Plan Review Details - Permit 02011426
Plan Review Stops For Permit 02011426
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-02-07 Cont ID  
Sent By kstevens Date 2002-02-05 Time 17:46 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-12 Cont ID  
Sent By btrobaug Date 2002-02-12 Time 08:51 Rev Time 0.00
Received By btrobaug Date 2002-02-12 Time 07:38 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-30 Cont ID  
Sent By btrobaug Date 2002-01-30 Time 11:53 Rev Time 0.50
Received By btrobaug Date 2002-01-30 Time 11:12 Sent To ENG
Notes
2002-01-30 00:00:00********************UNSAT!**************
 PLEASE PR0VIDE THE FOLLOWING AND
 RESUBMIT:
  
 1) NAMEPLATE RATING OF PUMP.
 2) LOCATION OF PANEL FEEDING PUMP.
 3) LOAD CALCULATION OF SUPPLYING PANEL.
 4) CONDUIT AND WIRE SIZE OF PUMP FEEDER.
 5) LENGTH OF FEEDER RUN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT.8392

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-01-30 Cont ID  
Sent By btrobaug Date 2002-01-30 Time 11:53 Rev Time 0.00
Received By mamini Date 2002-01-30 Time 14:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2002-01-31 Cont ID  
Sent By mcarsill Date 2002-01-31 Time 14:24 Rev Time 0.00
Received By mcarsill Date 2002-01-31 Time 14:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-02-04 Cont ID  
Sent By pkrauss Date 2002-02-04 Time 15:44 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-02-05 Cont ID  
Sent By btrobaug Date 2002-02-12 Time 08:51 Rev Time 0.50
Received By kstevens Date 2002-02-05 Time 17:41 Sent To B
Notes
2002-02-05 00:00:00MANUFACTURE/ENGINEER INFORMATION SUBMIT-
 TED SEPARATE 1-2902 KS

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-03 Cont ID  
Sent By pschmitz Date 2002-02-03 Time 13:43 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-02-03 00:00:00PLUMBING PLAN REVIEW,DENIED. PES
 SPC-94 SEC 104.3 PROVIDE MANFACTURE
 SPECIFICATIONS LISTING FOR REVIEW.
 END OF COMMENTSPAUL SCHMITZ
 561-659-8096X8233

Review Stop Z ZONING
Rev No 1 Status N Date 2002-02-12 Cont ID  
Sent By btrobaug Date 2002-02-12 Time 14:33 Rev Time 0.00
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***