Plan Review Details - Permit 02011555
Plan Review Stops For Permit 02011555
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-08 Cont ID  
Sent By btrobaug Date 2002-07-08 Time 13:13 Rev Time 0.00
Received By btrobaug Date 2002-07-08 Time 12:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-02-13 Cont ID  
Sent By btrobaug Date 2002-02-13 Time 17:17 Rev Time 0.00
Received By btrobaug Date 2002-02-13 Time 17:02 Sent To R
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-05 Cont ID  
Sent By pkrauss Date 2002-04-05 Time 11:31 Rev Time 0.30
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By hmoser Date 2002-02-11 Time 18:00 Rev Time 0.33
Received By hmoser Date 2002-02-11 Time 18:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-10-08 Cont ID  
Sent By kstevens Date 2002-10-08 Time 11:23 Rev Time 0.00
Received By kstevens Date 2002-10-08 Time 11:23 Sent To  
Notes
2002-10-08 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-10-02 Cont ID  
Sent By pschmitz Date 2002-10-02 Time 14:25 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-10-02 00:00:0010-2-02 REVISION DENIED, LT IN GARAGE.PS

Review Stop P PLUMBING
Rev No 1 Status P Date   Cont ID  
Sent By jleech Date 2002-02-09 Time 08:18 Rev Time 0.33
Received By jleech Date 2002-02-09 Time 08:18 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-04-05 Cont ID  
Sent By btrobaug Date 2002-07-08 Time 13:13 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-04-05 00:00:00PROVISO:SAME COMMENTS AS PERMIT 02011562
 4-5-02 RM

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-03-14 Cont ID  
Sent By btrobaug Date 2002-02-13 Time 17:17 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-03-14 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) STRUCTURE IS LOCATED IN AN AO FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 3)PROVIDE SOIL BEARING TEST PER 1804.2.2
 OF CITY OF WPB AMENDMENTS TO 1997 SBC.
  
 4)THE PLANS SUBMITTED ARE MISSING SHEETS
 7 AND 9.
  
 5) THE NOTE ON SHEET 2 REFERS TO TYPICAL
 FOOTING DWG.A8, WHICH IS NOT ON PLANS.
 PROVIDE TYPICAL FOOTING DETAILS.
  
 6) REVIEW THE VERTICAL REINFORCEMENT AT
 THE 2 HOUR PARTY WALL. SEVERAL APPEAR TO
 BE MISSING. PLEASE CORRECT.
  
 7) PROVIDE EXTERIOR WINDOW AND DOOR BUCK
 FASTENING DETAILS.
  
 8) PROVIDE A TYPICAL WALL SECTION.
  
 9) INDICATE ROOF SHEATHING TO BE USED
 AND FASTENING SCHEDULE.
  
 10) PROVIDE SITE SPECIFIC PRODUCT
 APPROVAL FORMS TO ACCOMPANY THE
 ENGINEERED DRAWINGS FOR THE FIXED GLASS
 WINDOWS AND THE MULLIONS. ENGINEER NEEDS
 TO INDICATE THE THICKNESS OF THE
 ALUMINUM IN THE 1"X4" ALUMINUM TUBES
 SPECIFIED ON THE FIXED GLASS DRAWINGS.
  
 11) THE SITE SPECIFIC PRODUCT APPROVAL
 FORMS ARE REQUIRED TO HAVE THE EMBOSSED
 SEAL,DATE AND WET SIGNATURE OF THE
 DESIGNER OF RECORD FOR THE STRUCTURE, IN
 ADDITION TO THE ENGINEER CERTIFYING THE
 PRODUCT. THE ENGINEER CERTIFYING THE
 PRODUCT IS REQUIRED TO LEGIBLY INDICATE
 THEIR NAME, ADDRESS AND NUMBER ON THE
 FORMS, AS WELL AS, EACH SHEET OF THE
 DRAWINGS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-07 Cont ID  
Sent By sgraham Date 2002-02-07 Time 09:53 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***