REGISTERED ENGINEER, TO
 ESTABLISH SIZES AND ANCHORING?
 IS THIS TO BE A SEPERATE PERMIT, OR
 IS THIS INFORMATION TO BE INCLUDED
 UNDER THIS PERMIT?
  
 2)- ROVIDE 2 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS WITH PROPOSED IMPROVEMENT
 TO BE COMPLETED.THEFRONT AND REAR
 DOORS INDICATE THEY ARE SWINGING OVER
 THE PROPERTY LINE.
  
 3)- 3203.1 DOORS SHALL NOT OPEN OR
 PROJECT UPON PUBLIC PROPERTY.
  
 4)- TABLE 704.1 OCCUPANCY SEPERATION
 REQUIREMENTS;MERCANTILE/ STORAGE
 LOW HAZARD 2HRS. INDICATE THE CEILING /
 2ND FL. ASSEMBLY NUMBER?
  
 5)- 106.4.3 POSTING OF FLOOR LOADS, IT
 SHALL BE THE OWNER, AGENT TO EMPLOY A
 COMPUTANT DESIGN PROFESSIONAL TO COMPUTE
 THE SAFE ALLOWABLE FLOOR LOADS. ALL
 SUCH COMPUTATIONSSHALL BE ACCOMPANIED
 BY AN AFFIDAVITFROM THE DESIGN PROFES-
 SIONAL STATING THE SAFE FLOOR LOAD. THE
 COMPUTATION & AFFIDAVIT SHALL BE ON FILE
 AS A PERMANENT RECORD OF THE BUILDING
 DEPARTMENT.
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-03-26 Cont ID  
Sent By jwitmer Date 2002-03-26 Time 18:47 Rev Time 0.50
Received By jwitmer Date 2002-03-26 Time 18:37 Sent To  
Notes
2002-03-26 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02011628
 1609 S DIXIE
 CONT: MIKE MOORE CONST
 TEL: 775-3447
  
 SBC= 1997STANDARD BUILDING CODE
 FL ACC CODE= FLORIDA ACCESSIBILITY CODE
  
 1)- SBC1606.4 PRODUCT APPROVALS SHEET
 A-2 INDICATES THE REMOVAL OF THE EXIST-
 ING STOREFRONT. 2 COPIES EITHER DADE
 COUNTY OR SBCCI REPORT.
 2)- SBC2405 GLAZING IN HAZARDOUS LOCA-
 TIONS. NEW STOREFRONT DOORS 100A,300A,
 AND 400A.
 3)- SBC 704.1 HAZARD H-2 LOW HAZARD,
 WHAT TYPE OF MATERIALS TO BE SSTORED?
 A 2 HR FLOOR CEILING RATING SHALL BE
 REQUIRED BETWEEN MERCANTILE / STORAGE.
 SHOW FLOOR/ CEILING UL RATING.
 4) STORAGE SECOND FLOOR REQUIRES 2
 MEANS OF EGRESS 1027.1.1.
 5)- SBC AMEND. 106.4 POSTING OF FLOOR
 LOADS 106.4.2 IT SHALL BE THE OWNER,
 AGENT OF GROUP S AND F OCCUPANCIES TO EM
 PLOY A COMPUTANT ARCHETECT OR ENGINEER
 TO COMPUTE THE SAFE FLOOR ALLOWABLE
 FLOOR LOADING CAPACITY. ALL SUCH COMPUTA
 TIONS SHALL BE ACCOMPANIED BY AN AFFIDAV
 IT FROM THE DESIGN PROFESSIONAL STATING
 THE SAFE FLOOR LOAD. THE COMPUTATIONS &
 AFFIDAVIT SHALL BE ON FILE AS A PERMAN-
 ENT RECORD OF THE BUILDING DEPARTMENT.
 SBC 106.4.3 SIGNS REQUIRED OWNERS RESPON
 CIBILITY TO ENSURE THAT THE SAFE FLOOR
 LOADS SHALL BE.
 6)- SBC TABLE 1604.1 WHAT IS THE SECOND
 FLOOR DESIGNED TO FOR LIVE LOADS?
 7) - THE FIRST FLOOR COORIDORS, 500 &
 600, WHERE DOES THE FLOOR CEILING RATING
 OCCUR AROUND THE FLOORESCENT CEILING
 FIXTURES?
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-13 Cont ID  
Sent By rbrown Date 2002-02-13 Time 10:59 Rev Time 0.00
Received By jwitmer Date 2002-02-13 Time 10:59 Sent To M
Notes
2002-02-13 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) UNTIL MARCH 1, 2001 EITHER STANDARD
 BUILDING CODE 1997 OR FLORIDA BUILDING
 CODE 2001 MAY BE USED.NEITHER CODE IS
 REFERENCED ON THE PLANS.STATE WHICH
 CODE THE WORK IS TO BE CONSTRUCTED TO.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SBC* 1606.4 (FBC 1606.1.4)PRODUCT
 APPROVALS.SUBMIT PRODUCT APPROVALS FOR
 THE NEW STOREFRONTS AND EXTERIOR GLAZED
 DOORS 100A, 200A, 300A AND 400A ON
 S. DIXIE HWY, AND FOR THE NEW STOREFRONT
 LITES ON THE PALM STREET ELEVATION.
  
