Plan Review Details - Permit 02011492
Plan Review Stops For Permit 02011492
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-31 Cont ID  
Sent By dpalmer Date 2002-01-31 Time 09:17 Rev Time 0.00
Received By dpalmer Date 2002-01-31 Time 09:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-30 Cont ID  
Sent By dpalmer Date 2002-01-30 Time 07:43 Rev Time 0.00
Received By dpalmer Date 2002-01-30 Time 07:43 Sent To  
Notes
2002-01-30 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 ALSO MISSING AN EQUIPMENT GROUNDING
 CONDUCTOR BETWEEN MAIN AND PANEL.
 CAN CE DRAWN IN/REDLINED. 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372