 4) SBC 2405 (FBC 2405)GLAZING IN
 HAZARDOUS LOCATIONS.ANNOTATE THE DOOR
 SCHEDULE TO SHOW THE REQUIREMENT FOR
 TEMPERED, OR ALTERNATIVE SAFETY, GLAZING
 IN DOORS 100A, 200A, 300A AND 400A.
  
 5) FL ACC CODE 4.22 (FBC 11-4.22)
 SHEET A-1, FLOOR PLAN.THE 'TYPICAL
 TOILET ROOM' ELEVATIONS DO NOT SHOW
 SUFFICIENT DIMENSIONS TO ENSURE
 COMPLIANCE WITH FIGURE 29, FOR EXAMPLE,
 DISTANCE BETWEEN THE W.C. AND ADJACENT
 WALL.ALSO, DOOR 401 IS NOT INCLUDED ON
 THE DOOR SCHEDULE.
  
 6) FL ACC CODE 4.15 (FBC 11-4.15)AN
 ACCESSIBLE DRINKING FOUNTAIN, IN
 COMPLIANCE WITH FIGURE 27, SHALL BE
 PROVIDED IN EACH TENANT SPACE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2002-10-23 Cont ID  
Sent By btrobaug Date 2002-10-23 Time 13:10 Rev Time 0.25
Received By btrobaug Date 2002-10-23 Time 12:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2002-09-18 Cont ID  
Sent By btrobaug Date 2002-09-18 Time 15:03 Rev Time 1.00
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2002-08-27 Cont ID  
Sent By btrobaug Date 2002-08-27 Time 14:40 Rev Time 0.00
Received By btrobaug Date 2002-08-26 Time 12:33 Sent To  
Notes
2002-08-27 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} CIRCUITS S2-2,4 & 6 ON SHEET E-1 2ND
 FLOOR ELECTRIC PLAN AREN'T LISTED ON
 SAMECIRCUITS ON THE PANEL SCHEDULE.
  
 2} PANEL S2 SHOWN AS REVISION #4WAS NOT
 ON REV #4.
  
 3} LOCATION OF S2 NOT SHOWN ON THE PLANS
  
 4}PLEASE CORRELATE THE REVISION NUMBERS
 WITH REVISIONS THAT WERE MADE.
  
 5} THE RISER DIAGRAM ON THE LAST
 REVISION DOES NOT MATCH THE RISER ON
 THIS REVISION (GUTTER LOCATION,# OF
 PANELS,ETC.)YET IS NOT INDICATED AS
 BEING REVISED (CLOUDED) ON THIS DRAWING.
  
 PLEASE CORRECT DRAWINGS TO INDICATE THE
 REVISIONS MADE AND RESUBMIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-06-10 Cont ID  
Sent By dpalmer Date 2002-06-10 Time 14:21 Rev Time 0.00
Received By dpalmer Date 2002-06-10 Time 14:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-05-31 Cont ID  
Sent By dpalmer Date 2002-05-31 Time 06:32 Rev Time 0.00
Received By dpalmer Date 2002-05-31 Time 06:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-05-14 Cont ID  
Sent By dpalmer Date 2002-05-14 Time 06:11 Rev Time 0.00
Received By dpalmer Date 2002-05-14 Time 06:11 Sent To  
Notes
2002-05-14 00:00:00*************** UNSAT ***************
  
 PLEASE NOTE THAT PLANS ARE COMING BACK
 WITH THE SOME OF THE SAME COMMENTS FROM
 THE FIRST TWO REVIEWS NOT ADDRESSED.
  
 1)NOTE: PLEASE NOTE FA/FAC 553-802B WITH
 RESPECT TO DESIGN PROFESSIONALS DOCUMENT
 (S). PLANS THAT ARE REJECTED 3 OR MORE
 TIMES WITH THE SAME COMMENTS ARE SUBJECT
 TO A FEE OF FOUR TIMES THE AMOUNT OF THE
 PROPORTION OF THE PERMIT
 FEE ATTRIBUTED TO PLANS REVIEW.
 PLEASE NOTE THAT % OF PERMIT FEE IS
 ABOUT 30%. PLEASE NOTE THAT THIS FEE
 WILL BE ASSESSED IF CORRECTIONS ARE NOT
 MADE THIS TIME AROUND.
  
 2)NOTE: PLEASE NOTE CONDUCTORS FOR
 RISER DIAGRAM STILL DO NOT MEET 240-3-C
 SEE 75 DEGREE COLUMN/ 110-14.
  
 3)NOTE: PLEASE NOTE THERE IS STILL NO
 CLARIFICATION FOR EQUIPMENT GROUNDING
 BETWEEN MAIN DISCONNECT AND PANELS AS
 ASKED.
  
 4)NOTE: PLEASE NOTE LOAD CALCULATIONS
 STILL NOTE SHOWN?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. AS PREVIUOUSLY STATED ON FIRST
 TWO REVIEWS. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. AS OF TODAYS DATE, NO ONE
 HAS CALLED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-03-25 Cont ID  
Sent By dpalmer Date 2002-03-25 Time 06:12 Rev Time 0.00
Received By dpalmer Date 2002-03-25 Time 06:12 Sent To  
Notes
2002-03-25 00:00:00****************** UNSAT ***************
  
 PLEASE NOTE THAT NOT ALL NOTES FROM
 FIRST REVIEW WERE ADDRESSED.
  
 1)NOTE: PLEASE SHOW LOAD CALCAULTIONS,
 NOTHING SHOWN. PLEASE NOTE ALL CONTINUOS
 LOADS NEED TO BE SHOWN AT 125%. 215-3,
 230-42 ETC.
  
 2)NOTE: PLEASE NOTE THAT UNIT "A" SHOWS
 PANEL "H" BEING INSIDE UNIT? PLEASE
 CLARIFY IF THIS IS "HOUSE" PANEL AND
 WHY IT IS SHOWN IN UNIT"A". GROUPING
 MAINS.230-72
 3)NOTE: PLEASE NOTE THAT PANEL"S" THAT
 IS SHOWN FOR STORAGE AREA DOES NOT
 CORRELATE ON RISER DIAGRAM. PLEASE NOTE
 OTHER METER LOCATION MENTIONS FOR FIRST
 FLOOR STORAGE? ARE THESE FOR POSSIBLE
 FUTURE TENANT SPACE?
 PLEASE NOTE THAT RISER MENTIONS THAT
 THERE WILL BE "MCB" PANELS IN THOSE
 AREAS, PLEASE NOTE GROUPING OF MAINS
 ON PLANS. 230-72
  
 4)NOTE: PLEASE CLARIFY "NUMBER OF
 SERVICE DROPS" AS NOTED ON PLANS> PLEASE
 NOTE THAT ONLY ONE SERVICE DROP IS
 PERMITTED UNDER 230-70. PLEASE CLARIFY
 IF THIS NOTE IS MEANT FOR "3" SETS OF
 SERVICE ENTRANCE CONDUCTORS.?
  
 5)NOTE: PLEASE NOTE THAT MAIN DISCONNECT
 FOR PANEL "S" IS SHOWN AS 200A WITH
 150A OCP. PLEASE NOTE THAT CONDUCTORS
 TO PANEL ARE ONLY SHOWN AS #6`S??
 310-16.
  
 6)NOTE: PLEASE NOTE THAT SERVICE
 ENTRANCE CONDUCTORS ARE SHOWN AS 3 SETS
 OF 500MCM. PLEASE NOTE PER 310-16/110-14
 500MCM IS RATED AT 380A. PLEASE NOTE
 240-3-C. RATED FOR MAIN.
  
 7)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDING BETWEEN MAINS AND PANELS
 . SIZE PER 250-122
  
 8)NOTE: PLEASE NOTE MISSING MAIN FOR
 PANEL"A". 230-72.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By dpalmer Date 2002-02-06 Time 20:43 Rev Time 0.00
Received By dpalmer Date 2002-02-06 Time 20:40 Sent To  
Notes
2002-02-06 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT ALL CIRCUITING
 NEEDS TO BE SHOWN ON PLANS AND CORRELATE
 WITH A PANEL SCHEDULE.
  
 2)NOTE: PLEASE NOTE THAT PLANS NEED TO
 BE COMPLETE FOR STORAGE AREA AND SECOND
 FLOOR.
  
 3)NOTE: PLEASE NOTE FIRE REVIEW COMMENTS
 AND NOTE THAT "GARAGE" STORAGE NEEDS TO
 BE CLARIFIED.
  
 4)NOTE: PLEASE NOTE NO LOAD CALCULATIONS
 WERE SUBMITTED.215-5
  
 5)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS 3-#10`S TO 150A PANEL? MISPRINT?
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7)NOTE: PLEASE NOTE THAT NO GROUNDING
 ELECTRODE SYSTEM IS SHOWN.215-5/250
  
 8)NOTE: PLEASE CLARIFY MAINS NOT SHOWN
 FOR FIRST FLOOR AND SECOND FLOOR STORAGE
 AREAS.?? PANELS? PLEASE NOTE GROUPING
 OF MAINS PER 230-72.
  
 9)NOTE: PLEASE NOTE THAT FIRST FLOOR
 STORAGE SHOWS ELECTRICAL BUT NO PANEL
  
 10)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 OUTLETS PER 210-62
  
 11)NOTE: PLEASE NOTE MISSING SIGN PER
 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-05-17 Cont ID  
Sent By mcarsill Date 2002-05-17 Time 12:56 Rev Time 0.00
Received By mcarsill Date 2002-05-17 Time 12:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-03-20 Cont ID  
Sent By mcarsill Date 2002-03-20 Time 10:04 Rev Time 0.00
Received By mcarsill Date 2002-03-20 Time 10:03 Sent To  
Notes
2002-03-20 00:00:00A) THE TENANT DATA BOX INDICATES A
 STORAGE OCCUPANCY OF 5,016 SQUARE
 FEET. IT ALSO INDICATES THAT THE
 SECOND FLOOR STORAGE OCCUPANCY (FUTURE)
 IS 11,322 SQUARE FEET. PLEASE INDICATE
 THE TOTAL SQUARE FEET FOR THE
 BUILDING. DOES THE MEAN SQUARE FEET
 OF BOTH FLOORS 22,644 SQUARE FEET.
 WHAT IS THE TENANT SEPARATION BETWEEN
 THE FIRST FLOOR MECANTILE AND THE
 SECOND FLOOR STORAGE. THIS OFFICE IS
 REQUESTING A SECTION VEIW OF THE
 BUILDING FROM FRONT TO BACK. THIS
 OFFICE IS ALSO UNSURE HOW EXITING
 IS ACCOMPLISHED FROM THE SECOND FLOOR
 STORAGE AREA. FUTURE OR NOT THE
 EXITING MUST BE CLARIFIED NOW SO
 EXITING AND ANY FIRE PROTECTION
 PRESCRIPTIVE CODE REQUIREMENTS BE
 CAN BE MET.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By mcarsill Date 2002-02-06 Time 09:02 Rev Time 0.00
Received By mcarsill Date 2002-02-06 Time 09:02 Sent To  
Notes
2002-02-06 00:00:001) PLEASE INDICATE OCCUPANCY TYPES FOR
 TENANT SPACES A,B,C AND D.
 2) PLEASE INDICATE INTERIOR FINISHES
 FOR WALLS AND CEILINGS.
 3) DOORS 200B AND 300B SWING TO FAR INTO
 THE CORRIDORS 500 AND 600.
 4) PLEASE INDICATE ON THE PLANS
 LOCATIONS OF EMERGENCY LIGHTING
 EQUIPMENT.
 5) MORE DETAILS WILL BE NEEDED WITH
 REGARDS TO EXITING, STORAGE ARRANGEMENTS
 SECOND FLOOR AREA OF FUTURE LOW HAZARD
 STORAGE OCCUPANCY.
 6) PLEASE INDICATE ON PLANS IF THE
 BUILDING IS SPRINKLER PROTECTED OR NOT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2002-05-08 Cont ID  
Sent By pkrauss Date 2002-05-08 Time 09:47 Rev Time 0.35
Received By pkrauss Date 2002-05-08 Time 09:47 Sent To  
Notes
2002-05-08 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-02-14 Cont ID  
Sent By jwitmer Date 2002-03-26 Time 18:34 Rev Time 0.25
Received By pkrauss Date 2002-02-14 Time 10:46 Sent To  
Notes
2002-02-14 00:00:00 
  
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT.8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-06-10 Cont ID  
Sent By kstevens Date 2002-06-10 Time 12:14 Rev Time 0.00
Received By kstevens Date 2002-06-10 Time 12:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-05-24 Cont ID  
Sent By kstevens Date 2002-05-24 Time 12:27 Rev Time 0.00
Received By kstevens Date 2002-05-24 Time 12:27 Sent To  
Notes
2002-05-24 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT MP-2 WATER RISER DIAGRAM - WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 FIXTURES IN AN "EFFECTIVE RANGE" -NOT-
 AT TOP OF DROPS AS SHOWN. PLEASE CHANGE
 PLANS
 2) SHT A-1 DRINKING FOUNTAINS SHALL
 COMPLY WITH SEC 4.15. PLEASE PROVIDE
 DETAILS WITH 4.25.2 SPOUT HEIGHT, 4.15.5
 CLEAR FLOOR SPACE, & 4.1.3(10) PROVIDE
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. (HI/LOW D.F OR CUP DISPENSER)
 3) SHT A-1 STORAGE AREAS SHALL HAVE ONE
 EACH MALE AND FEMALE TOILET R00MS FOR
 EACH FLOOR PER OCCUPANT LOAD GIVEN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-04-19 Cont ID  
Sent By kstevens Date 2002-04-19 Time 08:02 Rev Time 0.00
Received By kstevens Date 2002-04-19 Time 08:02 Sent To  
Notes
2002-04-19 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) FROM PREVIOUS REVIEW - SHT A-1 EXIST-
 ING TOILET ROOM AT NORTH WEST CORNER OF
 STORAGE AREA. IS THIS TOILET ROOM HDCP
 ACCESSIBLE, AND CAN IT BE ACCESSED FROM
 THE STORAGE AREA?
 2) TO CALCULATE MINIMUM FACILITIES FOR
 STORAGE AREAS,(FIRST & SECOND FLOOR), WE
 NEED TO KNOW THE NUMBER OF PEOPLE WORK-
 ING PER SHIFT IN STORAGE AREAS.
 3) SHT ME-2 WATER HAMMER ARRESTORS ARE
 LOCATED AT TOP OF DROP NOT NEAR FIXTURES
 IN AN "EFFECTIVE RANGE" AS REQUESTED IN
 PREVIOUS REVIEW.
 4) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-12 Cont ID  
Sent By kstevens Date 2002-02-12 Time 09:33 Rev Time 1.33
Received By kstevens Date 2002-02-12 Time 09:32 Sent To  
Notes
2002-02-12 00:00:00DENIED
  
 1) PLEASE INDICATE WHICH CODE THIS IS
 DESIGNED FOR.
 2) SHT A-1 PLEASE PROVIDE SQUARE FOOTAGE
 FOR ALL TENANT SPACES AND FOR STORAGE
 AREA.
 3) SHT A-1 IS EXISTING TOILET ROOM AT
 NORTH WEST CORNER OF STORAGE AREA HDCP
 ACCESSIBLE, AND CAN IT BE ACCESSED FROM
 STORAGE AREA?
 4) SHT A-1 PLEASE GIVE OCCUPANCY OF EACH
 TENANT SPACE.
 5) SHT A-1 TOILET ROOM DETAIL, PLEASE
 INDICATE THAT W/C SHALL BE 1'6" TO
 CENTER AND LAV SHALL BE 1'3" TO CENTER.
 6) SHT ME-2 SANT RISER ISOMETRIC SHOWS
 2" AT TIE IN TO EXISTING. MINIMUM 4" IS
 REQUIRED FOR STANDARD CODE AND 3" FOR
 FLA. BUILDING CODE 2001.
 7) SHT ME-2 PLEASE PROVIDE A WATER RISER
 DIAGRAM. SHOW LOCATION OF WATER HAMMER
 ARRESTORS NEAR FIXTURES NOT AT TOP OF
 DROPS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377